background image

876572-BIM-C-0213

Johnson Controls Unitary Products

5

Unit Location

Several important factors must be considered before selecting 
the site for this unit:

1.

 Site – Select a solid level position, preferably on a concrete 
slab, slightly above grade level and parallel to the home.

2.

Proximity to home or building – The length of the supply 
and return ducts should be kept to a minimum with no 
sharp bends. Consideration should be given to the 
distance and routing of electrical service to connect the 
unit. Try to select a site for the unit that it is as close as 
possible to the proposed return grille location. Unit may be 
positioned to draw air from underneath structure.

3.

Proximity to the clothes dryer vent – The clothes dryer vent 
should not be located upwind from the unit.

4.

Ability to service – Side access panels of the unit should 
not be closer than 24 inches to a structure so blower and 
controls may be serviced.

5.

Sound transmission – Locate the unit away from bedroom 
windows or other rooms where sound may be objectionable.

6.

 Air Circulation – The outside coil sides should not be 
closer than 24 inches to a structure that will restrict air flow 
through the coil. The air discharge of the unit requires a 60-
inch clearance between the top of the unit and any 
obstruction.See Figure 2.

7.

 Wind direction – The hot condenser air must be discharged 
up and away from the home or building, and if possible in a 
direction with the prevailing wind.

8.

 Relationship between building, sun and unit – If practical, 
place the air conditioner in an area where the unit and the 
ducts will be shaded from the afternoon sun (when the heat 
load is the greatest).

9.

Defrost and Water Drainage - Water will run off the outdoor 
coil when the heat pump defrosts during the heating 
season. This water will run through the drain holes of the 

heat pump base pan onto the ground below. A slight grade 
away from the unit will improve drainage.

10. Average Winter Snow Depth - The heat pump must be 

installed above the average snow depth to allow the 
outdoor coil to drain properly. 

Cinder blocks, if permitted by local codes, or a metal frame 
may be used to support the unit above the snow. Insure 
that the support does not obstruct drainage holes in the 
base pan of the unit. Metal frame legs must be supported 
by concrete pads. The heat pump must set level and 
securely upon the support.

NOTE: 

If installing on blocks, the middle rail must be supported.

Figure 2: Air Discharge Clearance

Site Preparation

After the site has been selected and prepared, using criteria 
mentioned above, install the air conditioner support pad at the 
selected site.

NOTE: 

This unit must be installed and operated on a level 
surface. Failure to do so will result in condensate 
drainage problems.

60”

Summary of Contents for UB0 Series

Page 1: ...ance 5 3 Unit 4 Point Load Weight 6 4 Unit Dimensions 7 5 Return Air Box and Grille 8 6 Wye Installation Outlet 9 7 Wye Installation Inlet and Outlet 10 8 Duct Connector With Damper 10 9 Duct Connecto...

Page 2: ...ed replacement parts Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service...

Page 3: ...oling Only Product Identifier B 13 SEER Heat Pump Airflow A Standard Drive Installation Options A No Options Installed Voltage Code F 208 230 1 60 T 208 230 3 60 W 460 3 60 Product Style A Style A Add...

Page 4: ...ed procedures identified by the Air Conditioning Contractors of America Figure 1 Component Location Direct Drive Condenser Fan Motor High Efficiency Enhanced Copper Tube Aluminum Fin Outdoor Coil High...

Page 5: ...ruction See Figure 2 7 Wind direction The hot condenser air must be discharged up and away from the home or building and if possible in a direction with the prevailing wind 8 Relationship between buil...

Page 6: ...per unit operation Figure 3 Unit 4 Point Load Weight C X Y CG D A B Right Left Front Rear Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 328 32...

Page 7: ...F D CONDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 15 16 47 1 4 12 9 16 8 1...

Page 8: ...be installed first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting c...

Page 9: ...ub collar in the raw end of the duct and tape securely in place 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with...

Page 10: ...a register This will help to eliminate the transmission of sound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locati...

Page 11: ...eturn air ducts passing through unconditioned spaces of the building must be insulated and covered with a vapor barrier Following this practice will prevent thermal losses and condensate formation on...

Page 12: ...accept a single circuit of supply power If an auxiliary heater is installed dual circuiting to the unit can be used When installing a 14 3 KW heater this method will avoid the use of large wiring To p...

Page 13: ...7 Never locate it in a room that is warmer or cooler than the rest of the home such as a kitchen or hallway 8 The living or dining room is normally a good location provided there is no cooking range o...

Page 14: ...e on If accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setti...

Page 15: ...0 F A forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while...

Page 16: ...8 1 17 2 19 9 47 8 51 1 60 60 60 60 2PH08520706 4 9 6 5 1 23 5 27 1 55 6 60 1 60 70 60 70 2PH08521006 7 2 9 6 1 34 5 39 8 69 4 76 70 80 70 80 2PH08521506 10 8 14 3 1 51 7 59 7 90 9 100 9 100 110 100 1...

Page 17: ...l Scroll Scroll Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 1 11 28 11 28 16 16 20 Rows 1 2 2 2 2 2 Fins per inch 20 15 20 15 15 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3...

Page 18: ...1 High 2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016...

Page 19: ...19 0 20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0...

Page 20: ...0 1300 1270 1270 060 5 0 208 230 1 60 1300 1300 1270 1270 Table 10 Indoor Blower Specifications Size Tons Motor HP RPM Eff SF Frame 024 2 0 1 2 1100 0 8 1 0 48 030 2 5 1 2 1100 0 8 1 0 48 036 3 0 1 2...

Page 21: ...95 TBD TBD TBD TBD TBD TBD TBD TBD 400 Cfm Ton 75 63 75 TBD TBD TBD TBD TBD TBD TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TBD Air Flow Indoor Db Wb Outdoor DB Suction P...

Page 22: ...TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TBD 400 Cfm Ton 75 63 75 TBD TBD TBD TBD TBD TBD TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TB...

Page 23: ...2 400 Cfm Ton 75 63 75 133 59 297 81 21 75 54 12 1 85 135 60 342 91 20 75 55 13 8 95 139 62 392 101 19 75 56 15 9 Air Flow Indoor Db Wb Outdoor DB Suction Pressure Suction Temp Discharge Pressure Liqu...

Page 24: ...COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner...

Page 25: ...876572 BIM C 0213 Johnson Controls Unitary Products 25 Typical Wiring Diagrams UB024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 26: ...876572 BIM C 0213 26 Johnson Controls Unitary Products UB036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram...

Page 27: ...876572 BIM C 0213 Johnson Controls Unitary Products 27 UB060 Typical Heat Pump 460 3 60 volt Wiring Diagram...

Page 28: ...o change without notice Printed in U S A 876572 BIM C 0213 Copyright 2013 by Johnson Controls Inc All rights reserved Supersedes 876572 BIM B 1212 York International Corporation 5005 York Drive Norman...

Reviews: