397763-YTG-B-0508

Johnson Controls Unitary Products

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnect-

ing line tubing.

2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data 

Table.

4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evapo-

rator + adder for line set.

Additional R-410A Charge / Orifice Size for Various Matched Systems

Outdoor Unit 

THGD18

S41S1

THGD24

S41S1

THGD30

S41S1

THGD36

S41S1

THGD42

S41S1

THGD48

S41S1

THGD60

S41S1

Required Orifice or TXV 

1,2

1TVM0901 1TVM0903 1TVM0903 1TVM0904 1TVM0904 1TVM0905 1TVM0906 

Factory Charge, lbs-oz

6 - 5 

8 - 7 

9 - 12 

9 - 15 

9 - 12 

13 - 9 

13 - 6 

Indoor Coil

3,4

Additional Charge, Oz

FC/MC/PC/UC18AB 

FC/MC/PC/UC24AB 

+ 4 

FC/MC/PC30AB 

FC/MC/PC32A 

FC/MC/PC35BC 

FC/MC/PC37A 

FC/MC/PC43BC 

FC/MC/PC/UC48CD 

10 

0 0 –

FC/MC/PC/UC60CD 

FC/MC62D 

12  0 

HC18A 

1 –

HC30A 

10 0  –

HC36B 

HC42 

0 0 0 –

HC60 

HD24 

14 

HD36 

HD48 

+ 8 

+ 8 

HD60 

AHP18 

0 –

AHP30 

0 –

AHP36 

AHP/SHP48 

AHP/SHP60 

AV24 

AV36 

6 0 0 –

AV/SV48 

AV/SV60 

0  –

F4FP24     

F4FP30     

F4FP40     

F4FP45     

F5FP48     

F4FV60     

F5FP60     

FOOTNOTES:

1. For applications requiring a TXV use 1TVM900 series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

See  Caution below   

See  Caution below   

See  Caution below   

See  Caution below   

See  Caution below   

See  Caution below   

See  Caution below   

F*FP Air Handlers come with a factory installed R-22 TXV which MUST BE CHANGED OUT to R-410A TXV or an orifice for proper opera-
tion. If the TXV is not changed out system damage will occur.

Summary of Contents for THGD18 THRU 60

Page 1: ...ating conditions occur A liquid line filter drier further protects the compres sor DURABLE FINISH The cabinet is made of pre painted steel The pre treated galvanized steel provides a better paint to s...

Page 2: ...850 Nominal CFM 2200 2900 3100 3800 3200 3000 3000 Coil Face Area Sq Ft 15 7 18 3 21 0 23 58 23 58 23 58 23 58 Rows Deep 1 1 1 1 1 2 2 Fin Inches 22 22 22 22 22 18 18 Liquid Line Set OD Field Installe...

Page 3: ...0905 1TVM0906 Factory Charge lbs oz 6 5 8 7 9 12 9 15 9 12 13 9 13 6 Indoor Coil3 4 Additional Charge Oz FC MC PC UC18AB 0 FC MC PC UC24AB 4 0 FC MC PC30AB 0 FC MC PC32A 0 0 FC MC PC35BC 0 0 FC MC PC3...

Page 4: ...0 47 0 35 6 13 00 11 00 THGD60S41S1 MA20D 24 MC62D 1800 54 0 42 5 13 00 11 00 13 SEER HP WITH MV VARIABLE SPEED THGD18S41S1 MV12B 17 FC MC PC18B 600 17 0 12 9 14 00 12 00 MV12B 17 FC MC PC24B 600 17 0...

Page 5: ...8 13 00 11 00 THGD42S41S1 AHP SHP48 21 1400 41 5 31 4 13 00 11 00 F4FP045 24 1400 41 0 31 2 13 00 11 00 F5FP048 24 1450 41 0 32 6 13 00 11 00 THGD48S41S1 AHP SHP60 24 1600 47 0 36 0 14 00 11 50 F5FP0...

Page 6: ...0 17 21 FC MC PC43 1000 29 0 23 4 13 00 11 00 800 1200 17 HC36 1000 29 0 23 2 13 00 11 00 800 1200 21 HC42 1000 29 0 23 4 13 00 11 00 800 1200 21 24 HD48 1000 29 0 23 4 13 00 11 00 THGD36S41S1 1000 14...

Page 7: ...V 9 B12 FC MC PC30B 17 800 23 0 17 5 14 00 12 00 PV8 A12 FC MC PC32A 14 750 23 0 17 4 14 00 12 00 PV9 A12 FC MC PC32A 14 800 23 0 17 7 14 00 12 00 P C V 9 B12 FC MC PC35B 17 800 23 0 17 8 14 00 12 00...

Page 8: ...50 P C V 9 C20 HC42C 21 1200 35 0 27 2 13 50 11 50 PV8 C16 HD48C 21 1200 35 0 27 2 13 50 11 50 PV8 C20 HD48C 21 1200 35 0 27 2 13 50 11 50 P C V 9 C16 HD48C 21 1200 35 0 27 2 13 50 11 50 P C V 9 C20 H...

Page 9: ...HD60C 21 1600 47 0 35 4 14 00 11 50 P C V 9 C16 HD60C 21 1600 47 0 35 4 13 00 11 00 P C V 9 C20 HD60C 21 1600 47 0 35 4 14 00 11 50 P C V 9 D20 HD60D 24 1550 47 0 35 6 14 00 11 50 PV8 C20 MC62C 21 16...

Page 10: ...3 83 8 00 MA20D MC62D 50 5 3 38 4 38 30 6 2 28 3 93 8 00 THGD60S41S1 MA20D MC62D 56 5 3 48 4 76 35 4 2 42 4 29 8 00 13 SEER HP WITH MV VARIABLE SPEED THGD18S41S1 MV12B FC MC18B 16 7 3 52 1 39 12 7 3...

Page 11: ...SHP F FP THGD18S41S1 AHP18 17 0 3 38 1 47 8 2 2 16 1 11 7 70 F4FP24 17 0 3 34 1 49 12 5 3 04 1 21 7 70 THGD24S41S1 AHP30 23 2 3 40 2 00 12 6 2 24 1 65 7 70 F4FP030 23 2 3 40 2 00 12 6 2 24 1 65 7 70...

Page 12: ...28 0 3 34 2 46 16 4 2 28 2 11 7 70 FC MC PC35 28 0 3 34 2 46 16 4 2 30 2 09 7 70 FC MC PC37 28 2 3 40 2 43 16 6 2 32 2 10 7 70 FC MC PC43 28 2 3 40 2 43 16 6 2 32 2 10 7 70 HC36 28 2 3 34 2 47 16 4 2...

Page 13: ...1 45 8 00 PV8 A12 FC MC PC32A 22 6 3 72 1 78 12 4 2 50 1 45 8 00 PV9 A12 FC MC PC32A 23 0 3 72 1 81 12 4 2 50 1 45 8 00 P C V 9 B12 FC MC PC35B 22 8 3 72 1 80 12 4 2 50 1 45 8 00 P C V 9 C16 FC MC PC...

Page 14: ...V 9 C20 HC42C 35 0 3 54 2 90 20 8 2 44 2 50 8 00 PV8 C16 HD48C 35 0 3 40 3 02 19 4 2 26 2 52 8 00 PV8 C20 HD48C 35 0 3 40 3 02 19 4 2 28 2 49 8 00 P C V 9 C16 HD48C 35 0 3 40 3 02 19 5 2 24 2 55 8 00...

Page 15: ...V 9 D20 HC60D 50 5 3 58 4 13 30 2 2 38 3 72 8 00 PV8 C16 HD60C 49 5 2 94 4 93 30 4 2 04 4 37 8 00 PV8 C20 HD60C 49 5 3 02 4 80 30 4 2 08 4 28 8 00 P C V 9 C16 HD60C 50 0 2 98 4 92 30 6 2 06 4 35 8 00...

Page 16: ...refer to the price book or consult factory SOUND POWER RATINGS Rated in accordance with ARI 270 95 Standards TYPICAL INSTALLATION TYPICAL FIELD WIRING UNIT MODEL dBA Cooling Heating 018 TBD TBD 024 T...

Page 17: ...4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 105 T C 13 2 13 6 13 4 15 2 17 0 14 7 14 9 14 2 16 0 17 9 16 3 16 3 15 0 16 7 18 7 S C 11 9 11 3 9 6 9 7 7 8 13 3 13 0 11 3 11 5 8 9 14 8 14 8 13 1 13 3 1...

Page 18: ...21 8 21 5 20 8 23 2 25 5 S C 17 6 16 7 14 3 14 4 11 7 19 2 18 6 16 2 16 4 12 8 20 8 20 5 18 1 18 4 13 9 KW 1 9 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 1 115 T C 17 1 17 3 17 4 19 6 21 5...

Page 19: ...5 2 5 115 T C 21 0 21 3 20 9 23 4 26 4 22 3 22 3 21 3 24 0 26 9 23 6 23 4 21 8 24 5 27 4 S C 21 2 20 8 17 7 17 7 13 9 22 5 22 2 19 3 19 7 15 0 23 9 23 6 20 9 21 8 16 1 KW 2 5 2 5 2 5 2 6 2 7 2 6 2 6 2...

Page 20: ...5 2 19 7 32 0 31 8 27 1 27 0 20 7 KW 2 9 3 0 3 0 3 0 3 1 3 0 3 0 3 0 3 0 3 1 3 0 3 0 3 0 3 0 3 1 115 T C 27 8 27 6 27 5 30 7 34 0 29 3 29 1 28 1 31 5 34 9 30 8 30 5 28 7 32 3 35 8 S C 26 9 25 7 22 1 2...

Page 21: ...4 7 33 4 28 0 27 8 21 7 36 1 35 3 30 1 29 8 22 8 37 5 37 1 32 3 31 9 23 8 KW 3 6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 7 3 7 115 T C 31 1 31 3 30 6 33 8 37 1 32 2 32 3 31 3 34 4 37 5 33 4...

Page 22: ...9 35 3 26 6 KW 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 4 0 115 T C 36 4 35 9 35 9 39 3 43 3 37 5 37 0 36 3 39 8 43 7 38 5 38 1 36 8 40 4 44 1 S C 37 2 35 7 30 7 30 4 23 4 38 3 37 3 32...

Page 23: ...7 52 6 58 0 63 4 S C 51 6 48 6 40 7 40 5 32 2 53 2 51 1 42 8 42 5 33 4 54 9 53 6 44 9 44 6 34 7 KW 3 6 3 6 3 6 3 6 3 7 3 6 3 6 3 6 3 7 3 7 3 6 3 6 3 6 3 7 3 7 95 T C 47 6 48 1 48 1 53 1 58 3 49 0 48...

Page 24: ...8 1 2 2 2 9 2 1 2 2 2 9 7 1 3 2 2 10 60 6 1 1 1 1 6 6 7 1 2 1 6 7 3 1 3 1 7 70 6 2 1 1 1 6 7 1 1 2 1 7 8 0 1 3 1 8 80 6 2 1 1 1 6 7 4 1 2 1 8 8 6 1 3 2 0 NOTE ALL CAPACITIES ARE NET KBTUH WITH INDOOR...

Page 25: ...9 1 6 1 9 10 6 1 6 1 9 80 8 0 1 5 1 6 8 6 1 6 1 6 9 3 1 6 1 7 NOTE ALL CAPACITIES ARE NET KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP FC MC PC24 1 00...

Page 26: ...Handler Coil MBH KW COP FC MC PC32 0 99 0 98 1 01 FC MC PC35 0 99 0 98 1 01 FC MC PC37 1 00 1 00 1 00 FC MC PC43 1 00 1 00 1 00 HC36 0 99 0 98 1 01 HC42 1 00 1 00 1 00 HD48 1 34 1 40 0 96 AHP36 1 00...

Page 27: ...LL CAPACITIES ARE NET KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP FC MC PC37 1 01 1 01 1 00 FC MC PC43 1 01 1 01 1 00 FC MC PC48 1 01 1 01 1 00 HC42 1...

Page 28: ...8 3 0 2 4 26 6 3 0 2 6 28 4 3 0 2 8 NOTE ALL CAPACITIES ARE NET KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP FC MC PC60 1 00 1 06 0 94 HC42 0 99 0 99 1...

Page 29: ...KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP FC MC PC48 1 00 0 95 1 04 FC MC PC60 1 00 1 02 0 99 HC60 1 00 1 02 0 99 HD60 0 98 0 85 1 16 MC62 1 00 0 9...

Page 30: ...8 3 4 56 3 4 8 3 5 56 8 4 7 3 5 80 54 7 5 2 3 1 55 2 5 2 3 1 55 6 5 1 3 2 40 60 51 9 4 3 3 5 51 7 4 3 3 5 51 4 4 3 3 5 70 50 6 4 8 3 1 51 1 4 7 3 2 51 7 4 7 3 2 80 49 3 5 2 2 8 50 6 5 1 2 9 51 9 5 0 3...

Reviews: