Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO.
THGD42S41S1
INDOOR COIL MODEL NO.
FC/MC/PC48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1200
1400
1600
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
39.7 42.2 42.3 46.6 50.3 41.4 43.0 43.0 47.1 51.6 43.2 43.9 43.7 47.7 52.9
S.C.
41.5 37.8 32.1 32.0 25.7 43.3 41.1 34.2 33.9 27.1 45.1 44.5 36.3 35.8 28.4
KW
2.4 2.4 2.5 2.5 2.4 2.4 2.4 2.5 2.5 2.4 2.5 2.5 2.4 2.5 2.5
75
T.C.
38.3 40.2 40.3 44.3 48.1 39.9 41.0 41.0 44.9 49.1 41.6 41.9 41.7 45.6 50.2
S.C.
40.0 36.9 31.2 31.0 24.8 41.7 39.9 33.3 33.0 26.1 43.4 42.8 35.4 34.9 27.3
KW
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
85
T.C.
36.9 38.2 38.2 41.9 45.8 38.4 39.0 39.0 42.7 46.7 40.0 39.9 39.7 43.5 47.5
S.C.
38.5 36.0 30.2 30.0 23.9 40.2 38.6 32.3 32.0 25.1 41.8 41.2 34.5 34.1 26.2
KW
2.9 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
95
T.C.
35.4 36.1 36.2 39.6 43.5 36.9 37.0 36.9 40.5 44.2 38.4 37.9 37.7 41.4 44.9
S.C.
37.0 35.1 29.2 29.0 23.0 38.6 37.3 31.4 31.1 24.1 40.1 39.6 33.5 33.2 25.1
KW
3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.3 3.3
105
T.C.
33.2 33.7 33.4 36.7 40.2 34.5 34.6 34.1 37.4 40.8 35.9 35.5 34.8 38.1 41.4
S.C.
34.7 33.4 28.0 27.8 21.7 36.1 35.3 30.1 29.8 22.8 37.5 37.1 32.3 31.9 23.8
KW
3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.7 3.7
115
T.C.
31.1 31.3 30.6 33.8 37.1 32.2 32.3 31.3 34.4 37.5 33.4 33.2 32.0 34.9 37.9
S.C.
32.5 31.8 26.8 26.6 20.4 33.7 33.3 28.9 28.6 21.5 34.9 34.7 31.0 30.6 22.6
KW
4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1
125
T.C.
28.9 28.9 27.9 31.0 33.9 29.9 29.9 28.5 31.4 34.2 30.9 30.9 29.2 31.7 34.5
S.C.
30.2 30.2 25.5 25.4 19.1 31.3 31.3 27.7 27.4 20.2 32.3 32.3 29.8 29.4 21.3
KW
4.5 4.4 4.4 4.4 4.5 4.4 4.4 4.4 4.4 4.5 4.4 4.4 4.4 4.4 4.5
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC60
0.99 0.99 1.00
–
HC42
1.00 0.99 1.00
–
HC60
0.99 0.99 1.00
–
HD60
1.01 1.00 1.00
AV48
–
1.01 1.02 1.00
F4FP045
–
0.99 1.00 1.00
F5FP048
–
1.02 1.04 1.00
AHP/SHP48
–
1.00
1.00
1.00
MA14D
FC/MC/PC48D
1.00 1.00 1.00
MA16C
FC/MC/PC48C
1.00 1.00 1.00
MV16C
FC/MC/PC48C
1.02 1.02 1.00
MV20D
FC/MC/PC48D
1.02 1.02 1.00
MA14D
FC/MC/PC60D
0.99 0.99 1.00
MA16C
FC/MC/PC60C
0.99 0.99 1.00
MV20D
FC/MC/PC60D
1.01 1.01 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
PV8*C16
FC/MC/PC48C 1.01
1.01
1.00
PV8*C20
FC/MC/PC48C 1.02
1.01
1.00
P(C,V)9*C16
FC/MC/PC48C 1.01
1.01
1.00
P(C,V)9*C20
FC/MC/PC48C 1.02
1.01
1.00
P(C,V)9*D20
FC/MC/PC48D 1.02
1.01
1.00
PV8*C16
FC/MC/PC60C 1.00
1.00
1.00
PV8*C20
FC/MC/PC60C 1.00
1.01
1.00
P(C,V)9*C16
FC/MC/PC60C 1.00
1.00
1.00
P(C,V)9*C20
FC/MC/PC60C 1.00
1.00
1.00
P(C,V)9*D20
FC/MC/PC60D 1.01
1.01
1.00
PV8*C16
HC42C 1.01
1.00
1.00
PV8*C20
HC42C 1.01
1.00
1.00
P(C,V)9*C16
HC42C 1.01
1.00
1.00
P(C,V)9*C20
HC42C 1.01
1.00
1.00
P(C,V)9*D20
HC60D 1.01
1.01
1.00
PV8*C16
HD60C 1.02
1.01
1.00
PV8*C20
HD60C 1.02
1.01
1.00
P(C,V)9*C16
HD60C 1.01
1.01
1.00
P(C,V)9*C20
HD60C 1.02
1.01
1.00
P(C,V)9*D20
HD60D 1.02
1.02
1.00