Johnson Controls Unitary Products
Installation
Limitations
These units must be installed in accordance with the following
national and local safety codes.
1.
National Electrical Code ANSI/NFPS No. 70 or Canadian
Electrical Code Part 1, C22.1 (latest editions).
2.
Local plumbing and waste water codes and other
applicable local codes.
Refer to Table 6 for unit physical data and to Table 5 for electrical
data.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.
Figure 1: Component Location
Direct Drive
Condenser Fan Motor
High Efficiency Enhanced
Copper Tube/Aluminum Fin
Outdoor Coil
High Efficiency
Compressor Rigidly
Mounted
Decorative Protective
Coil Guard
High Efficiency Enhanced
Copper Tube/Aluminum Fin
Indoor Coil
Blower Service
Access Panel
X13 or PSC
Direct Drive
Blower Motor
Refrigerant
Connections
Control Box Service
Access Panel
Heavy Gauge
Base Rails
Table 1:
Unit Limitations
Size
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
024
(2.0)
208/230-1-60
187
252
125
030
(2.5)
208/230-1-60
187
252
125
036
(3.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
042
(3.5)
208/230-1-60
187
252
125
048
(4.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
060
(5.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125