262292-YTG-C-0707
18
Unitary Products Group
TABLE 7: COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE)
Air on Evaporator Coil
Temperature of Air on Condenser Coil
75°F
85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65
4500
67
88
10.6
23
21
19
16
14
11
80
11.2
18
16
14
12
10
9
62
79
10.1
44
42
39
37
35
32
72
10.8
35
34
32
30
28
26
57
70
9.9
48
46
44
41
39
36
66
10.6
39
37
35
34
32
30
5250
67
90
10.7
32
29
25
22
19
15
82
11.3
26
24
21
18
15
12
62
81
10.2
59
56
53
49
46
43
74
10.8
53
50
47
44
41
39
57
72
10.0
61
59
58
55
51
48
68
10.7
55
54
53
50
47
44
6000
67
92
10.8
40
36
32
28
23
19
85
11.3
35
31
27
24
20
16
62
82
10.3
73
70
66
61
57
53
76
10.9
70
66
62
58
55
51
57
73
10.0
73
73
72
68
64
60
70
10.7
70
70
70
66
62
58
6750
67
95
10.8
49
44
39
33
28
23
87
11.3
43
38
34
29
25
20
62
85
10.2
75
74
72
66
61
56
78
10.9
72
70
68
63
59
55
57
75
10.0
75
75
75
70
65
59
72
10.7
72
72
72
67
63
58
7500
67
98
10.7
58
52
46
39
33
27
90
11.3
51
45
40
34
29
24
62
88
10.2
78
78
78
71
65
59
81
10.9
74
74
74
68
63
58
57
78
10.0
78
78
78
72
65
59
74
10.7
74
74
74
68
63
58
95°F
105°F
4500
67
71
11.8
12
11
10
8
7
6
65
12.5
8
8
7
6
5
4
62
64
11.4
27
25
24
23
22
20
60
12.1
21
20
19
18
17
16
57
61
11.3
30
29
27
26
25
24
57
12.1
23
22
21
20
19
18
5250
67
74
11.8
21
19
16
14
12
10
69
12.6
16
15
13
11
9
8
62
68
11.5
46
44
41
39
37
35
63
12.2
41
40
38
36
34
33
57
64
11.4
48
48
47
45
43
40
60
12.1
43
42
42
40
38
36
6000
67
78
11.9
29
26
23
20
17
14
72
12.6
24
22
19
16
14
11
62
71
11.5
65
62
59
56
52
49
66
12.2
62
60
57
54
52
49
57
67
11.4
67
67
67
63
60
57
63
12.1
63
63
62
60
57
55
6750
67
79
11.9
36
32
29
25
21
17
73
12.6
31
28
24
21
18
15
62
72
11.5
67
66
64
60
57
53
66
12.2
63
62
61
57
54
51
57
68
11.4
68
68
68
64
60
57
64
12.1
64
64
63
60
57
54
7500
67
81
11.9
43
39
34
30
25
21
74
12.6
37
34
30
26
22
18
62
73
11.5
70
70
70
65
61
56
67
12.2
64
64
64
60
57
53
57
70
11.4
70
70
70
65
61
56
64
12.1
64
64
64
61
57
53
115°F
125°F
4500
67
60
13.3
5
4
4
3
3
2
54
14.0
-
-
-
-
-
-
62
55
12.8
15
14
14
13
13
12
50
13.5
9
9
9
8
8
8
57
53
12.8
16
15
15
14
14
13
50
13.5
9
8
8
8
8
8
5250
67
63
13.3
12
11
9
8
7
6
57
14.1
8
7
6
5
4
3
62
58
12.9
37
36
35
33
32
31
53
13.6
33
31
31
30
29
29
57
56
12.8
37
37
36
35
34
33
52
13.6
31
31
31
30
30
29
6000
67
66
13.4
19
17
15
13
11
9
60
14.1
14
13
11
9
8
6
62
60
12.9
59
57
55
53
51
49
55
13.6
55
54
53
52
50
49
57
59
12.9
59
59
58
56
54
52
54
13.6
54
54
54
53
51
50
6750
67
66
13.4
25
23
20
18
15
12
59
14.1
20
18
16
14
12
10
62
61
12.9
59
58
57
54
52
49
55
13.6
54
54
53
52
49
47
57
59
12.9
59
59
59
56
53
51
54
13.6
54
54
54
52
50
48
7500
67
66
13.4
32
28
25
22
19
16
59
14.1
26
23
21
18
16
13
62
61
12.9
59
59
59
56
53
49
55
13.6
54
54
54
51
48
46
57
59
12.9
59
59
59
56
53
50
54
13.6
54
54
54
52
49
46
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity