TECHNICAL DATA
VOLTAGE CODE
-50 = 380/415-3-50
ELECTRICAL NOTES
LEGEND
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RATED LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
1. As standard, all units have single point power connection. Contact factory for information regarding dual
point power units.
2. Maximum Inverse Time Ciruit Breaker - 250% of the rated input current of the drive per NEC 430.52 (C1). ]
3. Maximum Dual Element (Time Delay) Fuse - 225% of the rated input current of the drive per NEC 430.52
(C1).
4. MCA - Minimum Circuit Ampacity - 125% of the largest compressor RLA plus 100% of the remaining
compressor RLA’s plus the sum of all condenser fan FLA’s per NEC 440.33.
5. Recommended time delay or dual element fuse size - 150%of the largest compressor RLA plus 100% of the
remaining compressor RLA’s plus the sum of all condenser fan FLA’s.
6. RLA - Rated Load Amps - rated in accordance with UL standard 1995 at 400VAC.
7. Local codes may take precedence.
8. Control KVA includes operational controls and evaporator heaters.
9. System inrush current is less than RLA due to the use of York Variable-speed Drive technology. Typical
Compressor Starting Current ( first four seconds of startup):
Rated Voltage
Typical Starting Current per Compressor
400/50/3
28A
10. Optional Compressor Service Disconnect switch is available on all units.
11. Voltage Utilization Range:
Rated Voltage
Utilization Range
380-415/50/3
360-440
12. Condenser fan FLA applies to both low sound and ultra quiet fans.
NOTES:
1. U.L. Label is provided on 50 Hz units for these electrical wiring configurations.
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with
local codes. Group Rated breaker must be HACR type for cUL machines.
Summary of Contents for YCAV0569
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 51: ...51 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 53: ...53 JOHNSON CONTROLS FORM 201 21 NM2 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 60: ...60 JOHNSON CONTROLS FORM 201 21 NM2 616 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 91: ...91 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 179: ...179 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This Page Intentionally Left Blank...
Page 201: ...201 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 8...
Page 221: ...221 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...
Page 249: ...249 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...