Johnson Controls Unitary Products

Installing Of Duct To Unit 
(Manufactured Housing)

Flanges for round ducts are packed with the unit.The unit’s supply 
and return air connections are sized for optimum performance.

Should the ductwork connecting to the air conditioner be of 
smaller dimensions, it is recommended that transitions 
connecting the ducts to the unit be constructed to allow a 
smooth airflow to the air conditioner’s return air opening and 
from the supply air opening. Abrupt duct size changes increase 
the system static pressure and reduces air volume which may 
cause unsatisfactory performance. Duct-work should be in 
accordance with Local and National Codes.

Ductwork exposed to outside environmental conditions must be 
insulated and weather proofed. Out-side wall openings through 
which the ducts pass must be weather proofed in accordance 
with Local and National Codes.

Supply and return air ducts passing through unconditioned 
spaces of the building must be insulated and covered with a 
vapor barrier. Following this practice will prevent thermal losses 
and condensate formation on the ducts.

Supply and Return Ducts

Duct should be sized to accommodate a maximum of .8” water 
column. Metal ducts may be used when properly insulated and 
vapor proofed. Any duct used should be covered with insulation 
having a minimum R-value of 4.0 or in accordance with any 
local codes or standards regarding duct material. Insulation 

must be covered with a vapor barrier. Install the air conditioning 
duct connections to the unit. Insure that the seam is towards 
bottom. A good quality duct tape should be used to insure an 
airtight installation.

The Return — Air Grille Boxes

The return air grille assembly should be installed first. The 
return air grille box and filter should be located and installed in 
the “out-rigger” areas of the home. Keep in mind, the closer to 
the cooling unit, the better. The return ducting connects to the 
bottom of the return air box so it will be necessary to provide an 
opening beneath the box. See Figure 5.

Figure 5: Return Air Box and Grille

After determining the location of the return air opening, start 
installation from beneath the manufactured home.

1.

Cut a small hole in the fiber under board to determine floor 
joist location.Floor joists are generally located on 16” 
centers, leaving 14-3/8” between joists.

2.

Cut a 12-1/2” x 20-1/2” rectangular hole in the floor 
between two joists.

3.

Set the return box into the opening and mark a circular 
pattern on the fiber under board through the flex duct 
connector collar, then remove the return box from the 
opening.

4.

Cut outside of the circular mark to allow enough space to 
pull the flex duct up through the hole and fasten to the 
return box.

Table 3:

Unit Clearances

Direction

Distance

(in.)

Direction

Distance

(in.)

Top

1

1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air 

discharge outlet.

60

Right

24

Front

36

Left

24

Rear

2

2. Unit may be positioned to draw air from underneath structure.

18

Bottom

0

When installing this air conditioning system in 
conjunction with a furnace, a damper must be installed 
in the furnace to prevent cold air being discharged 
around the heat exchanger. The presence of such cold 
air could damage the heat exchanger and could cause 
asphyxiation.A damper, part number 7900-6771* is 
available for use on Unitary Products Group 
manufactured housing gas and oil furnaces. (See 7900-
6771* damper assembly installation instructions packed 
with the damper assembly for more in-formation. For 
other makes of furnaces, check with the furnace 
manufacturer for damper requirements.

Grille

Filter

Return Box

Summary of Contents for UB0 Series

Page 1: ...ance 5 3 Unit 4 Point Load Weight 6 4 Unit Dimensions 7 5 Return Air Box and Grille 8 6 Wye Installation Outlet 9 7 Wye Installation Inlet and Outlet 10 8 Duct Connector With Damper 10 9 Duct Connecto...

Page 2: ...ed replacement parts Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service...

Page 3: ...oling Only Product Identifier B 13 SEER Heat Pump Airflow A Standard Drive Installation Options A No Options Installed Voltage Code F 208 230 1 60 T 208 230 3 60 W 460 3 60 Product Style A Style A Add...

Page 4: ...ed procedures identified by the Air Conditioning Contractors of America Figure 1 Component Location Direct Drive Condenser Fan Motor High Efficiency Enhanced Copper Tube Aluminum Fin Outdoor Coil High...

Page 5: ...ruction See Figure 2 7 Wind direction The hot condenser air must be discharged up and away from the home or building and if possible in a direction with the prevailing wind 8 Relationship between buil...

Page 6: ...per unit operation Figure 3 Unit 4 Point Load Weight C X Y CG D A B Right Left Front Rear Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 328 32...

Page 7: ...F D CONDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 15 16 47 1 4 12 9 16 8 1...

Page 8: ...be installed first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting c...

Page 9: ...ub collar in the raw end of the duct and tape securely in place 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with...

Page 10: ...a register This will help to eliminate the transmission of sound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locati...

Page 11: ...eturn air ducts passing through unconditioned spaces of the building must be insulated and covered with a vapor barrier Following this practice will prevent thermal losses and condensate formation on...

Page 12: ...accept a single circuit of supply power If an auxiliary heater is installed dual circuiting to the unit can be used When installing a 14 3 KW heater this method will avoid the use of large wiring To p...

Page 13: ...7 Never locate it in a room that is warmer or cooler than the rest of the home such as a kitchen or hallway 8 The living or dining room is normally a good location provided there is no cooking range o...

Page 14: ...e on If accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setti...

Page 15: ...0 F A forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while...

Page 16: ...8 1 17 2 19 9 47 8 51 1 60 60 60 60 2PH08520706 4 9 6 5 1 23 5 27 1 55 6 60 1 60 70 60 70 2PH08521006 7 2 9 6 1 34 5 39 8 69 4 76 70 80 70 80 2PH08521506 10 8 14 3 1 51 7 59 7 90 9 100 9 100 110 100 1...

Page 17: ...l Scroll Scroll Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 1 11 28 11 28 16 16 20 Rows 1 2 2 2 2 2 Fins per inch 20 15 20 15 15 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3...

Page 18: ...1 High 2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016...

Page 19: ...19 0 20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0...

Page 20: ...0 1300 1270 1270 060 5 0 208 230 1 60 1300 1300 1270 1270 Table 10 Indoor Blower Specifications Size Tons Motor HP RPM Eff SF Frame 024 2 0 1 2 1100 0 8 1 0 48 030 2 5 1 2 1100 0 8 1 0 48 036 3 0 1 2...

Page 21: ...95 TBD TBD TBD TBD TBD TBD TBD TBD 400 Cfm Ton 75 63 75 TBD TBD TBD TBD TBD TBD TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TBD Air Flow Indoor Db Wb Outdoor DB Suction P...

Page 22: ...TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TBD 400 Cfm Ton 75 63 75 TBD TBD TBD TBD TBD TBD TBD TBD 85 TBD TBD TBD TBD TBD TBD TBD TBD 95 TBD TBD TBD TBD TBD TBD TBD TB...

Page 23: ...2 400 Cfm Ton 75 63 75 133 59 297 81 21 75 54 12 1 85 135 60 342 91 20 75 55 13 8 95 139 62 392 101 19 75 56 15 9 Air Flow Indoor Db Wb Outdoor DB Suction Pressure Suction Temp Discharge Pressure Liqu...

Page 24: ...COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner...

Page 25: ...876572 BIM C 0213 Johnson Controls Unitary Products 25 Typical Wiring Diagrams UB024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 26: ...876572 BIM C 0213 26 Johnson Controls Unitary Products UB036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram...

Page 27: ...876572 BIM C 0213 Johnson Controls Unitary Products 27 UB060 Typical Heat Pump 460 3 60 volt Wiring Diagram...

Page 28: ...o change without notice Printed in U S A 876572 BIM C 0213 Copyright 2013 by Johnson Controls Inc All rights reserved Supersedes 876572 BIM B 1212 York International Corporation 5005 York Drive Norman...

Reviews: