262292-YTG-C-0707
44
Unitary Products Group
NOTE 1: HACR Type per NEC.
TABLE 31: WR ELECTRICAL DATA - LOW STATIC DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET
MODEL
(TONNAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
240
(20)
208
30.1
225
2.4
20.0
10.0
None
0.0
-
-
107.3
125
E18
13.5
1
37.5
107.3
125
E36
27.0
2
75.1
131.2
150
E54
40.6
2
112.7
178.4
200
E72
54.1
2
150.2
187.7
200
230
30.1
225
2.4
20.0
10.0
None
0.0
-
-
107.3
125
E18
18.0
1
43.3
107.3
125
E36
36.0
2
86.6
145.8
150
E54
54.0
2
129.9
167.4
175
E72
72.0
2
173.2
210.7
225
460
15.5
114
0.9
10.0
5.0
None
0.0
-
-
53.5
60
E18
18.0
1
21.7
53.5
60
E36
36.0
2
43.3
72.9
80
E54
54.0
2
65.0
83.7
90
E72
72.0
2
86.6
105.4
110
575
12.1
80
0.6
7.5
4.0
None
0.0
-
-
41.1
50
E18
18.0
1
17.3
41.1
50
E36
36.0
2
34.6
57.7
60
E54
54.0
2
52.0
66.3
70
E72
72.0
2
69.3
83.7
90
300
(25)
208
42.3
245
2.4
20.0
10.0
None
0.0
-
-
134.8
175
E18
13.5
1
37.5
134.8
175
E36
27.0
2
75.1
134.8
175
E54
40.6
2
112.6
178.4
200
E72
54.1
2
150.1
187.7
200
230
42.3
245
2.4
20.0
10.0
None
0.0
-
-
134.8
175
E18
18.0
1
43.3
134.8
175
E36
36.0
2
86.6
145.8
175
E54
54.0
2
129.9
167.4
175
E72
72.0
2
173.2
210.7
225
460
17.6
125
0.9
10.0
5.0
None
0.0
-
-
58.2
70
E18
18.0
1
21.7
58.2
70
E36
36.0
2
43.3
72.9
80
E54
54.0
2
65.0
83.7
90
E72
72.0
2
86.6
105.4
110
575
14.5
100
0.6
7.5
4.0
None
0.0
-
-
46.5
60
E18
18.0
1
17.3
46.5
60
E36
36.0
2
34.6
57.7
60
E54
54.0
2
52.0
66.3
70
E72
72.0
2
69.3
83.7
90
VOLTAGE LIMITATIONS
ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
MIN.
MAX.
208
208
1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60
187
253
240
230
0.92
460-3-60
414
506
480
460
0.92
575-3-60
518
630
600
575
0.92
1.
Utilization Range “A” in accordance with ARI Standard 110.