876572-BIM-C-0213
Johnson Controls Unitary Products
23
Table 16: UB048 Charging Table
Table 17: UB060 Charging Table
Air Flow
Indoor Db/Wb
Outdoor
DB
Suction
Pressure
Suction
Temp.
Discharge
Pressure
Liquid
Temp.
Delta T
Db
Entering
Evap Db
Leaving
Evap Db
Compressor
Amps
300 Cfm/Ton
80/62
75
126
54
293
81
-30
80
50
12.0
85
129
56
338
91
-29
80
51
13.8
95
133
59
390
102
-28
80
52
15.9
300 Cfm/Ton
80/67
75
138
60
301
82
-25
80
55
12.2
85
141
60
347
92
-24
80
56
14.0
95
145
62
398
103
-23
80
57
16.1
300 Cfm/Ton
80/72
75
150
64
306
83
-20
80
60
12.4
85
153
65
355
93
-19
80
61
14.2
95
157
67
405
103
-18
80
62
16.2
300 Cfm/Ton
75/63
75
128
57
294
81
-24
75
51
12.1
85
131
58
340
91
-23
75
52
13.8
95
134
60
390
101
-22
75
53
15.9
400 Cfm/Ton
80/62
75
131
57
294
81
-27
80
53
12.0
85
134
59
340
91
-26
80
54
13.7
95
137
60
390
101
-25
80
55
15.8
400 Cfm/Ton
80/67
75
143
63
302
82
-22
80
58
12.2
85
146
64
347
91
-21
80
59
13.9
95
148
65
397
101
-20
80
60
16.0
400 Cfm/Ton
80/72
75
155
67
309
83
-17
80
63
12.4
85
158
68
355
92
-17
80
63
14.1
95
161
69
405
102
-16
80
64
16.2
400 Cfm/Ton
75/63
75
133
59
297
81
-21
75
54
12.1
85
135
60
342
91
-20
75
55
13.8
95
139
62
392
101
-19
75
56
15.9
Air Flow
Indoor Db/Wb
Outdoor
DB
Suction
Pressure
Suction
Temp.
Discharge
Pressure
Liquid
Temp.
Delta T
Db
Entering
Evap Db
Leaving
Evap Db
Compressor
Amps
300 Cfm/Ton
80/62
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
300 Cfm/Ton
80/67
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
300 Cfm/Ton
80/72
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
300 Cfm/Ton
75/63
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
400 Cfm/Ton
80/62
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
400 Cfm/Ton
80/67
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
400 Cfm/Ton
80/72
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
400 Cfm/Ton
75/63
75
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
85
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
95
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD