5402847-UIM-A-0917

22

Johnson Controls Unitary Products

SECTION VII: START-UP AND 

ADJUSTMENTS

The initial start-up of the furnace requires the following additional
procedures:

When the gas supply is initially connected to the furnace, the gas piping
may be full of air. In order to purge this air, it is recommended that the
ground union be loosened until the odor of gas is detected. When gas is
detected, immediately retighten the union and check for leaks. Allow
five minutes for any gas to dissipate before continuing with the start-up
procedure. Be sure proper ventilation is available to dilute and carry
away any vented gas.

NOx SCREEN REMOVAL (Lo-NOx Models Only)

If the furnace is equipped with NOx screens and is to be used with LP
(propane) gas, the screens must be removed prior to start-up.

1.

Make sure that the electrical power to the unit is turned off and that
the gas supply is turned off at the shut-off valve.

2.

Remove the blower compartment and burner compartment access
doors.

3.

Disconnect the gas supply piping at the union to permit removal of
the entire burner and gas control assembly from the vestibule
panel. Use the wrench boss on the gas valve when removing or
installing the piping.

4.

Unplug the igniter from the wire harness. Disconnect the flame sen-
sor wires located on top of the air shield. Unplug the gas valve from
the wiring harness.

5.

Remove the screws holding the burner assembly to the vestibule
panel.

6.

Remove the burner assembly. It should be possible to swing the
burner assembly out of the way without disconnecting the remain-
ing wires.

7.

With the burner assembly out of the way, simply slide the NOx
screens out of the heat exchanger tubes and discard the screens.

8.

Replace all components in reverse order. Reconnect all wiring.

 WARNING

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon-
monxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances
connected to the venting system are not in operation:

1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other

deficiencies, which could cause an unsafe condition

2. Close all building doors and windows.

3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum

speed. Open the fireplace dampers. Do not operate a summer exhaust fan.

4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate contin-

uously.

5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening

after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the
appliance as possible. Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a
downdraft or inadequate draft condition.

6. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fire-

place dampers and any other gas burning appliance to their normal condition.

7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not

have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can
function safely.

NOTE: 

An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1 in. W.C. (-25 kPa) with

all of the appliance(s) operating at the same time.

8. Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code

Z223.1 or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the
appropriate tables in Appendix G of the above codes or for this appliance.

!

IMPORTANT

All electrical connections made in the field and in the factory should
be checked for proper tightness.

Summary of Contents for TM8V C Series

Page 1: ...les All Dimensions in Inches and All Surfaces Identified with the Unit in an Upflow Configuration 4 Coil Projection Dimensions PC Series Coils 6 Cabinet and Duct Dimensions 9 Recommended Filter Sizes...

Page 2: ...provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lift ing points as the tubes may...

Page 3: ...e National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NSCN...

Page 4: ...ide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery o...

Page 5: ...all be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges re...

Page 6: ...furnace A mounting plate supplied with every coil should always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS Dimension C should be at least 2 3 of...

Page 7: ...r installation RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION Return air may enter the furnace through the side s or bottom depend ing on the type of application Return air may not be co...

Page 8: ...mum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the furnace use a se...

Page 9: ...Y END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3 Cabinet and Duct Dimensions BTUH k...

Page 10: ...he type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 15 FIGURE 13 Side Return Cutout Markings IMPORTANT S...

Page 11: ...2742 2743 3048 Gas Heating Value BTU cu ft 800 3 5 3 5 3 5 Gas Heating Value MJ cu m 29 8 0 87 0 87 0 87 850 3 5 3 5 3 5 31 7 0 87 0 87 0 87 900 3 5 3 5 3 5 33 5 0 87 0 87 0 87 950 3 5 3 5 3 3 35 4 0...

Page 12: ...l thermostat and outdoor A C or heat pump using either conventional low voltage 24 VAC thermo stat wiring OR using four wire digital communications wiring To use conventional low voltage wiring see th...

Page 13: ...h may be connected to the FLT SWT terminals on the control board This feature is only functional when used with the Com munication Control It is intended for use with a water overflow switch Auxiliary...

Page 14: ...to Communication Control Installation Man ual LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermost...

Page 15: ...s for all UPG equipment refer to Low Voltage System Wiring document available on line at www upgnet com in the Product Catalog Section FIGURE 21 Thermostat Chart Single Stage Air Conditioner with Two...

Page 16: ...ls Unitary Products FIGURE 22 Thermostat Chart Single Stage Heat Pump with Two Stage Variable Speed Furnace Y Y2 TM8V W1 Room thermostat or external fossil fuel kit must be used to control fossil fuel...

Page 17: ...5402847 UIM A 0917 Johnson Controls Unitary Products 17 FIGURE 23 Thermostat Chart Two Stage Air Conditioner with Two Stage Variable Speed Furnace A0918 001 TM8V S1 THXU280 W1 TMLV...

Page 18: ...02847 UIM A 0917 18 Johnson Controls Unitary Products FIGURE 24 Thermostat Chart Two Stage Heat Pump with Two Stage Variable Speed Furnace Hot Heat Pump or Conventional TM8V S1 THXU280 W1 A0919 001 TM...

Page 19: ...rate appliance designed to burn solid fuel It is recommended that the appliance is installed in a location where the space temperature is 32 F 0 C or higher If the appliance is installed in a locatio...

Page 20: ...no dimen sion smaller than 0 25 0 64 cm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers sh...

Page 21: ...onal area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the free a...

Page 22: ...ng placed into operation while all other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no bl...

Page 23: ...clocking meter 1 Turn off all other gas appliances and pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note readi...

Page 24: ...Size of Test Dial Seconds For 1 Revolution Size of Test Dial 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346...

Page 25: ...pplies back on and with the burners in operation check for gas leakage around the gas valve pressure port for leakage using an approved non corrosive gas leak detec tion fluid or other non flammable l...

Page 26: ...is dependent upon the panel that covers the blower compartment being in place and properly positioned ROLLOUT SWITCH CONTROLS These controls are mounted on the burner assembly If the temperature in th...

Page 27: ...l run at the speed selected on the FAN SPEED jumpers on the main control board HI COOL LO COOL HI HEAT or LO HEAT When the jumper is in the VS G position the blower will run at 50 of the high cool spe...

Page 28: ...ce will lock out for one hour and then restart 9 RED FLASHES Indicates reversed line voltage polarity grounding problem or reversed low voltage transformer wires Both heating and cooling operations wi...

Page 29: ...3 D A 1013 676 1245 842 1284 842 C C 844 591 1092 765 1130 746 D C HIGH LOW HEAT CFM 060B12 080B12 080C16 Jumper Settings HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Tap ADJ Tap 1111...

Page 30: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft Req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Page 31: ...of flame during call for heat Hot Neutral reversed OR poor ground neutral Gas valve shorted ON Check blower motor wiring Vent OR termination problem None Slow Green Slow Amber Rapid Amber 4 Amber Ste...

Page 32: ...5402847 UIM A 0917 32 Johnson Controls Unitary Products NOTES...

Page 33: ...Equipment and Accessories Owner Information Equipment Data Furnace Configuration Venting B Vent Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Loc...

Page 34: ...Side Continuous Fan PSC Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle Test Operate the furnace through several heating c...

Reviews: