
60
JOHNSON CONTROLS
ELECTRICAL NOTES
NOTES
(for pages 50 - 56)
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the
system #1 MCA values in the YCAS Tables: -17, add 10A ; -28, add 9A; -40, add 5A; -46, add 4A; -58, add 3A.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). Min
-
imum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2. Minimum
circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan motor
FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3) indicate
the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be determined
based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the National
Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10. Two-compressor machines with Single-Point power connection, and equipped with Star-Delta compressor motor start, must also include
factory provided circuit breakers in each motor control center. All 3 & 4 compressor machines equipped with Star-Delta compressor motor
start must also include factory provided circuit breakers in each motor control center.
11. Consult factory for Electrical Data on units equipped with “High Static Fan” Option. 60 Hz High Static Fans are 3.8 kW each, 50 Hz 3.5 kW
each.
12. FLA for “Low Noise Fan” motors: 200V = 8.0A, 230V = 7.8A, 380V = 4.4A, 460V = 3.6A, 575V = 2.9A, 380
V
/50 Hz = 4.1A.
13. Group Rated breaker must be HACR type for cU.L. Machines.
NOTES & LEGEND
(for pages 50 - 56)
LEGEND
ACR-LINE
ACROSS THE LINE START
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RUNNING LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
Y-
∆
WYE-DELTA START
X-LRA
ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
Y-LRA
WYE-DELTA INRUSH LOCKED ROTOR AMPS
VOLTAGE CODE
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
Technical Data
NO. OF
CONTROL
MCA
MAX DUAL
NON-FUSED
COMPRESSORS
POWER
(MAX LOAD
ELEMENT
DISCONNECT
SUPPLY
CURRENT)
FUSE SIZE
SWITCH SIZE
2
115V-1Ø
20A
20A
20A
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)
Summary of Contents for YCAS 0138EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...