background image

5402847-UIM-A-0917

Johnson Controls Unitary Products

11

The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or less
than 1/2 psig (3.5 kPa).

Gas piping may be connected from either side of the furnace using any
of the gas pipe entry on both sides of the furnace. Refer to Figure 12.

GAS ORIFICE CONVERSION FOR PROPANE (LP)

This furnace is constructed at the factory for natural gas-fired operation,
but may be converted to operate on propane (LP) gas by using a fac-
tory-supplied LP conversion kit. Follow the instructions supplied with
the LP kit.

HIGH ALTITUDE GAS ORIFICE CONVERSION

This furnace is constructed at the factory for natural gas-fired operation
at 0 –5,000 feet (0-m – 1,524 m) above sea level.

The manifold pressure must be changed in order to maintain proper
and safe operation when the furnace is installed in a location where the
altitude is greater than 5,000 feet (1,524 m) above sea level. Refer to
Tables 5 & 6 for proper manifold pressure settings.

HIGH ALTITUDE PRESSURE SWITCH CONVERSION

For installation where the altitude is less than 5,000 feet (1,524m), it is
not required that the pressure switches be changed unless you are in
an area subject to low pressure inversions.

IMPORTANT

An accessible manual shutoff valve must be installed upstream of the
furnace gas controls and within 6 feet (1.8 m) of the furnace.

 CAUTION

The gas valve body is a very thin casting that cannot take any exter-
nal pressure. Never apply a pipe wrench to the body of the gas valve
when installing piping. A wrench must be placed on the octagon hub
located on the gas inlet side of the valve. Placing a wrench to the
body of the gas valve will damage the valve causing improper opera-
tion and/or the valve to leak.

!

 WARNING

LoNOx furnaces requiring propane (LP) gas must have the LoNOx
screens removed prior to installation and operation. See propane
instructions.

!

Table 5: 

Nominal Manifold Pressure - High Fire

Manifold Pressures (in. w.c.)

Manifold Pressures (kPa)

Altitude (feet)

Altitude (m)

0-7999

8000-8999

9000-9999

0-2437

2438-2742

2743-3048

Gas Heating V

alue

(BTU/cu ft.)

800

3.5

3.5

3.5

Gas Heating V

alue

(MJ/cu m)

29.8

0.87

0.87

0.87

850

3.5

3.5

3.5

31.7

0.87

0.87

0.87

900

3.5

3.5

3.5

33.5

0.87

0.87

0.87

950

3.5

3.5

3.3

35.4

0.87

0.87

0.81

1000

3.5

3.2

2.9

37.3

0.87

0.80

0.73

1050

3.5

2.9

2.7

39.1

0.87

0.73

0.67

1100

3.2

2.7

2.4

41.0

0.80

0.66

0.61

2500 (LP)

9.8

8.2

7.5

93.2 (LP)

2.44

2.03

1.86

TABLE 6: 

Nominal Manifold Pressure - Low Fire

First Stage Manifold Pressures (in. w.c.)

First Stage Manifold Pressures (kPa)

Altitude (feet)

Altitude (m)

0-7999

8000-8999

9000-9999

0-2437

2438-2742

2743-3048

Gas Heating V

alue

(BTU/cu ft.)

800

1.7

1.7

1.7

Gas Heating V

alue

(MJ/cu m)

29.8

0.42

0.42

0.42

850

1.7

1.7

1.7

31.7

0.42

0.42

0.42

900

1.7

1.7

1.7

33.5

0.42

0.42

0.42

950

1.7

1.7

1.5

35.4

0.42

0.42

0.38

1000

1.6

1.5

1.4

37.3

0.41

0.37

0.34

1050

1.5

1.4

1.3

39.1

0.37

0.34

0.31

1100

1.3

1.2

1.1

41.0

0.34

0.31

0.28

2500 (LP)

4.1

3.8

3.5

93.2 (LP)

1.03

0.95

0.87

 DANGER

PROPANE AND HIGH ALTITUDE CONVERSION KITS
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed.
Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-
pane (LP) gas. Do not use this furnace with butane gas.
Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death.
High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application.
An authorized distributor or dealer must make all gas conversions.
In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed.
Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames, caus-
ing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage and/or
death.

!

Summary of Contents for TM8V C Series

Page 1: ...les All Dimensions in Inches and All Surfaces Identified with the Unit in an Upflow Configuration 4 Coil Projection Dimensions PC Series Coils 6 Cabinet and Duct Dimensions 9 Recommended Filter Sizes...

Page 2: ...provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lift ing points as the tubes may...

Page 3: ...e National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NSCN...

Page 4: ...ide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery o...

Page 5: ...all be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges re...

Page 6: ...furnace A mounting plate supplied with every coil should always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS Dimension C should be at least 2 3 of...

Page 7: ...r installation RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION Return air may enter the furnace through the side s or bottom depend ing on the type of application Return air may not be co...

Page 8: ...mum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the furnace use a se...

Page 9: ...Y END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3 Cabinet and Duct Dimensions BTUH k...

Page 10: ...he type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 15 FIGURE 13 Side Return Cutout Markings IMPORTANT S...

Page 11: ...2742 2743 3048 Gas Heating Value BTU cu ft 800 3 5 3 5 3 5 Gas Heating Value MJ cu m 29 8 0 87 0 87 0 87 850 3 5 3 5 3 5 31 7 0 87 0 87 0 87 900 3 5 3 5 3 5 33 5 0 87 0 87 0 87 950 3 5 3 5 3 3 35 4 0...

Page 12: ...l thermostat and outdoor A C or heat pump using either conventional low voltage 24 VAC thermo stat wiring OR using four wire digital communications wiring To use conventional low voltage wiring see th...

Page 13: ...h may be connected to the FLT SWT terminals on the control board This feature is only functional when used with the Com munication Control It is intended for use with a water overflow switch Auxiliary...

Page 14: ...to Communication Control Installation Man ual LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermost...

Page 15: ...s for all UPG equipment refer to Low Voltage System Wiring document available on line at www upgnet com in the Product Catalog Section FIGURE 21 Thermostat Chart Single Stage Air Conditioner with Two...

Page 16: ...ls Unitary Products FIGURE 22 Thermostat Chart Single Stage Heat Pump with Two Stage Variable Speed Furnace Y Y2 TM8V W1 Room thermostat or external fossil fuel kit must be used to control fossil fuel...

Page 17: ...5402847 UIM A 0917 Johnson Controls Unitary Products 17 FIGURE 23 Thermostat Chart Two Stage Air Conditioner with Two Stage Variable Speed Furnace A0918 001 TM8V S1 THXU280 W1 TMLV...

Page 18: ...02847 UIM A 0917 18 Johnson Controls Unitary Products FIGURE 24 Thermostat Chart Two Stage Heat Pump with Two Stage Variable Speed Furnace Hot Heat Pump or Conventional TM8V S1 THXU280 W1 A0919 001 TM...

Page 19: ...rate appliance designed to burn solid fuel It is recommended that the appliance is installed in a location where the space temperature is 32 F 0 C or higher If the appliance is installed in a locatio...

Page 20: ...no dimen sion smaller than 0 25 0 64 cm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers sh...

Page 21: ...onal area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the free a...

Page 22: ...ng placed into operation while all other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no bl...

Page 23: ...clocking meter 1 Turn off all other gas appliances and pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note readi...

Page 24: ...Size of Test Dial Seconds For 1 Revolution Size of Test Dial 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346...

Page 25: ...pplies back on and with the burners in operation check for gas leakage around the gas valve pressure port for leakage using an approved non corrosive gas leak detec tion fluid or other non flammable l...

Page 26: ...is dependent upon the panel that covers the blower compartment being in place and properly positioned ROLLOUT SWITCH CONTROLS These controls are mounted on the burner assembly If the temperature in th...

Page 27: ...l run at the speed selected on the FAN SPEED jumpers on the main control board HI COOL LO COOL HI HEAT or LO HEAT When the jumper is in the VS G position the blower will run at 50 of the high cool spe...

Page 28: ...ce will lock out for one hour and then restart 9 RED FLASHES Indicates reversed line voltage polarity grounding problem or reversed low voltage transformer wires Both heating and cooling operations wi...

Page 29: ...3 D A 1013 676 1245 842 1284 842 C C 844 591 1092 765 1130 746 D C HIGH LOW HEAT CFM 060B12 080B12 080C16 Jumper Settings HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Tap ADJ Tap 1111...

Page 30: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft Req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Page 31: ...of flame during call for heat Hot Neutral reversed OR poor ground neutral Gas valve shorted ON Check blower motor wiring Vent OR termination problem None Slow Green Slow Amber Rapid Amber 4 Amber Ste...

Page 32: ...5402847 UIM A 0917 32 Johnson Controls Unitary Products NOTES...

Page 33: ...Equipment and Accessories Owner Information Equipment Data Furnace Configuration Venting B Vent Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Loc...

Page 34: ...Side Continuous Fan PSC Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle Test Operate the furnace through several heating c...

Reviews: