TABLE 8: COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE)
Air on Evaporator Coil
Temperature of Air on Condenser Coil
75°F
85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65
6000
67
100
15.9
20
18
16
14
12
10
94
16.6
13
12
11
9
8
7
62
93
15.1
44
42
40
38
36
35
86
15.9
30
29
27
26
25
23
57
83
15.1
50
48
46
45
43
41
77
15.8
34
33
32
30
29
28
7000
67
109
15.8
31
28
24
21
18
15
103
16.5
25
23
20
18
15
12
62
102
15.1
68
65
62
59
56
53
95
15.8
57
54
52
49
47
44
57
90
15.0
74
74
71
68
64
61
85
15.7
63
63
60
58
55
52
8000
67
119
15.7
42
37
33
29
24
20
112
16.4
38
34
30
26
22
18
62
110
15.0
92
88
83
79
75
70
103
15.8
84
80
76
72
69
65
57
98
14.9
98
98
95
91
86
82
93
15.7
93
93
89
85
81
77
8450
67
113
15.7
42
38
33
29
25
21
107
16.4
39
35
31
27
23
19
62
105
15.0
88
88
85
80
76
72
98
15.8
84
84
80
76
72
68
57
93
14.9
93
93
92
87
83
79
88
15.7
88
88
86
82
78
75
8900
67
107
15.7
42
38
34
30
26
22
101
16.4
40
36
32
29
25
21
62
99
14.9
88
88
86
82
78
73
93
15.8
84
84
83
79
75
71
57
88
14.9
88
88
88
84
80
76
84
15.7
84
84
84
80
76
72
95°F
105°F
6000
67
87
17.3
7
6
5
5
4
3
77
18.2
3
3
3
2
2
2
62
79
16.7
16
15
14
14
13
12
68
17.7
8
7
7
7
6
6
57
72
16.5
18
18
17
16
16
15
63
17.4
9
9
9
8
8
7
7000
67
96
17.2
20
18
16
14
12
10
86
18.2
15
14
12
11
9
7
62
88
16.6
46
44
42
40
38
35
76
17.7
36
35
33
32
30
28
57
79
16.4
53
52
50
48
46
44
70
17.4
43
43
41
40
38
36
8000
67
106
17.2
34
30
27
23
20
16
94
18.2
28
25
22
19
16
13
62
96
16.6
76
73
69
66
62
59
84
17.7
65
62
59
57
54
51
57
87
16.4
87
86
83
79
76
72
78
17.4
78
77
74
71
68
65
8450
67
101
17.2
36
32
29
25
22
18
90
18.1
29
26
23
20
17
14
62
92
16.6
78
78
75
71
68
64
80
17.6
68
66
63
60
57
54
57
83
16.4
83
83
81
77
74
70
74
17.3
74
74
72
69
67
64
8900
67
96
17.2
38
35
31
27
24
20
86
18.1
30
27
24
21
19
16
62
87
16.6
79
79
79
75
72
67
76
17.6
71
69
66
63
60
57
57
79
16.4
79
79
79
75
72
68
71
17.3
71
71
71
68
65
62
115°F
125°F
6000
67
67
19.1
-
-
-
-
-
-
57
20.0
-
-
-
-
-
-
62
57
18.7
-
-
-
-
-
-
46
19.7
-
-
-
-
-
-
57
54
18.3
-
-
-
-
-
-
46
19.2
-
-
-
-
-
-
7000
67
75
19.1
11
10
8
7
6
5
64
20.1
6
5
5
4
3
3
62
64
18.7
27
26
25
24
23
21
52
19.7
18
17
16
16
15
14
57
61
18.3
34
33
32
31
30
29
52
19.2
25
24
24
23
22
22
8000
67
83
19.2
21
19
17
15
13
10
72
20.1
15
14
12
11
9
7
62
71
18.7
54
52
50
47
45
43
58
19.8
43
41
40
38
37
35
57
68
18.3
68
67
65
62
60
58
58
19.3
58
57
56
54
52
51
8450
67
80
19.1
22
19
17
15
13
11
70
20.0
14
13
12
10
9
7
62
68
18.6
55
53
51
48
46
44
56
19.7
41
40
38
37
36
34
57
65
18.2
65
65
64
61
59
57
56
19.2
56
56
55
54
52
51
8900
67
77
19.0
22
20
18
16
14
12
67
19.9
13
12
11
10
9
7
62
65
18.5
55
53
51
49
47
45
54
19.5
40
38
37
36
35
33
57
63
18.2
63
63
63
61
59
56
54
19.0
54
54
54
53
52
51
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity