Engineering Guide Speci

fi

 cations cont.

Affinity & Affinity Advanced Series

1 - 6 Tons 60Hz

SD2500AK6      11/22 

57 

Page _____ of _____

have thermostatic overload protection. Variable speed ECM and 
5-speed ECM motors shall be long-life ball bearing type.

Electrical

A control box shall be located within the unit compressor 
compartment and shall contain a 75VA transformer, 24 volt activated, 
2 pole compressor contactor, circuit breakers for protecting loop 
pumps, terminal block for thermostat wiring, and solid-state controller 
for complete unit operation. Electromechanical operation WILL NOT 
be accepted. Units shall be name-plated for use with time delay fuses 
or HACR circuit breakers. Unit controls shall be 24 volt and provide 
heating or cooling as required by the remote thermostat/sensor. An 
Aurora, a microprocessor-based controller, interfaces with a multi-
stage electronic thermostat to monitor and control unit operation 
shall be provided. The control shall provide operational sequencing, 
blower speed control, blower failure, high and low pressure switch 
monitoring, freeze detection, hot water limit thermistor sensing, 
condensate overflow sensing, auxiliary heat staging, lockout mode 
control, hot water and loop pump control, LED status and fault 
indicators, fault memory, field selectable options, and accessory 
output. The Lockout signal output shall have a pulsed option so that 
DDC systems can read specific lockout conditions from the control. 

The optional Aurora Advanced Control shall also feature an 
Energy Monitoring Package that will provide real time total power 
consumption, compressor monitoring, On Peak input signal for 
utility controlled demand programs, intelligent hot water generation 
with user adjustable temperature limit, loop pump linking for 
multiple units driving a common flow center and up to two optional 
home automation inputs to drive dedicated alarms for sump 
pump, security system, and smoke/CO2 or dirty air filter sensors. 
Optional Refrigerant and Performance Monitoring kits to provide 
real time data including refrigerant superheat and subcooling, as 
well as heat of extraction/rejection capacity data. The capability for 
communicating to advanced IntelliZone2 zoning packages with up 
to 6 zones (Variable Speed), 4 zones (Dual Capacity), or 2 zones 
(Single Speed) shall also be provided with complete fault and 
information display on the zoning MasterStat.

A detachable terminal block with screw terminals will be provided 
for field control wiring. All units shall have knockouts for entrance 
of low and line voltage wiring. The blower motor and control box 
shall be harness plug wired for easy removal.
An optional Aurora Interface Diagnostic (AID) Tool shall 
communicate with the Aurora control allowing quick and easy 
access to setup, monitoring, and troubleshooting of any Aurora 
control. The device shall include the features of ECM airflow setup, 
fault description and history, manual operation capability, sensor 
readings, timings, and other diagnostic tools.

Optional IntelliStart

®

 (compressor Soft Starter) shall be factory 

installed for use in applications that require low starting amps, 
reduced compressor start-up noise, off-grid, and improved start-
up behavior. IntelliStart shall reduce normal starting current by up 
to 60%.

Piping

Supply and return water connections shall be 1 in. [25.4 mm] FPT 
brass swivel fittings, which provide a union and eliminate the need 
for pipe wrenches and sealants when making field connections. The 
optional hot water generator shall have sweat type connections. All 
water piping shall be insulated to prevent condensation at low liquid 
temperatures, on the vertical units, the condensate connection shall 
be a 3/4 in. [19.1 mm] PVC socket with internally-trapped hose that 
can be routed to front or side locations.

Hanger Kit

(field-installed horizontal units only) 

The hanger kit shall consist of galvanized steel brackets, bolts, 
lock washers, and isolators and shall be designed to fasten to the 
unit bottom panel for suspension from 3/8-inch threaded rods. Unit 
sizes 012-030 shall include four brackets. Unit sizes 036-072 shall 
include six brackets.

Options and Accessories

Cupronickel Heat Exchanger

An optional cupronickel water-to-refrigerant heat exchanger shall 
be provided.

Hot Water Generator

An optional ThermaShield coated heat reclaiming hot water 
generator coil of vented double-wall copper construction suitable 
for potable water shall be provided. The coil and hot water 
circulating pump shall be factory mounted inside the unit with 
integral electronic high limit temperature monitoring and external 
on/off switch.

5-Speed ECM Blower Motor

An optional constant torque 5-speed ECM blower motor is 
available on model sizes 022-072.

Thermostat (field-installed)

A multi-stage auto-changeover electronic digital thermostat shall 
be provided. The thermostat shall offer three heating and two 
cooling stages with precise temperature control. An OFF-HEAT-
AUTO-COOL-EMERG system switch, OFF-AUTO blower switch, 
and indicating LEDs shall be provided. The thermostat shall 
display in °F or °C. The thermostat shall be either a communicating
type or a traditional 24 VAC type.

Communicating Thermostat (field-installed)

A communicating auto-changeover electronic digital thermostat 
shall be provided. The thermostat shall offer variable speed 
heating and cooling staging with precise temperature control. An 

Summary of Contents for YAFS012

Page 1: ...NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www york geothermal com Additional rating information can found at www ahr...

Page 2: ...tory Installed Pump No IntelliStart1 3 No HWG IntelliStart1 4 HWG with Factory Installed Pump IntelliStart1 Vintage Factory Use Only Controls D Aurora Performance and Refrigeration Package Air Coil Op...

Page 3: ...2 000 6 1 22 200 29 7 17 500 4 9 21 000 26 0 16 400 4 5 038 Full 9 1300 36 500 17 0 43 300 5 5 40 000 24 4 35 000 4 9 38 200 19 7 28 500 4 2 038 Part 8 1150 26 500 19 0 31 300 6 4 29 900 32 1 24 900 5...

Page 4: ...on AHRI ISO 13256 1 Performance Ratings cont Affinity Affinity Advanced Series 1 6 Tons 60Hz SD2500AK6 11 22 4 Page _____ of _____ Cooling capacities based upon 80 6 F DB 66 2 F WB entering air temper...

Page 5: ...es 1 6 Tons 60Hz SD2500AK6 11 22 5 Page _____ of _____ Energy Star Rating Criteria In order for water source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirem...

Page 6: ...5 34 0 41 7 24 4 17 5 23 9 29 7 16 0 1 8 35 6 35 6 6 9 5 8 55 9 45 7 5 1 022 030 in 22 5 26 5 48 5 2 0 7 0 13 5 16 5 10 2 1 in Swivel 1 2 in Female 9 5 12 1 14 3 6 1 0 8 14 0 14 0 4 4 1 7 22 2 26 0 1...

Page 7: ...ate Supply Width Supply Depth Return Depth Return Height 022 030 in 22 5 26 5 52 5 35 3 40 2 46 7 49 7 3 6 1 in Swivel 1 2 in Female 41 9 43 6 45 1 8 6 6 0 9 3 10 5 1 0 2 2 22 2 26 0 5 6 cm 57 2 67 3...

Page 8: ...ate Power Supply Ext Pump Low Voltage Supply Width Supply Depth Return Depth Return Height 042 049 in 25 6 31 6 54 4 2 3 7 3 15 9 18 9 10 6 1 Swivel 1 2 female 9 5 12 1 14 3 13 3 13 6 39 4 9 1 8 1 1 7...

Page 9: ...11 7 1 8 10 5 9 5 8 2 2 2 21 8 16 5 1 5 cm 57 2 134 6 49 0 5 8 13 5 35 1 42 7 20 3 17 5 24 1 29 7 4 6 26 7 24 1 20 8 5 6 55 4 41 9 3 8 022 030 in 22 5 63 0 19 3 2 0 7 0 13 5 16 5 0 8 1 in Swivel 1 2...

Page 10: ...le Sweat I D in mm n a 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 0 35 1 3 0 40 1 5 0 7 2 6 1 0 3 8 1 3 4 9 1 3 4 9 1 6 6 1 1 6 6 1 2 3 8 7...

Page 11: ...279 x 254 5 Spd ECM 9 x 7 229 x 178 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 Coax and Water Piping Water Connections Size Swivel in mm 1 25 4 1 25 4 1 25 4 1 25 4 1 25...

Page 12: ...e 34 7 40 0 53 3 60 0 60 60 60 60 60 60 EAL H 15A Single 52 0 60 0 75 0 85 0 80 90 80 90 70 100 L1 L2 34 7 40 0 53 3 60 0 60 60 60 60 60 60 L3 L4 17 3 20 0 21 7 25 0 25 25 25 25 20 30 EAL H 20A Single...

Page 13: ...14 1 73 0 26 0 0 4 5 4 4 0 23 9 27 4 40 042 208 230 60 1 187 253 26 0 16 6 79 0 28 0 0 4 5 4 4 0 26 4 30 6 45 048 208 230 60 1 187 253 31 0 19 8 109 0 38 0 0 4 5 4 4 0 29 6 34 6 50 060 208 230 60 1 1...

Page 14: ...LA LRA LRA 026 208 230 60 1 187 253 18 2 11 6 58 3 21 0 0 4 5 4 4 0 21 4 24 4 35 038 208 230 60 1 187 253 23 8 15 2 83 0 30 0 0 4 5 4 4 0 25 0 28 8 40 049 208 230 60 1 187 253 33 0 21 1 104 0 37 0 0 4...

Page 15: ...0 75 800 950 1100 1300 1500 1750 1950 2100 2300 2325 G L H Aux 070 0 75 800 950 1100 1300 1500 1750 1950 2100 2300 2325 G L H Aux Factory settings are at recommended G L H Aux speed settings L H setti...

Page 16: ...2 Med Low 2 Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 048 High 5 11 x 10 1 1934 1910 1886 18...

Page 17: ...1659 1617 Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med Low 2 Y1 1575 1560 1540 1...

Page 18: ...r Performance Data cont Affinity Affinity Advanced Series 1 6 Tons 60Hz SD2500AK6 11 22 18 Page _____ of _____ Unit with Standard PSC Motor Model Motor Spd Blower Size Motor HP Airflow cfm at External...

Page 19: ...6 66 2 27 19 68 20 0 Max Entering Air db wb 110 83 43 28 3 80 26 7 Water Limits Min Entering Water 30 1 1 20 6 7 Normal Entering Water 50 110 10 43 3 30 70 1 1 Max Entering Water 120 48 9 90 32 2 NOTE...

Page 20: ...987 1 018 475 119 1 017 1 099 1 037 1 022 1 018 0 984 1 025 500 125 1 020 1 132 1 052 1 027 1 022 0 982 1 031 520 130 1 022 1 159 1 064 1 030 1 025 0 979 1 034 5 30 06 Air Flow Corrections Dual Capaci...

Page 21: ...he corrected heating and cooling performance at 30 F and 90 F respectively as well as pressure drop at 30 F for a Affinity Series Single Speed Model 022 ECM The corrected cooling capacity at 90 F woul...

Page 22: ...1 1 0 1 0 0 9 0 8 9 2 3 2 1 2 0 1 9 1 7 12 3 9 3 7 3 4 3 2 3 0 16 6 7 6 3 5 9 5 5 5 1 060 9 2 4 2 2 2 1 2 0 1 8 12 3 9 3 6 3 4 3 2 2 9 15 5 7 5 3 5 0 4 7 4 3 20 9 5 8 9 8 3 7 8 7 2 070 12 3 0 2 8 2 6...

Page 23: ...9 50 1 5 0 3 0 7 10 6 0 83 7 8 92 5 3 75 15 0 10 0 0 66 0 61 17 1 24 6 2 5 1 0 2 3 11 0 0 83 8 2 93 5 3 86 15 2 9 9 0 65 0 56 17 1 27 3 3 5 1 7 3 8 11 4 0 84 8 5 94 4 3 97 15 5 9 9 0 64 0 51 17 2 30...

Page 24: ...94 22 4 20 5 1 1 4 0 2 8 6 6 500 18 8 1 34 14 3 102 9 4 11 2 1 500 18 9 11 4 0 60 0 81 21 7 23 2 1 0 600 19 4 1 37 14 8 98 0 4 16 2 0 600 19 4 12 6 0 65 0 88 22 4 22 2 1 1 5 0 4 1 9 5 500 19 2 1 36 1...

Page 25: ...0 1 4 4 5 1 6 3 7 600 21 2 1 27 16 9 102 7 4 89 2 4 600 24 8 16 1 0 65 0 88 27 8 28 3 1 2 700 21 8 1 26 17 5 98 8 5 05 2 3 700 25 3 17 5 0 69 0 91 28 5 27 7 1 3 6 0 2 6 6 0 600 21 6 1 29 17 2 103 3 4...

Page 26: ...23 7 1 8 6 0 2 4 6 4 700 28 9 1 69 23 1 108 2 5 01 3 3 700 29 6 19 1 0 65 1 16 33 5 25 4 1 6 900 29 7 1 69 23 9 100 6 5 16 3 0 900 30 5 21 3 0 70 1 23 34 7 24 7 1 7 8 0 4 0 10 7 700 29 5 1 71 23 6 10...

Page 27: ...9 4 3 1050 34 5 2 01 27 6 100 4 5 03 4 0 1050 35 4 24 1 0 68 1 40 40 2 25 4 1 9 1250 35 5 2 01 28 6 96 3 5 18 3 7 1250 36 5 27 0 0 74 1 48 41 6 24 7 2 0 9 0 3 1 7 3 1050 35 2 2 04 28 2 101 0 5 06 4 2...

Page 28: ...4 6 1150 39 2 2 39 31 0 101 6 4 80 5 9 1150 43 0 28 0 0 65 1 70 48 8 25 4 2 8 1350 40 0 2 32 32 1 97 4 5 06 5 4 1350 44 7 31 4 0 70 1 78 50 8 25 1 3 0 11 0 3 9 9 1 1150 40 1 2 41 31 9 102 3 4 87 6 1...

Page 29: ...8 1300 51 3 3 28 40 1 106 5 4 59 7 8 1300 50 6 32 4 0 64 2 13 57 9 23 7 3 3 1500 52 3 3 18 41 5 102 3 4 83 7 2 1500 52 6 36 4 0 69 2 24 60 2 23 5 3 6 12 0 3 5 8 2 1300 52 5 3 31 41 2 107 4 4 65 8 0 13...

Page 30: ...9 4 16 50 7 110 0 4 57 9 4 1500 68 7 46 4 0 68 2 93 78 7 23 4 4 4 2000 65 8 4 21 51 4 100 5 4 57 8 7 2000 70 4 49 3 0 70 3 24 81 4 21 7 4 8 15 0 5 2 11 9 1500 66 3 4 23 51 9 110 9 4 59 9 7 1500 69 4 4...

Page 31: ...5 16 59 5 112 0 4 38 11 2 1700 72 6 47 0 0 65 3 22 83 5 22 6 4 8 2200 79 1 5 12 61 6 103 3 4 53 10 3 2200 76 4 53 8 0 70 3 62 88 8 21 1 5 2 18 0 5 3 12 3 1700 78 0 5 20 60 2 112 5 4 39 11 5 1700 73 5...

Page 32: ...6 2 96 3 5 37 1 9 700 23 7 16 0 0 68 0 77 26 4 31 0 1 0 5 0 1 8 4 1 500 20 2 1 08 16 5 107 4 5 50 2 1 500 23 3 14 6 0 63 0 73 25 8 31 8 0 9 700 20 7 1 08 17 0 97 3 5 60 2 0 700 24 0 16 1 0 67 0 75 26...

Page 33: ...8 32 9 22 3 1 6 900 26 8 1 59 21 4 97 6 4 94 2 9 900 29 9 19 9 0 67 1 34 34 4 22 3 1 7 6 0 2 5 5 8 700 27 2 1 63 21 6 105 9 4 90 3 2 700 29 2 18 1 0 62 1 22 33 3 24 0 1 5 900 28 1 1 64 22 5 98 9 5 02...

Page 34: ...1 3 1050 28 8 1 68 23 1 95 4 5 03 2 6 1050 31 3 23 1 0 74 1 06 35 0 29 7 1 4 6 0 1 5 3 6 900 29 3 1 67 23 6 100 1 5 15 3 0 900 30 8 21 0 0 68 1 01 34 2 30 5 1 3 1050 29 9 1 68 24 2 96 4 5 24 2 7 1050...

Page 35: ...1250 40 0 2 48 31 5 99 6 4 72 3 8 1250 41 3 28 7 0 70 2 09 48 4 19 8 2 4 7 0 2 0 4 6 1050 40 5 2 54 31 8 105 7 4 68 4 3 1050 40 4 26 1 0 65 1 90 46 8 21 3 2 2 1250 41 8 2 55 33 1 100 9 4 80 4 0 1250 4...

Page 36: ...50 34 9 2 22 27 3 93 9 4 61 4 8 1350 40 7 27 5 0 67 1 76 46 8 23 1 2 4 8 0 1 8 4 0 1150 36 5 2 29 28 6 99 3 4 67 5 4 1150 40 2 23 5 0 59 1 50 45 3 26 8 2 1 1350 37 9 2 26 30 2 96 0 4 91 5 0 1350 41 4...

Page 37: ...0 3 24 36 9 98 7 4 34 7 0 1550 54 1 34 3 0 63 2 90 64 0 18 7 3 9 9 0 2 2 5 0 1350 50 1 3 34 38 7 104 4 4 40 7 8 1350 53 4 29 3 0 55 2 47 61 8 21 6 3 4 1550 52 1 3 30 40 8 101 1 4 62 7 2 1550 55 0 34 5...

Page 38: ...7 6 2 89 37 8 99 4 4 84 5 7 1500 53 0 33 7 0 64 2 06 60 0 25 8 3 0 10 0 2 4 5 5 1250 48 1 2 96 38 0 105 6 4 76 6 3 1250 51 6 30 1 0 58 1 90 58 1 27 2 2 6 1500 48 9 2 92 38 9 100 2 4 90 5 8 1500 53 2 3...

Page 39: ...0 2 103 2 4 52 8 0 1800 70 0 45 9 0 66 3 51 81 9 19 9 5 1 12 0 3 4 7 8 1500 66 0 4 18 51 7 110 7 4 62 9 0 1500 68 9 42 6 0 62 3 23 79 9 21 3 4 5 1800 67 4 4 24 53 0 104 7 4 66 8 3 1800 70 7 46 3 0 66...

Page 40: ...0 4 02 48 3 103 8 4 52 6 9 1700 59 8 41 3 0 69 2 66 68 9 22 5 3 4 13 0 3 2 7 3 1400 61 1 4 15 47 0 110 4 4 32 7 7 1400 58 3 36 9 0 63 2 46 66 7 23 7 3 0 1700 63 6 4 07 49 7 104 6 4 57 7 1 1700 60 1 4...

Page 41: ...5 4 24 10 3 2200 75 5 52 0 0 69 4 26 90 1 17 7 5 6 15 0 4 1 9 6 1850 80 6 5 49 61 9 110 3 4 30 11 5 1850 74 7 48 6 0 65 3 93 88 1 19 0 4 9 2200 83 2 5 58 64 2 105 0 4 37 10 6 2200 76 2 52 5 0 69 4 17...

Page 42: ...ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT CT1 4...

Page 43: ...er Refer to EAS EAM EAL Auxiliary Heat kit installation instructions 1 Switch blue and red wires for 208V operation 2 The blk wh and gray wh wires are removed when Aux Heatis installed 7 Wires provide...

Page 44: ...ration LED LED 2 Yellow Fault LED LED 1 Red Normal Mode Dehumidification Mode Flash Code 2 DIP Switch Overide Slow Flash Status LED LED 3 Green Normal Mode ON Control is Non Functional OFF Test Mode S...

Page 45: ...sing Valve 2nd Stage Compressor 1st StageCompressor Y1 Y2 O R C LO ABC Board G G Fan W W Auxil iary HeatR ela y Note 11 Fiel di nstalled SPST dual fuel rel ay Required for dual fuel i nstallation Auxi...

Page 46: ...ATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT COMP1 4 3 FAN 4 3 COMP2 2 1 AUX 2 1 Status G DISCH P16 P17 P18 P15 Aurora Expansion Board AXB Aurora Expansion Board AXB SeeFigure1...

Page 47: ...gle Speed units Wire is secured at blower 6 Wires provided for Auxiliary Heatlow voltage control Wires are secured at blower 7 Brown blower power wire routed through CurrentTransducer two times 8 Fiel...

Page 48: ...D Flash Codes 1 second on and 1 second off No Software Overide OFF 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Rand...

Page 49: ...ostat Dual Fuel Wiring Diagram Using Field Installed Relay 24VDC R from Fossil Fuel Furnace To Fossil Fuel FurnaceW input EH1 C ABC Board Note 11 Fiel di nstalled SPST dual fuel rel ay Required for du...

Page 50: ...OTE4 NOTE6 Water Solenoid see Open Loop Groundwater Systems section UNIT 12 18 22 30 36 42 48 60 70 UNIT 22 30 36 42 48 M M H M M H M M M M HIGH STATIC PSC FACTORY SET FAN SPEED M M STANDARD PSC M M C...

Page 51: ...Flash Flash Code Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode FutureUse FutureUse Load Shed ESD OFF ON SlowFlash Fast Flash Flash Code 2 Flash Code 3 Flash Code...

Page 52: ...Switch Run Winding Active Start Common IntelliStart Red Pink Black Blue NOTE6 CC2 Factory Fault ALG ALM LS ES ACC c Status AURORA BASE CONTROL RV K1 CC2 CC K2 CCHi K3 Fan K4 Alarm K5 Acc K6 ACC no AC...

Page 53: ...h 1 secondon and 1 secondoff 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off witha 2 secondpause before repeating SlowFlash Fast Flash Flash Code Normal Mode...

Page 54: ...5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT 4 3 CT2 4 3 CT1 2 1 CT1 2 1 Status G DISCH P16 P17 P18 P15 Aurora Expansion Bo...

Page 55: ...3 4 5 ON OFF FutureUse Acc 2 Dip 4 Acc 2 Dip 5 CT2 SCT P8 MOTOR P6 RS485 P7 ZONE P9 ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SG...

Page 56: ...tical units shall be supplied with left or right horizontal air inlet and top bottom 022 072 or rear vertical 042 072 air discharge Horizontal units shall be supplied with left or right air inlet and...

Page 57: ...Dual Capacity or 2 zones Single Speed shall also be provided with complete fault and information display on the zoning MasterStat A detachable terminal block with screw terminals will be provided for...

Page 58: ...to any Aurora Advanced Control System including both ABC and AXB to monitor a sump pump The sen sor can be connected to the Aurora Home Automation inputs HA 1 or HA 2 of the AXB board These will each...

Page 59: ...the equipment is acceptable under the provisions of the job specification Statements and other information contained herein are not express warranties and do not form the basis of any bargain between...

Page 60: ...not express warranties and do not form the basis of any bargain between the parties but are merely the manufacturer s opinion or commendation of its products York and Affinity are registered trademar...