240
JOHNSON CONTROLS
FORM 201.21-NM2 (616)
UNIT SETUP MODE
MICRO PANEL
Unit Setup Mode will allow the programming all of the
programmable values that the user should never change.
These will either be programmed at the factory or by
service personnel on the job.
TABLE 19 - UNIT SETUP PROGRAMMABLE VALUES
SETUP MODE VALUE
PRAGRAMMABLE RANGE
DEFAULT
Sys 1 Number of Cond Fans
4 to 6
6
Sys 2 Number of Cond Fans
4 to 6
6
Sys 3 Number of Cond Fans
4 to 6
6
Sys 4 Number of Cond Fans
4 to 6
6
Compressor 1 Operating hours
0 to 99,999
0
Compressor 2 Operating hours
0 to 99,999
0
Compressor 3 Operating hours
0 to 99,999
0
Compressor 4 Operating hours
0 to 99,999
0
Compressor 1 Starts
0 to 99,999
0
Compressor 2 Starts
0 to 99,999
0
Compressor 3 Starts
0 to 99,999
0
Compressor 4 Starts
0 to 99,999
0
Clear History Buffers
Yes/ No
-
Remote Temp Reset Option
Disabled/Enabled
Disabled
Remote Current Limit Option
Disabled/Enabled
Disabled
Sound Limit Option
Disabled/Enabled
Disabled
Remote Inputs Service Time
5 Min - 60 Min
15 Min
Sys 1 Motor Sensor to Ignore
See Below
None
Sys 2 Motor Sensor to Ignore
See Below
None
Sys 3 Motor Sensor to Ignore
See Below
None
Sys 4 Motor Sensor to Ignore
See Below
None
The following messages will be displayed for the Unit
Setup Mode in the order they appear. The first group
of displays relates to setup parameters that relate to unit
configuration and factory setpoints.
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 1 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 2 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 3 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 4 NUMBER OF COND FANS
= X
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 1 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 2 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 3 OPERATING HOURS
= XXXXX
SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX
COMP 4 OPERATING HOURS
= XXXXX
This mode may be entered by pressing the PROGRAM
key, entering the password 4245, and pressing the
(ENTER) key. TABLE 19 lists the values that can be
programmed in this mode. Details relating to the actual
message follow the table.
Summary of Contents for YCAV0569
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 51: ...51 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 53: ...53 JOHNSON CONTROLS FORM 201 21 NM2 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 60: ...60 JOHNSON CONTROLS FORM 201 21 NM2 616 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 91: ...91 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 179: ...179 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This Page Intentionally Left Blank...
Page 201: ...201 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 8...
Page 221: ...221 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...
Page 249: ...249 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...