background image

5402847-UIM-A-0917

24

Johnson Controls Unitary Products

ADJUSTMENT OF MANIFOLD GAS PRESSURE & 

INPUT RATE

Inlet and manifold gas pressure may be measured by connecting the
“U” tube manometer to the gas valve with a piece of tubing. Follow the
appropriate section in the instructions below. Refer to Figure 28 for a
drawing of the locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line 
before the gas valve. Find the pressure ports on the gas 
valve marked Out P and In P.

1.

The manifold pressure must be taken at the port marked OUT P.

2.

The gas line pressure must be taken at the port marked IN P.

3.

Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turn-
ing it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.

Read the inlet gas pressure

Connect the positive side of the manometer to the IN P Tap on the gas
valve. Do not connect any tubing to the negative side of the manometer,
as it will reference atmospheric pressure. Refer to Figure 29 for connec-
tion details.

1.

Turn gas and electrical supplies on and follow the operating instruc-
tions to place the unit back in operation.

Table 11: 

Gas Rate (CU FT/HR)

Seconds For 
1 Revolution

Size of Test Dial

Seconds For 
1 Revolution

Size of Test Dial

1 Cu Ft

2 Cu Ft

5 Cu Ft

1 Cu Ft

2 Cu Ft

5 Cu Ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

Table 12: 

Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Propane (LP)

Minimum*

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

Summary of Contents for TM8V C Series

Page 1: ...les All Dimensions in Inches and All Surfaces Identified with the Unit in an Upflow Configuration 4 Coil Projection Dimensions PC Series Coils 6 Cabinet and Duct Dimensions 9 Recommended Filter Sizes...

Page 2: ...provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lift ing points as the tubes may...

Page 3: ...e National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NSCN...

Page 4: ...ide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery o...

Page 5: ...all be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges re...

Page 6: ...furnace A mounting plate supplied with every coil should always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS Dimension C should be at least 2 3 of...

Page 7: ...r installation RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION Return air may enter the furnace through the side s or bottom depend ing on the type of application Return air may not be co...

Page 8: ...mum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the furnace use a se...

Page 9: ...Y END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3 Cabinet and Duct Dimensions BTUH k...

Page 10: ...he type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 15 FIGURE 13 Side Return Cutout Markings IMPORTANT S...

Page 11: ...2742 2743 3048 Gas Heating Value BTU cu ft 800 3 5 3 5 3 5 Gas Heating Value MJ cu m 29 8 0 87 0 87 0 87 850 3 5 3 5 3 5 31 7 0 87 0 87 0 87 900 3 5 3 5 3 5 33 5 0 87 0 87 0 87 950 3 5 3 5 3 3 35 4 0...

Page 12: ...l thermostat and outdoor A C or heat pump using either conventional low voltage 24 VAC thermo stat wiring OR using four wire digital communications wiring To use conventional low voltage wiring see th...

Page 13: ...h may be connected to the FLT SWT terminals on the control board This feature is only functional when used with the Com munication Control It is intended for use with a water overflow switch Auxiliary...

Page 14: ...to Communication Control Installation Man ual LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermost...

Page 15: ...s for all UPG equipment refer to Low Voltage System Wiring document available on line at www upgnet com in the Product Catalog Section FIGURE 21 Thermostat Chart Single Stage Air Conditioner with Two...

Page 16: ...ls Unitary Products FIGURE 22 Thermostat Chart Single Stage Heat Pump with Two Stage Variable Speed Furnace Y Y2 TM8V W1 Room thermostat or external fossil fuel kit must be used to control fossil fuel...

Page 17: ...5402847 UIM A 0917 Johnson Controls Unitary Products 17 FIGURE 23 Thermostat Chart Two Stage Air Conditioner with Two Stage Variable Speed Furnace A0918 001 TM8V S1 THXU280 W1 TMLV...

Page 18: ...02847 UIM A 0917 18 Johnson Controls Unitary Products FIGURE 24 Thermostat Chart Two Stage Heat Pump with Two Stage Variable Speed Furnace Hot Heat Pump or Conventional TM8V S1 THXU280 W1 A0919 001 TM...

Page 19: ...rate appliance designed to burn solid fuel It is recommended that the appliance is installed in a location where the space temperature is 32 F 0 C or higher If the appliance is installed in a locatio...

Page 20: ...no dimen sion smaller than 0 25 0 64 cm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers sh...

Page 21: ...onal area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the free a...

Page 22: ...ng placed into operation while all other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no bl...

Page 23: ...clocking meter 1 Turn off all other gas appliances and pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note readi...

Page 24: ...Size of Test Dial Seconds For 1 Revolution Size of Test Dial 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346...

Page 25: ...pplies back on and with the burners in operation check for gas leakage around the gas valve pressure port for leakage using an approved non corrosive gas leak detec tion fluid or other non flammable l...

Page 26: ...is dependent upon the panel that covers the blower compartment being in place and properly positioned ROLLOUT SWITCH CONTROLS These controls are mounted on the burner assembly If the temperature in th...

Page 27: ...l run at the speed selected on the FAN SPEED jumpers on the main control board HI COOL LO COOL HI HEAT or LO HEAT When the jumper is in the VS G position the blower will run at 50 of the high cool spe...

Page 28: ...ce will lock out for one hour and then restart 9 RED FLASHES Indicates reversed line voltage polarity grounding problem or reversed low voltage transformer wires Both heating and cooling operations wi...

Page 29: ...3 D A 1013 676 1245 842 1284 842 C C 844 591 1092 765 1130 746 D C HIGH LOW HEAT CFM 060B12 080B12 080C16 Jumper Settings HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Tap ADJ Tap 1111...

Page 30: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft Req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Page 31: ...of flame during call for heat Hot Neutral reversed OR poor ground neutral Gas valve shorted ON Check blower motor wiring Vent OR termination problem None Slow Green Slow Amber Rapid Amber 4 Amber Ste...

Page 32: ...5402847 UIM A 0917 32 Johnson Controls Unitary Products NOTES...

Page 33: ...Equipment and Accessories Owner Information Equipment Data Furnace Configuration Venting B Vent Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Loc...

Page 34: ...Side Continuous Fan PSC Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle Test Operate the furnace through several heating c...

Reviews: