background image

WARNING:Troubleshooting of components necessarily re-

quires opening the electrical control box with the

power connected to the unit. Use extreme care

when working with live circuits! Check the unit

nameplate for the correct line voltage and set the

volt meter to the correct range before making any

connections with line terminals.

CAUTION: The wire number or color and terminal designa-

tions referred to may vary. Check the wiring label

inside the control box access panel for the correct

wiring.

1. Draft motor operates and furnace lights but supply air

blower does not start after a short time delay with room

thermostat fan switch set to “AUTO”.

a. Set fan switch to “ON”. If blower motor runs, go to Step f.

If it does not, check to see if line voltage is being sup-

plied to the contacts of the blower relay, “BR”, and if the

blower relay is pulled in. Check for loose wiring.

b. If “BR” is pulled in, touch the supply air blower motor

housing. If it is hot the motor may be off on inherent pro-

tection. Disconnect power to the unit and check the

blower motor capacitor. If it is defective, replace it with

one of equal capacitance and voltage.

c. If “BR” is pulled in and the blower motor still does not

run, replace the blower motor.

d. If “BR” is not pulled in check for 24 volts at the “BR” coil.

If 24 volts is present, replace the “BR” relay.

e. If 24 volts is not present at the “BR” coil, check for loose

24 volt wiring back to the relay board. Check control wir-

ing to the room thermostat. If all is fine, replace the relay

board.

f. If the blower motor runs with the fan switch in the “ON”

position but does not run soon after the furnace has ig-

nited with the fan switch in the “AUTO” position, check

for loose 24 volt wiring between the relay board in the

main control box, the Mate-N-Lok connector in the par-

tition between the evaporator and gas heat sections

and the time delay relay “BT” or “ETD”.

g. If all control wiring is fine, check for 24 volts at the relay

board. If 24 volts is present, replace the relay board. If

24 volts is not present, replace the “BT” or “ETD”.

NOTE: The furnace may shut itself down on a high temperature

condition during the procedure but this will not effect the

test if it is done within 5 minutes of furnace shut-down.

2. The supply air blower operates but the draft motor does not

when the room thermostat is set to call for heat and the fan

switch in the “ON” position.

a. The draft motor has inherent protection. If the motor shell

is hot to the touch, wait for the internal overload to reset.

b. If the motor shell is cold with the room thermostat calling

for heat, check for line voltage at the motor's Mate-N-

Lok connector attached to the evaporator partition. If

line voltage is present, replace the draft motor.

c. If line voltage is not present, check for line voltage at the

draft motor relay “DMR” or “DMC” contacts in the main

control box and check to see if the “DMR” or “DMC” is

pulled in.

d. If the “DMR” or “DMC” relay is pulled in, check for a

loose line voltage connection.

e. If the “DMR” or “DMC” relay is not pulled in, check for 24

volts at the “DMR” or 24 volts at “TMC-G” terminal coil. If

24 volts is present, replace the “DMR” or “DMC” relay. If

24 volts is not present, check for a loose 24 volt connec-

tion back to the relay board and check the connections

from the room thermostat to the relay board. If all connec-

tions are correct, replace the relay board.

3. The draft motor runs but the furnace does not light and the

sparker does not spark.

a. Check all 24 volt connections from the relay board to

and in the gas heat section. Check low voltage connec-

tions to the “BT" and “DMC” or “ETD” located in the con-

trol box.

b. If the furnace is hot, it may be out on an over tempera-

ture condition, wait for limit reset.

c. With the draft motor running, check for 24 volts at termi-

nal 24V on the ignitor control (IC) where the red lead

from the draft motor attaches. If 24 volts is not present,

the centrifugal switch (CS) has not closed or has gone

bad. Check the line voltage to the unit, if it is correct re-

place the draft motor. If line voltage is low call the power

company.

d. If 24 volts is present at the ignitor control, check all con-

trol wiring at the ignitor control and the high tension wire

to the ignitor. Check that the green ground wires from

the ignitor control, the gas valve and pilot burner are all

intact and making good electrical connection. Check to

make sure that the ceramic insulator on the pilot ignitor

or sensor is not broken or cracked, if all are intact re-

place the ignition control “IC”.

4. The draft motor runs and the sparker sparks at the pilot

burner but the pilot does not ignite and a gas odor is not

detected at the draft motor outlet.

a. Check to make sure gas is being supplied to the unit.

Make sure that the gas pressure to the unit is within the

proper limits as described in the “POST START

CHECK LIST” and that the pilot adjust screw is allowing

some flow of gas as described in “PILOT CHECKOUT”.

b. Check all wiring between the ignitor control and the gas

valve. Check to make sure the ground connections are

intact.

c. If the wiring is intact, check for 24 volts across terminals

“PV” and “COMMON” on the ignitor control. If 24 volts is

not present, replace the ignitor control.

d. If 24 volts is present, remove the pilot burner and re-

move the pilot orifice from the pilot burner. The orifice is

removed in the direction opposite the flow of gas. In-

spect the orifice for obstruction. If it is clear, replace the

main gas valve.

5. The sparker sparks at the pilot burner but the pilot does not

ignite and a gas odor is detected at the draft motor outlet.

a. Adjust the pilot adjust screw on the gas valve as de-

scribed in “PILOT CHECKOUT”.

b. Check the supply pressure as described in “POST

START CHECK LIST”. Make adjustments as neces-

sary.

c. Check the pilot orifice for obstruction as described in

Item 4. Clean as needed but the problem should not be

the gas valve.

18

Unitary Products Group

035-14832-003-A-0204

TROUBLESHOOTING

Cont'd

Summary of Contents for SUNLINE PLUS D2EG 048

Page 1: ...g of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 Forinstallationdirectlyoncombustibleflooringor intheU S A on wood flooring or Class A B or ...

Page 2: ...Air Conditioner Air Cooled PRODUCT IDENTIFIER EG High Efficiency Gas Electric VOLTAGE CODE 06 208 230 1 60 25 208 230 3 60 46 460 3 60 58 575 3 60 NOMINAL GAS HEATING OUTPUT CAPACITY 036 3 Ton 048 4 Ton 060 5 Ton 0 0 3 0 6 2 5 FACTORY INSTALLED HEAT N Natural Gas NOMINAL COOLING CAPACITY 040 40 MBH 060 60 MBH 079 79 MBH 099 99 MBH MAINTENANCE TROUBLESHOOTING Normal Maintenance 17 Cleaning Flue Pas...

Page 3: ...Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units...

Page 4: ...sign certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized...

Page 5: ...U N I T H A S A N E C O N O M I Z E R R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D T H E E C O N O M I Z E R I F Y O U W A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C ...

Page 6: ...that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 48kPa 7 A 1 8 inch NPT plugged tapping accessible for test gage connection must be installed immediately upstream of t...

Page 7: ...er 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B provided...

Page 8: ...13 5 1 COND FAN PROPELLER DIA in FAN MOTOR HP NOM CFM TOTAL 22 4 500 22 4 200 22 4 500 COND COIL ROWS DEEP FINS PER INCH FACE AREA Sq Ft 2 18 17 1 2 18 17 1 2 18 17 1 AIR FILTERS SEE NOTE QUANTITY PER UNIT 14 x 20 x 1 QUANTITY PER UNIT 14 X 25 X 1 TOTAL FACE AREA sq ft 2 1 6 3 2 1 6 3 2 1 6 3 CHARGE REFRIGERANT 22 lbs oz 9 12 9 8 9 8 COMPRESSOR QUANTITY PER UNIT HERMETIC TYPE 1 RECPT 1 RECPT 1 SCR...

Page 9: ...53 780 992 815 1034 855 1080 905 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 1 FILTERS AND THE GAS FIRED HEAT EXCHANGERS REFER TO TABLE 8 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watt...

Page 10: ...815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON SIDE DUCT CONNECTIONS 230 460 575 Volts MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 115...

Page 11: ...6 3 4 9 135 130 64 52 0 2 3 2 3 1 4 1 4 5 0 5 0 2 2 2 2 38 6 25 7 13 2 11 4 60 40 20 15 60 40 20 15 060 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 32 1 19 3 10 0 7 9 135 150 73 50 2 3 2 3 1 4 1 4 6 6 6 6 3 3 3 3 49 0 33 0 17 2 14 6 80 50 25 20 80 50 25 20 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 10 ELECTRI...

Page 12: ...r motorized Air Damper Left Side Filter Access 24 Less Economizer 36 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 For Condenser Air Discharge 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet NOTE A ...

Page 13: ...lose and the blower motor operates INTERMITTENT BLOWER With the room thermostat system switch set to the AUTO or HEAT position and the fan switch set to AUTO the supply air blower will operate after the room thermostat calls for heat and the air in the gas heat compartment has achieved a pre set temeprature When TH1 on the thermostat closes the draft motor relay DMR or DMC is energized The DMR or ...

Page 14: ...e same as listed on the unit nameplate 2 Make sure that the vent and combustion air hoods have been properly installed 14 Unitary Products Group 035 14832 003 A 0204 Units Tons Capacity MBH Limit Control Opens F Input Output 3 4 3 4 5 5 50 75 100 125 100 125 40 60 79 99 79 99 165 165 165 165 165 165 TABLE 12 LIMIT CONTROL SETTING OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an inte...

Page 15: ...red supply air CFM Refer to Table 9 for blower motor and drive data The tension on the belts should be adjusted as shown in Figure 14 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equi...

Page 16: ...rom Table 14 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it var...

Page 17: ...harge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge The manufacture recommends that the furnace system be inspected once a year by a qualified service person CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need c...

Page 18: ... DMC is pulled in d If the DMR or DMC relay is pulled in check for a loose line voltage connection e If the DMR or DMC relay is not pulled in check for 24 volts at the DMR or 24 volts at TMC G terminal coil If 24 volts is present replace the DMR or DMC relay If 24 volts is not present check for a loose 24 volt connec tion back to the relay board and check the connections from the room thermostat t...

Page 19: ...volts across terminals MV and COMMON terminals If no voltage is detected replace the ignitor control If voltage is pres ent replace the gas valve 8 Furnace lights with roll out or one burner has delayed igni tion a Make sure that the pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level...

Page 20: ... 0204 Supersedes 035 14832 002 A 0302 Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved ...

Reviews: