background image

COOLING SYSTEM

The cooling section is a complete factory package utilizing an

air-cooled condenser. The system is factory-charged with

Refrigerant-22.

The compressor is hermetically sealed and internally sprung.

The compressors have inherent (internal) protection. If there is

an abnormal temperature rise in the compressor, the protector

will open to shut down the compressor.

PRELIMINARY OPERATION COOLING

After the installation has been completed, energize the

crankcase heater (3 ton only) for at least 4 hours before

operating the unit. After this initial warm-up, the compressor

should be given three false starts (energized just long enough

to make a few revolutions) with a 5 minute delay between each

start before being put into full time service.

NOTE: Prior to each cooling season, the crankcase heater (3

ton only) must be energized at least 10 hours before

the system is put into operation.

COOLING SEQUENCE OF OPERATION

Single-Stage Cooling: When the thermostat calls for “cooling”,

“R” is closed to “G” and “Y1" (wiring schematic) which

completes the low voltage control circuit, immediately

energizing the compressor, condenser fan motor and blower

motor simultaneously.

Two-Stage Cooling: A two-stage cooling thermostat may be

used if the unit has an economizer. First-stage cooling is

provided by the economizer - if the outdoor air enthalpy is

acceptable, and second-stage cooling is provided by the

compressor. Jumper wire J1 must be removed. Refer to the

unit wiring diagram.

After the thermostat is satisfied and opens, the blower will

continue to run for a short time. All other components will stop.

CONTINUOUS BLOWER - Continuous blower operation is

possible by closing the R to G circuit on the thermostat.

SAFETY CONTROLS (Cooling)

The refrigerant system is equipped wth the following safety

controls:

1. A Suction Line Freezestat to protect against low evapora-

tor temperature due to low air flow or a low return air tem-

perature.

2. AHigh Pressure Cutout Switch to protect against excessive

discharge pressures due to a blocked condenser coil or a

condenser motor failure.

3. A Low Pressure Switch to protect against loss of refrigerant

charge.

If neither one of the above safety controls opens, the refrigerant

system will be locked out. The lock out of the system can be

reset by opening the 24V circuit either at the room thermostat

or at the unit disconnect.

HEATING SEQUENCE OF OPERATION

The following sequence describes the operation of the gas

heat section.

CONTINUOUS BLOWER: With the room thermostat switch

set to “ON”, the supply air blower will operate continuously. The

normally closed blower interlock relay contact “K3-1" provides

24 volt power to the blower relay ”BR". The “BR” power

contacts close and the blower motor operates.
INTERMITTENT BLOWER: With the room thermostat system

switch set to the “AUTO” or “HEAT” position and the fan switch

set to “AUTO”, the supply air blower will operate after the room

thermostat calls for heat and the air in the gas heat

compartment has achieved a pre-set temeprature.
When “TH1" on the thermostat closes, the draft motor relay

”DMR" or “DMC” is energized. The “DMR” or “DMC” power

contacts close which energizes the line voltage draft motor. As

the speed of the draft motor reaches approximately 2500 RPM,

the centrifugal switch contact “CS” located on the end of the

draft motor shaft closes to power the ignition control “IC”.
After 15 seconds the “IC” will start the ignitor sparking and will

open the redundant valve locted inside the main gas valve

“GV” to allow a flow of gas to only the carryover tube. See

Figure 10. Only after the pilot flame has been ignited and the

presence of pilot flame detected at the “IC” by a signal sent

back through the flame sensor is sparking terminated and the

main gas valve opened.

Gas flows into each of the main burners and is ignited from the

carryover tube flame.

The “IC” will try for 85 seconds to ignite the pilot carryover tube.

If the “IC” fails to detect a pilot flame during the 85 seconds, it

will close the redundant valve. After a 5 minute purge period,

the “IC” will again try to light the pilot carryover tube. This will

continue continuously until the “IC” detects a pilot flame.

If, after detecting a pilot flame and opening the main gas valve,

the “IC” looses pilot flame indication, it will close both the main

and redundant gas valves. The “IC” will start the above

sequence over until a pilot flame is detected and it will open the

main gas valve again.

The “IC” will only allow 16 pilot flameouts and a single rollout

switch opening per thermostat cycle. After 16 pilot flameouts or

a single rollout switch opening, the “IC” closes both the main

and redundant gas valves. The “IC” requires resetting the

thermostat or removal of it's power lead coming from the draft

motor to reset the “IC” and return it to the above sequence of

operation.

At the same time power was supplied to the “DMR” or “DMC”, a

parallel circuit activates the time delay relay “BT” or “ETD”. The

“BT” or “ETD” closes in approximetly 35 seconds and starts the

circulating air blower by energizing the blower interlock relay

“K3", thus closing the ”K3-2" contact and energizing the blower

relay “BR”.

When the heating cycle is complete, “TH-1" opens de-

energizing the “IC”, thus closing the redundant and main gas

valves. The blower motor and the draft motor continue to run

for a short period after the furnace is shut down until the “BT” or

“ETD” opens (in approximately 25 seconds) de-energizing the

“K3", ”BR" and “DMR” or “DMC” relays.

Unitary Products Group

13

035-14832-003-A-0204

OPERATION

GAS
VALVE

GAS MAIN

MAIN VALVE

TO MAIN
BURNER

REDUNDANT
VALVE

TO PILOT BURNER

FIG. 10

- GAS VALVE PIPING

Summary of Contents for SUNLINE PLUS D2EG 048

Page 1: ...g of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 Forinstallationdirectlyoncombustibleflooringor intheU S A on wood flooring or Class A B or ...

Page 2: ...Air Conditioner Air Cooled PRODUCT IDENTIFIER EG High Efficiency Gas Electric VOLTAGE CODE 06 208 230 1 60 25 208 230 3 60 46 460 3 60 58 575 3 60 NOMINAL GAS HEATING OUTPUT CAPACITY 036 3 Ton 048 4 Ton 060 5 Ton 0 0 3 0 6 2 5 FACTORY INSTALLED HEAT N Natural Gas NOMINAL COOLING CAPACITY 040 40 MBH 060 60 MBH 079 79 MBH 099 99 MBH MAINTENANCE TROUBLESHOOTING Normal Maintenance 17 Cleaning Flue Pas...

Page 3: ...Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units...

Page 4: ...sign certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized...

Page 5: ...U N I T H A S A N E C O N O M I Z E R R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D T H E E C O N O M I Z E R I F Y O U W A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C ...

Page 6: ...that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 48kPa 7 A 1 8 inch NPT plugged tapping accessible for test gage connection must be installed immediately upstream of t...

Page 7: ...er 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B provided...

Page 8: ...13 5 1 COND FAN PROPELLER DIA in FAN MOTOR HP NOM CFM TOTAL 22 4 500 22 4 200 22 4 500 COND COIL ROWS DEEP FINS PER INCH FACE AREA Sq Ft 2 18 17 1 2 18 17 1 2 18 17 1 AIR FILTERS SEE NOTE QUANTITY PER UNIT 14 x 20 x 1 QUANTITY PER UNIT 14 X 25 X 1 TOTAL FACE AREA sq ft 2 1 6 3 2 1 6 3 2 1 6 3 CHARGE REFRIGERANT 22 lbs oz 9 12 9 8 9 8 COMPRESSOR QUANTITY PER UNIT HERMETIC TYPE 1 RECPT 1 RECPT 1 SCR...

Page 9: ...53 780 992 815 1034 855 1080 905 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 1 FILTERS AND THE GAS FIRED HEAT EXCHANGERS REFER TO TABLE 8 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watt...

Page 10: ...815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON SIDE DUCT CONNECTIONS 230 460 575 Volts MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 115...

Page 11: ...6 3 4 9 135 130 64 52 0 2 3 2 3 1 4 1 4 5 0 5 0 2 2 2 2 38 6 25 7 13 2 11 4 60 40 20 15 60 40 20 15 060 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 32 1 19 3 10 0 7 9 135 150 73 50 2 3 2 3 1 4 1 4 6 6 6 6 3 3 3 3 49 0 33 0 17 2 14 6 80 50 25 20 80 50 25 20 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 10 ELECTRI...

Page 12: ...r motorized Air Damper Left Side Filter Access 24 Less Economizer 36 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 For Condenser Air Discharge 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet NOTE A ...

Page 13: ...lose and the blower motor operates INTERMITTENT BLOWER With the room thermostat system switch set to the AUTO or HEAT position and the fan switch set to AUTO the supply air blower will operate after the room thermostat calls for heat and the air in the gas heat compartment has achieved a pre set temeprature When TH1 on the thermostat closes the draft motor relay DMR or DMC is energized The DMR or ...

Page 14: ...e same as listed on the unit nameplate 2 Make sure that the vent and combustion air hoods have been properly installed 14 Unitary Products Group 035 14832 003 A 0204 Units Tons Capacity MBH Limit Control Opens F Input Output 3 4 3 4 5 5 50 75 100 125 100 125 40 60 79 99 79 99 165 165 165 165 165 165 TABLE 12 LIMIT CONTROL SETTING OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an inte...

Page 15: ...red supply air CFM Refer to Table 9 for blower motor and drive data The tension on the belts should be adjusted as shown in Figure 14 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equi...

Page 16: ...rom Table 14 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it var...

Page 17: ...harge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge The manufacture recommends that the furnace system be inspected once a year by a qualified service person CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need c...

Page 18: ... DMC is pulled in d If the DMR or DMC relay is pulled in check for a loose line voltage connection e If the DMR or DMC relay is not pulled in check for 24 volts at the DMR or 24 volts at TMC G terminal coil If 24 volts is present replace the DMR or DMC relay If 24 volts is not present check for a loose 24 volt connec tion back to the relay board and check the connections from the room thermostat t...

Page 19: ...volts across terminals MV and COMMON terminals If no voltage is detected replace the ignitor control If voltage is pres ent replace the gas valve 8 Furnace lights with roll out or one burner has delayed igni tion a Make sure that the pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level...

Page 20: ... 0204 Supersedes 035 14832 002 A 0302 Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved ...

Reviews: