background image

PILOT CHECKOUT

The pilot flame should envelope 3/8 inches of the end of the

flame sensor. Refer to Figure 12. To adjust pilot flame, (1)

remove pilot adjustment cover screw, (2) adjust the screw for

the proper pilot flame, (3) be sure to replace cover screw after

adjustment to prevent possible gas leakage.

Put the system into operation and observe through complete

cycle to be sure all controls function properly.

BURNER INSTRUCTIONS

To check or change burners, pilot or orifices, CLOSE MAIN

MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER

TO THE UNIT.

1. Remove the two screws holding either end of the manifold

to the burner supports.

2. Open the union fitting in the gas supply line just upstream of

the unit gas valve and downstream from the main manual

shut-off valve.

3. Remove the gas piping patch plate.

4. Disconnect wiring to the gas valve and spark ignitor.

Remove the manifold-burner gas valve assembly by lifting

up and pulling back.

Burners are now accessible for service.

Reverse the above procedure to replace the assembly. Make

sure that burners are level and seat at the rear of the heat

exchanger.

BURNER AIR SHUTTER ADJUSTMENT

Adjust burner shutters so that a distinct, sharp, blue flame is

obtained. Refer to Figure 13.

SUPPLY AIR AIR BLOWER AND TEMPERATURE

RISE ADJUSTMENTS

The speed of the supply air blower will depend on the required

CFM, the unit accessories and the static resistances of both the

supply and the return air duct systems. With this information,

the speed for the supply air blower can be determined from the

blower performance and accessory static resistance data in

Table 5 through 8.

Knowing the required blower RPM and the blower motor HP,

the speed setting for the supply air motor can be determined.
The setting (turns open) for the optional belt-drive supply air

motor pulley can be determined from Table 13.

OPTIONAL BELT-DRIVE BLOWER
All units with belt-drive blowers have single speed motors. The

variable pitch pulley on the blower motor can be adjusted to

obtain the desired supply air CFM. Refer to Table 9 for blower

motor and drive data. The tension on the belts should be

adjusted as shown in Figure 14.

Start the supply air blower motor. Adjust the resistances in both

the supply and the return air duct systems to balance the air

distribution throughout the conditioned space. The job

specifications may require that this balancing be done by

someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been

completed:

1. Remove the (two)

#

$

" dot plugs from the holes located on

the filter access panel side of the unit.

2. Insert at least 8" of 1/4 inch tubing into each of these holes

for sufficient penetration into the air flow on both sides of

the evaporator coil.

Unitary Products Group

15

035-14832-003-A-0204

FIG. 12

- PROPER FLAME ADJUSTMENT

FIG. 13

- TYPICAL FLAME APPEARANCE

TURNS

OPEN*

BLOWER DRIVE RANGE (RPM)

3 TON

4 TON

5 TON

5

4

3

2

1

0

780

842

904

966

1028

1090

790

856

922

988

1054

1120

850

924

998

1072

1246

1220

*

Pulley can be adjusted in half-turn increments.

TABLE 13

- BELT-DRIVE SUPPLY AIR

MOTOR PULLEY ADJUSTMENT

SPAN LENGTH

DEFL FORCE

* NEVER LOOSEN

(A)

(C)*

(D)

CAUTION

Procedure for adjusting belt tension:

1. Loosen nut (D) from the motor mount.

2. Never loosen nuts (C) from each other while loosening nut (D).

3. Adjust the tension by turning bolt (B).

4. Do not loosen the four nuts (top and bottom) (A); unless additional tensioning

distance is required; immediately re-tighten these bolts if loosened.

5. Use a belt tension checker to apply a perpendicular force to one belt at the

midpoint of the span as shown. The deflection force should be applied

until a specific deflection distance of 4mm (5/32")is obtained. To determine

the deflection distance from normal position, use a straight edge from

sheave to sheave as a reference line. The recommended deflection force

is as follows:

Tension new belts at the max. deflection force recommended for the belt

section. Check the belt tension at least two times during the first 24 hours of

operation. Any re-tensioning should fall between the min. and max.

deflection force values.
6. After adjusting, re-tighten nut (D) against the motor mount taking care not

to loosen nuts (C).

(B)

FIG. 14

- BELT ADJUSTMENT

Summary of Contents for SUNLINE PLUS D2EG 048

Page 1: ...g of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 Forinstallationdirectlyoncombustibleflooringor intheU S A on wood flooring or Class A B or ...

Page 2: ...Air Conditioner Air Cooled PRODUCT IDENTIFIER EG High Efficiency Gas Electric VOLTAGE CODE 06 208 230 1 60 25 208 230 3 60 46 460 3 60 58 575 3 60 NOMINAL GAS HEATING OUTPUT CAPACITY 036 3 Ton 048 4 Ton 060 5 Ton 0 0 3 0 6 2 5 FACTORY INSTALLED HEAT N Natural Gas NOMINAL COOLING CAPACITY 040 40 MBH 060 60 MBH 079 79 MBH 099 99 MBH MAINTENANCE TROUBLESHOOTING Normal Maintenance 17 Cleaning Flue Pas...

Page 3: ...Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units...

Page 4: ...sign certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized...

Page 5: ...U N I T H A S A N E C O N O M I Z E R R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D T H E E C O N O M I Z E R I F Y O U W A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C ...

Page 6: ...that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 48kPa 7 A 1 8 inch NPT plugged tapping accessible for test gage connection must be installed immediately upstream of t...

Page 7: ...er 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B provided...

Page 8: ...13 5 1 COND FAN PROPELLER DIA in FAN MOTOR HP NOM CFM TOTAL 22 4 500 22 4 200 22 4 500 COND COIL ROWS DEEP FINS PER INCH FACE AREA Sq Ft 2 18 17 1 2 18 17 1 2 18 17 1 AIR FILTERS SEE NOTE QUANTITY PER UNIT 14 x 20 x 1 QUANTITY PER UNIT 14 X 25 X 1 TOTAL FACE AREA sq ft 2 1 6 3 2 1 6 3 2 1 6 3 CHARGE REFRIGERANT 22 lbs oz 9 12 9 8 9 8 COMPRESSOR QUANTITY PER UNIT HERMETIC TYPE 1 RECPT 1 RECPT 1 SCR...

Page 9: ...53 780 992 815 1034 855 1080 905 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 1 FILTERS AND THE GAS FIRED HEAT EXCHANGERS REFER TO TABLE 8 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watt...

Page 10: ...815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON SIDE DUCT CONNECTIONS 230 460 575 Volts MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 115...

Page 11: ...6 3 4 9 135 130 64 52 0 2 3 2 3 1 4 1 4 5 0 5 0 2 2 2 2 38 6 25 7 13 2 11 4 60 40 20 15 60 40 20 15 060 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 32 1 19 3 10 0 7 9 135 150 73 50 2 3 2 3 1 4 1 4 6 6 6 6 3 3 3 3 49 0 33 0 17 2 14 6 80 50 25 20 80 50 25 20 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 10 ELECTRI...

Page 12: ...r motorized Air Damper Left Side Filter Access 24 Less Economizer 36 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 For Condenser Air Discharge 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet NOTE A ...

Page 13: ...lose and the blower motor operates INTERMITTENT BLOWER With the room thermostat system switch set to the AUTO or HEAT position and the fan switch set to AUTO the supply air blower will operate after the room thermostat calls for heat and the air in the gas heat compartment has achieved a pre set temeprature When TH1 on the thermostat closes the draft motor relay DMR or DMC is energized The DMR or ...

Page 14: ...e same as listed on the unit nameplate 2 Make sure that the vent and combustion air hoods have been properly installed 14 Unitary Products Group 035 14832 003 A 0204 Units Tons Capacity MBH Limit Control Opens F Input Output 3 4 3 4 5 5 50 75 100 125 100 125 40 60 79 99 79 99 165 165 165 165 165 165 TABLE 12 LIMIT CONTROL SETTING OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an inte...

Page 15: ...red supply air CFM Refer to Table 9 for blower motor and drive data The tension on the belts should be adjusted as shown in Figure 14 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equi...

Page 16: ...rom Table 14 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it var...

Page 17: ...harge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge The manufacture recommends that the furnace system be inspected once a year by a qualified service person CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need c...

Page 18: ... DMC is pulled in d If the DMR or DMC relay is pulled in check for a loose line voltage connection e If the DMR or DMC relay is not pulled in check for 24 volts at the DMR or 24 volts at TMC G terminal coil If 24 volts is present replace the DMR or DMC relay If 24 volts is not present check for a loose 24 volt connec tion back to the relay board and check the connections from the room thermostat t...

Page 19: ...volts across terminals MV and COMMON terminals If no voltage is detected replace the ignitor control If voltage is pres ent replace the gas valve 8 Furnace lights with roll out or one burner has delayed igni tion a Make sure that the pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level...

Page 20: ... 0204 Supersedes 035 14832 002 A 0302 Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved ...

Reviews: