397763-YTG-B-0508
12
Johnson Controls Unitary Products
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.
HEATING PERFORMANCE - Upflow, Downflow, and Horizontal Furnaces and Coils
UNIT
MODEL*
COIL
1
MODEL
ARI HEATING
2
47
°
F
17
°
F
HSPF
MBH
COP
KW
MBH
COP
KW
STD
THGD18S41S1
FC/MC/PC/UC1
17.0 3.32 1.50 12.7 3.00 1.24 7.70
FC/MC/PC/UC2
17.0 3.44 1.45 10.4 2.60 1.17 7.70
HC18
17.0 3.32 1.50 12.7 3.00 1.24 7.70
HC30
17.0 3.38 1.47 10.4 2.60 1.17 7.70
HD24
16.6 3.16 1.54 12.8 3.00 1.25 7.70
THGD24S41S1
FC/MC/PC24
23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC30
23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC32
23.2 3.40 2.00 12.6 2.24 1.65 7.70
FC/MC/PC35
23.2 3.40 2.00 12.6 2.24 1.65 7.70
HC30
23.0 3.40 1.98 12.6 2.24 1.65 7.70
HC36
23.2 3.40 2.00 12.6 2.24 1.65 7.70
HD36
23.2 3.40 2.00 12.6 2.24 1.65 7.70
THGD30S41S1
FC/MC/PC32
28.0 3.34 2.46 16.4 2.28 2.11 7.70
FC/MC/PC35
28.0 3.34 2.46 16.4 2.30 2.09 7.70
FC/MC/PC37
28.2 3.40 2.43 16.6 2.32 2.10 7.70
FC/MC/PC43
28.2 3.40 2.43 16.6 2.32 2.10 7.70
HC36
28.2 3.34 2.47 16.4 2.28 2.11 7.70
HC42
28.2 3.40 2.43 16.6 2.32 2.10 7.70
HD48
28.2 3.60 2.30 16.6 2.32 2.10 7.70
THGD36S41S1
FC/MC/PC37
35.0 3.40 3.02 21.2 2.36 2.63 8.00
FC/MC/PC43
35.0 3.42 3.00 21.2 2.36 2.63 8.00
FC/MC/PC48
35.0 3.42 3.00 21.4 2.36 2.66 8.00
HC42
35.0 3.42 3.00 21.2 2.36 2.63 8.00
HD48
35.0 3.40 3.02 20.0 2.16 2.71 8.00
THGD42S41S1
FC/MC/PC48
41.0 3.48 3.45 28.0 2.46 3.34 8.00
FC/MC/PC60
41.0 3.66 3.28 27.8 2.56 3.18 8.00
HC42
41.0 3.46 3.47 27.8 2.48 3.29 8.00
HC60
41.0 3.66 3.28 27.8 2.56 3.18 8.00
HD60
41.0 3.14 3.83 27.6 2.26 3.58 8.00
THGD48S41S1
FC/MC/PC48
50.5 3.32 4.46 30.8 2.24 4.03 8.00
FC/MC/PC60
51.0 3.50 4.27 30.6 2.34 3.83 8.00
HC60
51.0 3.50 4.27 30.6 2.34 3.83 8.00
HD60
50.0 2.98 4.92 30.6 2.06 4.35 8.00
MC62
50.5 3.38 4.38 30.6 2.28 3.93 8.00
THGD60S41S1
MC62
56.5 3.48 4.76 35.4 2.42 4.29 8.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.