TABLE 24: DR300 BLOWER PERFORMANCE - HIGH STATIC DRIVE
ESP
CFM RPM KW
BHP CFM RPM KW
BHP CFM RPM KW
BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.4
11600 1200 12.5 16.0 11175 1164 11.5 14.7 10620 1127 10.4 13.3 10500 1092 9.2 11.7 9875 1058 8.2 10.5 9100 1020 7.4
9.4
0.6
11060 1201 11.8 15.1 10600 1166 10.8 13.8 10100 1131 9.7
12.4
9980
1095 8.6 11.0 9320 1060 7.6
9.7
8920 1022 6.9
8.8
0.8
10500 1203 11.1 14.2 10100 1169 10.2 13.0
9520
1132 9.1
11.6
9360
1097
8
10.2 8600 1061 6.9
8.8
8230 1024 6.3
8.0
1
9930 1205 10.4 13.3
9430 1171
9.5
12.1
8870
1134 8.4
10.7
8800
1099 7.4
9.4
8240 1063 6.4
8.2
7500 1025 5.7
7.3
1.2
9800 1207
9.9
12.6
9270 1173
8.9
11.4
8590
1136 7.9
10.1
8120
1101 6.8
8.7
7240 1065 5.7
7.3
6990 1027 5.2
6.6
1.4
9200 1210
9.2
11.7
8480 1174
7.9
10.1
8070
1039 7.1
9.1
7340
1103 6.1
7.8
6820 1066 5.3
6.8
6100 1029 4.8
6.1
1.6
8400 1213
8.4
10.7
7750 1177
7.2
9.2
7560
1140 6.5
8.3
7220
1103 5.9
7.5
5380 1069 4.2
5.4
1.8
7830 1215
7.7
9.8
7600 1178
7
8.9
6600
1142 5.6
7.1
5810
1106 4.7
6.0
2
7300 1216
7
8.9
6300 1180
6.1
7.8
5450
1145 4.9
6.3
2.2
6400 1218
6.2
7.9
5230 1184
5.1
6.5
2.4
5400 1221
5.4
6.9
15 HP motor
10 HP motor
7.5 HP motor
Chart shading corresponds to minimum horsepower requirements as defined below.
5 Turns
6 Turns
DR300 Blower Performance (Horizontal Discharge)
1 Turn
2 Turns
3 Turns
4 Turns
25-Ton High Static Drive
1VP71 & 1B5V94
5500
6500
7500
8500
9500
10500
11500
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
External Static ("WC)
CFM
6 Turns
4 Turns
5 Turns
3 Turns
2 Turns
1 Turn