Blower Performance Data cont.
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
SD2500AK6 11/22
18
Page _____ of _____
Unit with Standard PSC Motor
Model
Motor
Spd
Blower
Size
Motor
HP
Airflow (cfm) at External Static Pressure (in. wg)
0
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.60
0.70
0.80
0.90
1.00
012
H
6 x 8
1/10
480
450
440
420
410
380
360
340
330
310
300
-
-
-
-
-
MH*
440
410
400
380
370
350
330
310
300
280
270
-
-
-
-
-
ML
395
370
360
340
330
310
290
280
270
250
240
-
-
-
-
-
L
325
310
300
280
270
250
240
230
220
210
200
-
-
-
-
-
7/15/22
Factory settings are in Bold
Air flow values are with dry coil and standard filter
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by
0.16 in. wg.