JOHNSON CONTROLS
300
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
Yorktalk 2 Communications
Received Data (Control Data)
The unit receives eight data values from the Micro-
Gateway or E-Link. The first four are analog values
and the last four are digital values. These eight data
values are used as control parameters when in RE-
MOTE mode. When the unit is in LOCAL mode, these
eight values are ignored. If the unit receives no valid
YorkTalk 2 transmission for 5 minutes it will revert
back to all local control values.
“Yorktalk 2 Communications Data Map” lists the con-
trol parameters. These values are found under feature
54 in the MicroGateway or E-Link.
Transmitted Data
After receiving a valid transmission from the Micro-
Gateway or E-Link, the unit will transmit either op-
erational data or history buffer data depending on the
“History Buffer Request” on ENG PAGE 10. Data
must be transmitted for every page under feature 54.
If there is no value to be sent to a particular page, a
zero will be sent.
“Yorktalk 2
Communications Data Map” shows the data values and
page listings for this unit.
The latest point map information is listed
on the Johnson Controls Equipment In-
tegration website.
Summary of Contents for YCIV Series
Page 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...