FORM 150.44-NM4
33
YORK INTERNATIONAL
GENERAL
The ENTRY key allows the user to change programmed
numerical values such as chiller setpoints, cut-outs,
clock, etc.
Numerical Keypad
The NUMERICAL keypad provides all keys needed to
program numerical values as required.
The * Key is used to designate holidays when pro-
gramming special start and stop times for designated
holidays in the SET SCHEDULE/HOLIDAY display.
The +/- key allows programming -°C setpoints and
cut-outs in the metric display mode.
Enter Key
The ENTER key must be pushed after any change is
made to setpoints, cut-outs or the system clock. Press-
ing this key tells the micro to accept the new values
into memory.
If this is not done, the new numbers entered will be lost
and the original values will be returned.
The ENTER key is also used to scroll through avail-
able data after any one of the following keys is pressed:
PROGRAM
SET SCHEDULE/HOLIDAY
OPER DATA
HISTORY
Cancel Key
The CANCEL key allows the user to change errors in
the data being programmed into memory.
When the CANCEL key is pressed, any data which has
been keyed in, but not entered, will be erased. The
original values will re-appear on the display and the
cursor will return to the first character to be programmed
in the display message.
AM/PM Key
The AM/PM key allows the user to change AM/PM while
programming the correct time in the SET TIME display.
The same key allows changing the AM/PM schedule
while programming daily chiller start and stop times in
the SET SCHEDULE/HOLIDAY display.
Advance Day Key
The ADVANCE DAY key advances the day when the
SET TIME display is being programmed. The day is
normally advanced to correspond to the current day of
the week. The day will advance a day at a time, each
time the key is pressed.
1
2
3
4
5
6
7
8
9
*
0
+/-
ENTER
CANCEL
AM/PM
ADVANCE
DAY
26572A
ENTRY KEYS
ENTRY
KEYS