FORM 150.44-NM4
9
YORK INTERNATIONAL
WEIGHT DISTRIB.
WATER CONN.
MODEL YCA
(LBS.)
INLET/OUTLET
A
B
C
D
DIA. (IN.)
Z33BA3
791
791 1707
1707
4
Z44BA3
858
858 1811
1811
4
Z74BB3
931
931 1948
1948
4
Z77CB3
935
935 2011
2011
6
Z88DB3
977
977 2079
2079
6
Z88DB3
977
977 2079
2079
6
1. CLEARANCES Recommended YORK required clearances to
prevent condenser air recirculation and faulty operation of units
are as follows:
Side to wall - 5'0" ** / Rear to wall - 8'0" ** / Front to wall -
8'0" ** / Top - 50'0" / Distance between adjacent units - 12'0"
* No more than one wall can be higher than the top of the unit.
Failure to heed recommended clearances may result in re-
duced system performance, nuisance shutdowns and ser-
vicing problems.
The area within the clearances shown above and area under the
unit must be kept clear of all obstructions that would impede free
air flow to the unit. In installations where winter operation is in-
tended and snow accumulations are expected, additional unit
height must be provided to insure full air flow.
2. Panel bottom to be punched in field to accommodate power wir-
ing conduit.
3. Use of isolators (optional) will increase height of unit approxi-
mately 6".
4. Drawings not to scale and are for planning purposes only. Refer
to QMS drawings for most up-to-date dimensions.
5. Be sure to review WARNINGS on page 2 prior to installation.
CAUTION
FAILURE TO HEED FOLLOWING MINIMUM RECOM-
MENDED CLEARANCES MAY RESULT IN REDUCED
SYSTEM PERFORMANCE, NUISANCE SHUT-
DOWNS, AND SERVICE PROBLEMS.
NOTES
CHILLER
Y
X
Z33BA3
7'2"
1'2-1/8"
Z44BA3
7'2"
1'2-1/8"
Z74BB3
7'2"
1'2-1/8"
Z77CB3
7'0"
1'3-1/8"
Z88DB3
7'1"
1'3-3/4"
DIMENSIONS
LD01982
LD01983
LD01984