Engineering Guide Speci

fi

 cations cont.

Affinity & Affinity Advanced Series

1 - 6 Tons 60Hz

SD2500AK6      11/22 

58 

Page _____ of _____

OFF-HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO 
blower switch, and indicating display shall be provided. The 
thermostat shall display in °F or °C. The thermostat shall provide 
real time energy consumption data of the unit.

Communicating Color Touchscreen Thermostat
(field-installed)

A color touchscreen communicating auto-changeover electronic 
digital thermostat shall be provided. The thermostat shall 
offer variable speed heating and cooling staging with precise 
temperature control. An OFF-HEAT-AUTO-COOL-EMERG system 
switch, OFF-AUTO blower switch, and indicating display shall be 
provided. The thermostat shall display in °F or °C. The thermostat 
shall provide real time and historical energy consumption data of 
the unit.

Electronic Air Cleaner (field-installed)

A 1 in. [25 mm] electronic air cleaner, cleanable 97% efficiency at 
0.3 microns and larger, shall be provided in lieu of the standard 
throwaway filter. The initial pressure drop across the filter shall not 
exceed 0.2 in. w.g. at 300 fpm force velocity.

Electrostatic Air Cleaner (field-installed)

A 1 in. [25 mm] electrostatic air cleaner, cleanable 90% efficiency, 
shall be provided in lieu of the standard throwaway filter. The initial 
pressure drop across the filter shall not exceed 0.15 in. w.g. at 300 
fpm force velocity.

External Sump Alarm Sensors for Aurora Controls

The sensor can be added to any Aurora Advanced Control System 
(including both ABC and AXB) to monitor a sump pump. The sen-
sor can be connected to the Aurora Home Automation inputs (HA-1 
or HA-2) of the AXB board. These will each display an E23 and 
E24 code respectively when the alarm is active and when Sym-
phony/AWL is installed will also produce text/e-mail notifications.

• 

This sensor provides a relay closure that can be used to trip a 
fault when moisture is present. This can be used as a primary 
sump alarm or simply a wet basement or signal a blown 
washing machine hose.

AlpinePure MERV 13 Filter (field installed)

A 2 in. [50 mm] thick MERV 13 filter shall be provided in lieu of the 
standard filter and fits the factory filter rack. The filter maintains 
MERV 13 rating in full ASHRAE 52.2 independent testing as 
required for LEED

®

 certification. Helps fulfill a full credit under the 

LEED rating system.

AlpinePure HEPA Filter (field installed)

For the ultimate in air filtration, the AlpinePure Series HEPA filter 
captures 99.97% of all particles down to 0.30 microns in size.

AlpinePure Drain Pan Treatment (field installed)

Provides dependable, sustained time-release protection from slime 
build-up and foul smelling odors in the drain pan. Also adds a light, 
pleasant scent to the air.

Earth Loop Flow Center (field-installed)

A self-contained module shall provide all liquid flow, fill and 
connection requirements for ground source closed loop systems 
up to 20 gpm. The pumps shall be wired to a power block located 
in the nearest unit. The heat pump units shall contain low voltage 
pump linking control so that two units may share one flow center.

Auxiliary Heater (field-installed)

An electric resistance heater shall provide supplemental and/or 
emergency heating capability. Vertical units shall have the control 
panel and resistance heater coil assembly mounted internally. For 
horizontal units, the control panel shall be mounted internally while 
the resistance heater coil assembly shall be mounted externally. A 
low voltage plug shall be provided in each unit for quick auxiliary 
heat connection. The heater shall operate in sequenced stages 
as controlled by the unit’s microprocessor. The heater shall feed 
line voltage power to the unit blower and transformer to provide 
emergency heat capability in the event of an open compressor 
circuit breaker.

Summary of Contents for YAFS012

Page 1: ...NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www york geothermal com Additional rating information can found at www ahr...

Page 2: ...tory Installed Pump No IntelliStart1 3 No HWG IntelliStart1 4 HWG with Factory Installed Pump IntelliStart1 Vintage Factory Use Only Controls D Aurora Performance and Refrigeration Package Air Coil Op...

Page 3: ...2 000 6 1 22 200 29 7 17 500 4 9 21 000 26 0 16 400 4 5 038 Full 9 1300 36 500 17 0 43 300 5 5 40 000 24 4 35 000 4 9 38 200 19 7 28 500 4 2 038 Part 8 1150 26 500 19 0 31 300 6 4 29 900 32 1 24 900 5...

Page 4: ...on AHRI ISO 13256 1 Performance Ratings cont Affinity Affinity Advanced Series 1 6 Tons 60Hz SD2500AK6 11 22 4 Page _____ of _____ Cooling capacities based upon 80 6 F DB 66 2 F WB entering air temper...

Page 5: ...es 1 6 Tons 60Hz SD2500AK6 11 22 5 Page _____ of _____ Energy Star Rating Criteria In order for water source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirem...

Page 6: ...5 34 0 41 7 24 4 17 5 23 9 29 7 16 0 1 8 35 6 35 6 6 9 5 8 55 9 45 7 5 1 022 030 in 22 5 26 5 48 5 2 0 7 0 13 5 16 5 10 2 1 in Swivel 1 2 in Female 9 5 12 1 14 3 6 1 0 8 14 0 14 0 4 4 1 7 22 2 26 0 1...

Page 7: ...ate Supply Width Supply Depth Return Depth Return Height 022 030 in 22 5 26 5 52 5 35 3 40 2 46 7 49 7 3 6 1 in Swivel 1 2 in Female 41 9 43 6 45 1 8 6 6 0 9 3 10 5 1 0 2 2 22 2 26 0 5 6 cm 57 2 67 3...

Page 8: ...ate Power Supply Ext Pump Low Voltage Supply Width Supply Depth Return Depth Return Height 042 049 in 25 6 31 6 54 4 2 3 7 3 15 9 18 9 10 6 1 Swivel 1 2 female 9 5 12 1 14 3 13 3 13 6 39 4 9 1 8 1 1 7...

Page 9: ...11 7 1 8 10 5 9 5 8 2 2 2 21 8 16 5 1 5 cm 57 2 134 6 49 0 5 8 13 5 35 1 42 7 20 3 17 5 24 1 29 7 4 6 26 7 24 1 20 8 5 6 55 4 41 9 3 8 022 030 in 22 5 63 0 19 3 2 0 7 0 13 5 16 5 0 8 1 in Swivel 1 2...

Page 10: ...le Sweat I D in mm n a 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 0 35 1 3 0 40 1 5 0 7 2 6 1 0 3 8 1 3 4 9 1 3 4 9 1 6 6 1 1 6 6 1 2 3 8 7...

Page 11: ...279 x 254 5 Spd ECM 9 x 7 229 x 178 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 Coax and Water Piping Water Connections Size Swivel in mm 1 25 4 1 25 4 1 25 4 1 25 4 1 25...

Page 12: ...e 34 7 40 0 53 3 60 0 60 60 60 60 60 60 EAL H 15A Single 52 0 60 0 75 0 85 0 80 90 80 90 70 100 L1 L2 34 7 40 0 53 3 60 0 60 60 60 60 60 60 L3 L4 17 3 20 0 21 7 25 0 25 25 25 25 20 30 EAL H 20A Single...

Page 13: ...14 1 73 0 26 0 0 4 5 4 4 0 23 9 27 4 40 042 208 230 60 1 187 253 26 0 16 6 79 0 28 0 0 4 5 4 4 0 26 4 30 6 45 048 208 230 60 1 187 253 31 0 19 8 109 0 38 0 0 4 5 4 4 0 29 6 34 6 50 060 208 230 60 1 1...

Page 14: ...LA LRA LRA 026 208 230 60 1 187 253 18 2 11 6 58 3 21 0 0 4 5 4 4 0 21 4 24 4 35 038 208 230 60 1 187 253 23 8 15 2 83 0 30 0 0 4 5 4 4 0 25 0 28 8 40 049 208 230 60 1 187 253 33 0 21 1 104 0 37 0 0 4...

Page 15: ...0 75 800 950 1100 1300 1500 1750 1950 2100 2300 2325 G L H Aux 070 0 75 800 950 1100 1300 1500 1750 1950 2100 2300 2325 G L H Aux Factory settings are at recommended G L H Aux speed settings L H setti...

Page 16: ...2 Med Low 2 Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 048 High 5 11 x 10 1 1934 1910 1886 18...

Page 17: ...1659 1617 Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med Low 2 Y1 1575 1560 1540 1...

Page 18: ...r Performance Data cont Affinity Affinity Advanced Series 1 6 Tons 60Hz SD2500AK6 11 22 18 Page _____ of _____ Unit with Standard PSC Motor Model Motor Spd Blower Size Motor HP Airflow cfm at External...

Page 19: ...6 66 2 27 19 68 20 0 Max Entering Air db wb 110 83 43 28 3 80 26 7 Water Limits Min Entering Water 30 1 1 20 6 7 Normal Entering Water 50 110 10 43 3 30 70 1 1 Max Entering Water 120 48 9 90 32 2 NOTE...

Page 20: ...987 1 018 475 119 1 017 1 099 1 037 1 022 1 018 0 984 1 025 500 125 1 020 1 132 1 052 1 027 1 022 0 982 1 031 520 130 1 022 1 159 1 064 1 030 1 025 0 979 1 034 5 30 06 Air Flow Corrections Dual Capaci...

Page 21: ...he corrected heating and cooling performance at 30 F and 90 F respectively as well as pressure drop at 30 F for a Affinity Series Single Speed Model 022 ECM The corrected cooling capacity at 90 F woul...

Page 22: ...1 1 0 1 0 0 9 0 8 9 2 3 2 1 2 0 1 9 1 7 12 3 9 3 7 3 4 3 2 3 0 16 6 7 6 3 5 9 5 5 5 1 060 9 2 4 2 2 2 1 2 0 1 8 12 3 9 3 6 3 4 3 2 2 9 15 5 7 5 3 5 0 4 7 4 3 20 9 5 8 9 8 3 7 8 7 2 070 12 3 0 2 8 2 6...

Page 23: ...9 50 1 5 0 3 0 7 10 6 0 83 7 8 92 5 3 75 15 0 10 0 0 66 0 61 17 1 24 6 2 5 1 0 2 3 11 0 0 83 8 2 93 5 3 86 15 2 9 9 0 65 0 56 17 1 27 3 3 5 1 7 3 8 11 4 0 84 8 5 94 4 3 97 15 5 9 9 0 64 0 51 17 2 30...

Page 24: ...94 22 4 20 5 1 1 4 0 2 8 6 6 500 18 8 1 34 14 3 102 9 4 11 2 1 500 18 9 11 4 0 60 0 81 21 7 23 2 1 0 600 19 4 1 37 14 8 98 0 4 16 2 0 600 19 4 12 6 0 65 0 88 22 4 22 2 1 1 5 0 4 1 9 5 500 19 2 1 36 1...

Page 25: ...0 1 4 4 5 1 6 3 7 600 21 2 1 27 16 9 102 7 4 89 2 4 600 24 8 16 1 0 65 0 88 27 8 28 3 1 2 700 21 8 1 26 17 5 98 8 5 05 2 3 700 25 3 17 5 0 69 0 91 28 5 27 7 1 3 6 0 2 6 6 0 600 21 6 1 29 17 2 103 3 4...

Page 26: ...23 7 1 8 6 0 2 4 6 4 700 28 9 1 69 23 1 108 2 5 01 3 3 700 29 6 19 1 0 65 1 16 33 5 25 4 1 6 900 29 7 1 69 23 9 100 6 5 16 3 0 900 30 5 21 3 0 70 1 23 34 7 24 7 1 7 8 0 4 0 10 7 700 29 5 1 71 23 6 10...

Page 27: ...9 4 3 1050 34 5 2 01 27 6 100 4 5 03 4 0 1050 35 4 24 1 0 68 1 40 40 2 25 4 1 9 1250 35 5 2 01 28 6 96 3 5 18 3 7 1250 36 5 27 0 0 74 1 48 41 6 24 7 2 0 9 0 3 1 7 3 1050 35 2 2 04 28 2 101 0 5 06 4 2...

Page 28: ...4 6 1150 39 2 2 39 31 0 101 6 4 80 5 9 1150 43 0 28 0 0 65 1 70 48 8 25 4 2 8 1350 40 0 2 32 32 1 97 4 5 06 5 4 1350 44 7 31 4 0 70 1 78 50 8 25 1 3 0 11 0 3 9 9 1 1150 40 1 2 41 31 9 102 3 4 87 6 1...

Page 29: ...8 1300 51 3 3 28 40 1 106 5 4 59 7 8 1300 50 6 32 4 0 64 2 13 57 9 23 7 3 3 1500 52 3 3 18 41 5 102 3 4 83 7 2 1500 52 6 36 4 0 69 2 24 60 2 23 5 3 6 12 0 3 5 8 2 1300 52 5 3 31 41 2 107 4 4 65 8 0 13...

Page 30: ...9 4 16 50 7 110 0 4 57 9 4 1500 68 7 46 4 0 68 2 93 78 7 23 4 4 4 2000 65 8 4 21 51 4 100 5 4 57 8 7 2000 70 4 49 3 0 70 3 24 81 4 21 7 4 8 15 0 5 2 11 9 1500 66 3 4 23 51 9 110 9 4 59 9 7 1500 69 4 4...

Page 31: ...5 16 59 5 112 0 4 38 11 2 1700 72 6 47 0 0 65 3 22 83 5 22 6 4 8 2200 79 1 5 12 61 6 103 3 4 53 10 3 2200 76 4 53 8 0 70 3 62 88 8 21 1 5 2 18 0 5 3 12 3 1700 78 0 5 20 60 2 112 5 4 39 11 5 1700 73 5...

Page 32: ...6 2 96 3 5 37 1 9 700 23 7 16 0 0 68 0 77 26 4 31 0 1 0 5 0 1 8 4 1 500 20 2 1 08 16 5 107 4 5 50 2 1 500 23 3 14 6 0 63 0 73 25 8 31 8 0 9 700 20 7 1 08 17 0 97 3 5 60 2 0 700 24 0 16 1 0 67 0 75 26...

Page 33: ...8 32 9 22 3 1 6 900 26 8 1 59 21 4 97 6 4 94 2 9 900 29 9 19 9 0 67 1 34 34 4 22 3 1 7 6 0 2 5 5 8 700 27 2 1 63 21 6 105 9 4 90 3 2 700 29 2 18 1 0 62 1 22 33 3 24 0 1 5 900 28 1 1 64 22 5 98 9 5 02...

Page 34: ...1 3 1050 28 8 1 68 23 1 95 4 5 03 2 6 1050 31 3 23 1 0 74 1 06 35 0 29 7 1 4 6 0 1 5 3 6 900 29 3 1 67 23 6 100 1 5 15 3 0 900 30 8 21 0 0 68 1 01 34 2 30 5 1 3 1050 29 9 1 68 24 2 96 4 5 24 2 7 1050...

Page 35: ...1250 40 0 2 48 31 5 99 6 4 72 3 8 1250 41 3 28 7 0 70 2 09 48 4 19 8 2 4 7 0 2 0 4 6 1050 40 5 2 54 31 8 105 7 4 68 4 3 1050 40 4 26 1 0 65 1 90 46 8 21 3 2 2 1250 41 8 2 55 33 1 100 9 4 80 4 0 1250 4...

Page 36: ...50 34 9 2 22 27 3 93 9 4 61 4 8 1350 40 7 27 5 0 67 1 76 46 8 23 1 2 4 8 0 1 8 4 0 1150 36 5 2 29 28 6 99 3 4 67 5 4 1150 40 2 23 5 0 59 1 50 45 3 26 8 2 1 1350 37 9 2 26 30 2 96 0 4 91 5 0 1350 41 4...

Page 37: ...0 3 24 36 9 98 7 4 34 7 0 1550 54 1 34 3 0 63 2 90 64 0 18 7 3 9 9 0 2 2 5 0 1350 50 1 3 34 38 7 104 4 4 40 7 8 1350 53 4 29 3 0 55 2 47 61 8 21 6 3 4 1550 52 1 3 30 40 8 101 1 4 62 7 2 1550 55 0 34 5...

Page 38: ...7 6 2 89 37 8 99 4 4 84 5 7 1500 53 0 33 7 0 64 2 06 60 0 25 8 3 0 10 0 2 4 5 5 1250 48 1 2 96 38 0 105 6 4 76 6 3 1250 51 6 30 1 0 58 1 90 58 1 27 2 2 6 1500 48 9 2 92 38 9 100 2 4 90 5 8 1500 53 2 3...

Page 39: ...0 2 103 2 4 52 8 0 1800 70 0 45 9 0 66 3 51 81 9 19 9 5 1 12 0 3 4 7 8 1500 66 0 4 18 51 7 110 7 4 62 9 0 1500 68 9 42 6 0 62 3 23 79 9 21 3 4 5 1800 67 4 4 24 53 0 104 7 4 66 8 3 1800 70 7 46 3 0 66...

Page 40: ...0 4 02 48 3 103 8 4 52 6 9 1700 59 8 41 3 0 69 2 66 68 9 22 5 3 4 13 0 3 2 7 3 1400 61 1 4 15 47 0 110 4 4 32 7 7 1400 58 3 36 9 0 63 2 46 66 7 23 7 3 0 1700 63 6 4 07 49 7 104 6 4 57 7 1 1700 60 1 4...

Page 41: ...5 4 24 10 3 2200 75 5 52 0 0 69 4 26 90 1 17 7 5 6 15 0 4 1 9 6 1850 80 6 5 49 61 9 110 3 4 30 11 5 1850 74 7 48 6 0 65 3 93 88 1 19 0 4 9 2200 83 2 5 58 64 2 105 0 4 37 10 6 2200 76 2 52 5 0 69 4 17...

Page 42: ...ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT CT1 4...

Page 43: ...er Refer to EAS EAM EAL Auxiliary Heat kit installation instructions 1 Switch blue and red wires for 208V operation 2 The blk wh and gray wh wires are removed when Aux Heatis installed 7 Wires provide...

Page 44: ...ration LED LED 2 Yellow Fault LED LED 1 Red Normal Mode Dehumidification Mode Flash Code 2 DIP Switch Overide Slow Flash Status LED LED 3 Green Normal Mode ON Control is Non Functional OFF Test Mode S...

Page 45: ...sing Valve 2nd Stage Compressor 1st StageCompressor Y1 Y2 O R C LO ABC Board G G Fan W W Auxil iary HeatR ela y Note 11 Fiel di nstalled SPST dual fuel rel ay Required for dual fuel i nstallation Auxi...

Page 46: ...ATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT COMP1 4 3 FAN 4 3 COMP2 2 1 AUX 2 1 Status G DISCH P16 P17 P18 P15 Aurora Expansion Board AXB Aurora Expansion Board AXB SeeFigure1...

Page 47: ...gle Speed units Wire is secured at blower 6 Wires provided for Auxiliary Heatlow voltage control Wires are secured at blower 7 Brown blower power wire routed through CurrentTransducer two times 8 Fiel...

Page 48: ...D Flash Codes 1 second on and 1 second off No Software Overide OFF 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Rand...

Page 49: ...ostat Dual Fuel Wiring Diagram Using Field Installed Relay 24VDC R from Fossil Fuel Furnace To Fossil Fuel FurnaceW input EH1 C ABC Board Note 11 Fiel di nstalled SPST dual fuel rel ay Required for du...

Page 50: ...OTE4 NOTE6 Water Solenoid see Open Loop Groundwater Systems section UNIT 12 18 22 30 36 42 48 60 70 UNIT 22 30 36 42 48 M M H M M H M M M M HIGH STATIC PSC FACTORY SET FAN SPEED M M STANDARD PSC M M C...

Page 51: ...Flash Flash Code Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode FutureUse FutureUse Load Shed ESD OFF ON SlowFlash Fast Flash Flash Code 2 Flash Code 3 Flash Code...

Page 52: ...Switch Run Winding Active Start Common IntelliStart Red Pink Black Blue NOTE6 CC2 Factory Fault ALG ALM LS ES ACC c Status AURORA BASE CONTROL RV K1 CC2 CC K2 CCHi K3 Fan K4 Alarm K5 Acc K6 ACC no AC...

Page 53: ...h 1 secondon and 1 secondoff 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off witha 2 secondpause before repeating SlowFlash Fast Flash Flash Code Normal Mode...

Page 54: ...5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT 4 3 CT2 4 3 CT1 2 1 CT1 2 1 Status G DISCH P16 P17 P18 P15 Aurora Expansion Bo...

Page 55: ...3 4 5 ON OFF FutureUse Acc 2 Dip 4 Acc 2 Dip 5 CT2 SCT P8 MOTOR P6 RS485 P7 ZONE P9 ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SG...

Page 56: ...tical units shall be supplied with left or right horizontal air inlet and top bottom 022 072 or rear vertical 042 072 air discharge Horizontal units shall be supplied with left or right air inlet and...

Page 57: ...Dual Capacity or 2 zones Single Speed shall also be provided with complete fault and information display on the zoning MasterStat A detachable terminal block with screw terminals will be provided for...

Page 58: ...to any Aurora Advanced Control System including both ABC and AXB to monitor a sump pump The sen sor can be connected to the Aurora Home Automation inputs HA 1 or HA 2 of the AXB board These will each...

Page 59: ...the equipment is acceptable under the provisions of the job specification Statements and other information contained herein are not express warranties and do not form the basis of any bargain between...

Page 60: ...not express warranties and do not form the basis of any bargain between the parties but are merely the manufacturer s opinion or commendation of its products York and Affinity are registered trademar...

Reviews: