UNIT PARAMETERS (CONT’D)
NO.
Short Name
(BACnet Object Name)
Function Code
Register
Address
Note
39
EVA heater
3
bit4: 1-ON, 1-OFF
40
Ckt1 oil heater
3
bit5: 1-ON, 1-OFF
41
Fault Output
3
bit6: 1-ON, 1-OFF
42
Chiller Pump
3
bit7: 1-ON, 1-OFF
43
Water Heater
3
bit8: 1-ON, 1-OFF
44
VSD fan
3
bit9: 1-ON, 1-OFF
45
Ckt2 Fan Motor
3
bit10: 1-ON, 1-OFF
46
Ckt2 Fan Motor speed
3
bit11: 1-ON, 1-OFF
47
Ckt2 Comp1
3
bit12: 1-ON, 1-OFF
48
Ckt2 Comp2
3
bit13: 1-ON, 1-OFF
49
Ckt1 FWV
3
bit14: 1-ON, 1-OFF
50
Ckt2 FWV
3
bit15: 1-ON, 1-OFF
51
Ckt1 EEV
3
1057
52
Ckt2 EEV
3
1058
53
Ckt1 Fan Speed
3
1065
54
Ckt2 Fan Speed
3
1066
55
Dial switch Status
3
1073
56
VSD Info
3
1075-1090
16 addresses for VSD Info
57
Fault Word 1
3
1155
Modular fault codes, 128 bits
58
Fault Word 2
3
1156
59
Fault Word 3
3
1157
60
Fault Word 4
3
1158
61
Fault Word 5
3
1159
62
Fault Word 6
3
1160
63
Fault Word 7
3
1161
64
Fault Word 8
3
1162
65
3
1164-1199
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz