152
JOHNSON CONTROLS
This message shows the Run Time logged on the system
since the last compressor start, in Days (D), Hours (H),
Minutes (M), and Seconds (S).
This message indicates the compressor motor current in
as a percentage of Full Load Amps.
This message shows the system differential oil pressure
at the time of the fault.
This message indicates the system oil line temperature
at the time of the fault.
These messages indicate compressor suction gas satura-
tion temperature and superheat at the time of the fault.
This message indicate compressor discharge gas satura-
tion temperature and superheat at the time of the fault.
S Y S # M O T O R C U R R E N T
7 8
% F L A
S Y S # O I L = 1 5 4 . 8 ° F
S T = 9 . 0 D T = 1 2 3 . 7 ° F
S Y S # O I L = 6 5 P S I G
S P = 6 2 D P = 2 7 1 P S I G
S # S A T S U C T = 3 4 . 7 ° F
S U C T S H E A T = - 6 . 5 ° F
S # S A T D S C H = 1 2 9 ° F
D S C H S H E A T < - 8 . 4 ° F
S Y S # S V S T E P = 4 0
S Y S # C O O L E R I N L E T
R E F R I G T E M P = 2 8 . 2 ° F
S Y S # L L S V I S O
N
E C O N T X V S O L I S O F F
S Y S # F A N S T A G E 3
C O M P H E A T E R I S O F F
S Y S # R U N T I M E
1 - 3 - 4 8 - 1 7 D - H - M - S
Micro Panel Contents
This message indicates the compressor slide valve po-
sition at the time of the fault. 0 steps equals minimum
capacity and 75 steps equals fully loaded.
This message, which is only displayed if the unit is in
R-407c mode, indicates the refrigerant temperature at
the inlet of the cooler.
This message indicates the Liquid Line Solenoid Valve
and the economizer Thermal Expansion Valve Solenoid
Valve position: ON = Energized / OFF = De-Energized
(OFF) at the time of the fault.
This message indicates the stage of condenser fan op-
eration on the system and the status of the compressor
heater at the time of the fault. See Section 8.4 for details
of fan staging.
Summary of Contents for YCAS 0138EB
Page 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Page 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Page 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Page 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Page 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Page 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Page 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Page 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Page 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Page 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Page 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Page 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Page 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...