YORK INTERNATIONAL
78
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/91
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP
65.0 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
50 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
143 PSIG
OIL PRESSURE
75
PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
0 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
80 PSIG
OIL PRESSURE
1
PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
* = HOLIDAY
SUN
START=06:00AM
STOP=11:00PM
MON
START=06:00AM
STOP=11:00PM
TUE
START=06:00AM
STOP=11:00PM
WED
START=06:00AM
STOP=11:00PM
THU
START=06:00AM
STOP=11:00PM
FRI
START=06:00AM
STOP=11:00PM
SAT
START=06:00AM
STOP=11:00PM
HOL
START=00:00AM
STOP=00:00AM
FIG. 31
PRINT-OUT
The WEIGH-TRONIX IMP-24 Model 2600 printer can
be purchased from:
Weigh-Tronix
2320 Airport Blvd.
Santa Rosa, CA 95402
Phone: 1-800-358-9110 or 1-707-527-5555
(International Orders Only)
NOTE: The printout is made to be universal to all types
of chillers, both air and water cooled with or
without options. Items may be indicated on the
printout which may not be present on the chiller.
Installation Limitations
The following limitations must be adhered to. Failure to
do so may result in improper printer and/or chiller op-
eration.
1. The printer option is adaptable to all versions and
revisions of Microprocessor Boards and EPROMs.
No modifications are necessary to the panel.
2. Maximum cable length between the printer and the
Microprocessor Board is 25 feet. Twisted pair
shielded cable is required.
3. The printer must be supplied a 115 VAC source.
4. The printer may be left connected to the micro panel.
Parts
The following parts are required:
1. Weigh-Tronix IMP-24, Model 2600 printer.
2. 2.25" wide desk top calculator paper.
3. 25 ft. Twisted Pair Shielded Cable (minimum 3 con-
ductor), #18 AWG Stranded, 300V min. insulation.
4. (1 ea.) 25-pin Cannon connector and shell. Connec-
tor: Cannon P/N DB-25P or equivalent. Shell: Can-
non P/N DB-C2-J9.
Assembly and Wiring
All components should be assembled and wired as fol-
lows in Fig. 42. Strip the outside insulation back sev-
eral inches and individual wires about 3/8" to connect
the cable at the
Micro Logic Board
. Connect the shield
of the cable as shown on the
Micro Logic Board
. Do
not connect at the printer end of the cable.
Printer Configuration
2 Switches on the printer must be properly configured.
Remove the paper roll to access these switches. Place
the switches in the following position:
SW. 1 OFF
SW. 2 ON
Obtaining a Print Out
A printout of current operating data may be obtained
by pressing the OPER DATA key. A snap-shot will be
taken by the micro of current operating conditions.