TABLE 23: DR300 BLOWER PERFORMANCE - STANDARD DRIVE
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW
BHP CFM RPM KW BHP CFM RPM KW BHP
0.4
9550 996
7.1 9.04 8800 959
6.1 7.79 8700 950
5.9 7.53 8250 913
4.95 6.97 8050 877
4.7 5.99 7250 842
3.9 4.97
0.6
9010 997
6.6 8.43 8150 960
5.6 7.15 8010 950
5.4 6.89 7540 915
4.57 6.44 7290 879
4.2 5.33 6460 843
3.5 4.47
0.8
8430 998
6.1 7.79 7510 961
5.1 6.51 7330 952
4.9 6.25 6820 916
4.09 5.77 6480 880
3.7 4.76 5600 844
3.1 3.99
1
7830 1000 5.6 7.15 6830 962
4.6 5.87 6570 953
4.4 5.62 5990 916
3.52 4.96 5500 881
3.1 3.99
1.2
7210 1000 5.1 6.51 6140 964
4.2 5.36 5850 954
3.8 4.86 5210 918
3.05 4.29
1.4
6500 1001 4.6 5.87 5480 965
3.6
4.6
1.6
5460 1003 3.9 4.97
5 HP motor
Chart shading corresponds to minimum motor horsepower requirements as defined below.
6 Turns
10 HP motor
7.5 HP motor
DR300 Blower Performace (Horizontal Discharge)
2 Turns
3 Turns
4 Turns
5 Turns
1 Turn
25-Ton Standard Drive
1VP60 & 1B5V94
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
0.4
0.6
0.8
1
1.2
1.4
External Static ("WC)
CFM
6 Turns
5 Turns
4 Turns
3 Turns
2 Turns
1 Turn