228
JOHNSON CONTROLS
FORM 201.21-NM2 (616)
MICRO PANEL
MICRO PANEL
PRINT KEY (CON'T)
A sample of the operating data printout is shown below.
The operating data printout is a snapshot of current
system operating conditions when the printout was se-
lected. The sample shows combined printouts of 2, 3,
and 4 circuit units. The actual printout will only show
data for the appropriate chiller type.
Bold italic text below a line of print is
not on the actual printout. Bold italic
text indicates information that may
not be available on all printouts or is
additional information to help explain
the difference in a 2/3 or 4-circuit
printout.
OPERATING DATA PRINTOUT
YORK INTERNATIONAL CORPORATION
LATITUDE SCREW CHILLER
OPERATING DATA
2:04:14 PM 18 JUN 05
SYS 1
NOT RUNNING
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED
LIQUID
W A T E R
LOCAL/REMOTE
MODE
R E M O T E
LEAD/LAG
CONTROL A U T O M A T I C
REMOTE TEMP RESET
D I S A B L E D
REMOTE CURRENT LIMIT
0 T O 1 0 V
REMOTE SOUND LIMIT
4 TO 20 MA
(if Sound Limiting enabled)
LOW AMBIENT CUTOUT
E N A B L E D
PROGRAM VALUES
SUCT PRESS CUTOUT
4 4 P S I G
LOW AMBIENT CUTOUT
2 5 . 0 D E G F
LEAVING LIQUID CUTOUT
3 6 . 0 D E G F
MOTOR CURRENT LIMIT
1 0 0 % F L A
PULLDOWN CURRENT LIMIT
1 0 0 % F L A
PULLDOWN LIMIT TIME
0 MIN
SUCTION SUPERHEAT SETP
1 2 . 0 D E G F
UNIT
ID
NUMBER
0
SOUND
LIMIT
SETPOINT
1 0 0 %
(if Sound Limiting enabled)
UNIT DATA
LEAVING LIQUID TEMP
4 9 . 0 D E G F
RETURN LIQUID TEMP
5 8 . 2 D E G F
TEMP RATE
X X X . X D E G F / M I N
COOLING RANGE
42.0+/-2.0 DEGF
REMOTE
SETPOINT 4 4 . 0
D E G F
AMBIENT AIR TEMP
7 4 . 8 D E G F
LEAD
SYSTEM
SYS
2
FLOW
SWITCH
O N
EVAPORATOR
PUMP
RUN
O N
EVAPORATOR
HEATER
O F F
ACTIVE
REMOTE
CONTROL
N O N E
O P E R A T I N G H O U R S 1 = X X X X X , 2 = X X X X X
3=XXXXX
(3 circuit)
3=XXXXX,
4=XXXXX
START
COUNTER
1=XXXXX,
2=XXXXX
3=XXXXX
(3 circuit)
3=XXXXX,
4=XXXXX
(4 circuit)
SOFTWARE VERSION
C . A C S . X X . 0 0
VSD DATA
ACTUAL
FREQUENCY X X X . X
H Z
COMMAND
FREQUENCY
X X X . X
H Z
DC
BUS
VOLTAGE
X X X
V D C
(2 circuit & 3 circuit)
DC BUS VOLTAGES
XXX XXX VDC
(4 circuit)
INTERNAL AMBIENT TEMP
XXX.X DEGF
COOLING
SYSTEM
STATUS
X X X
BASEPLATE TEMPS
XXX XXX DEGF
PRECHARGE
SIGNAL X X X
(2 circuit & 3 circuit)
PRECHARGE
SIGNALS
X X X
X X X
(4 circuit)
MOTOR OVERLOADS 1/2
XXX XXX AMPS
MOTOR OVERLOADS 3/4
XXX XXX AMPS
(3 circuit & 4 circuit)
SOFTWARE
VERSION C.VSD.XX.00
SYSTEM 1 DATA
COMPRESSOR
STATUS
O F F
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
0 AMPS
0 % F L A
SUCTION
PRESSURE 1 2 5
P S I G
DISCHARGE
PRESSURE
1 3 1
P S I G
OIL
PRESSURE
1 3 0
P S I G
SUCTION
TEMPERATURE
6 8 . 4
D E G F
DISCHARGE
TEMPERATURE
6 8 . 8
D E G F
OIL
TEMPERATURE 6 8 . 8
D E G F
SAT SUCTION TEMP
7 1 . 8 D E G F
SUCTION SUPERHEAT
3 . 4 D E G F
SAT DISCHARGE TEMP
7 4 . 5 D E G F
DISCHARGE SUPERHEAT
6 . 3 D E G F
MOTOR
TMP
XXX.X XXX.X XXX.X
D E G F
COMPRESSOR
SPEED XXX.X
%
ECONOMIZER
SOLENOID
O F F
FLASH
TANK
LEVEL XXX.X
%
FEED VALVE % OPEN
XXX.X %
DRAIN VALVE % OPEN
XXX.X %
CONDENSER
FANS
ON
0
COMPRESSOR
HEATER
O N
RUN
PERMISSIVE
O N
VSD
RUN
RELAY
O F F
VSD SOFTWARE RUN SIGNAL
O F F
SYSTEM 2 DATA
COMPRESSOR
STATUS
O N
RUN TIME
0-0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS
8 7 % F L A
SUCTION
PRESSURE 5 7
P S I G
DISCHARGE
PRESSURE
2 3 3
P S I G
OIL
PRESSURE
2 1 8
P S I G
SUCTION
TEMPERATURE
4 2 . 9
D E G F
DISCHARGE
TEMPERATURE
145.5
DEGF
OIL
TEMPERATURE 102.8
DEGF
SAT SUCTION TEMP
3 1 . 7 D E G F
SUCTION
SUPERHEAT
1 1 . 2
D E G F
SAT DISCHARGE TEMP
112.1 DEGF
DISCHARGE
SUPERHEAT
3 3 . 4
D E G F
Summary of Contents for YCAV0569
Page 43: ...43 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 51: ...51 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 53: ...53 JOHNSON CONTROLS FORM 201 21 NM2 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Page 60: ...60 JOHNSON CONTROLS FORM 201 21 NM2 616 LOCATION LABEL LD10519 TECHNICAL DATA...
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 91: ...91 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Page 179: ...179 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This Page Intentionally Left Blank...
Page 201: ...201 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 8...
Page 221: ...221 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...
Page 249: ...249 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...