127915-YIM-A-0405
44
Unitary Products Group
TABLE 19: DR240 BLOWER PERFORMANCE - STANDARD DRIVE (COOLING ONLY)
ESP
CFM
RPM
KW
BHP CFM RPM
KW
BHP CFM RPM
KW BHP
CFM
RPM
KW
BHP
CFM
RPM
KW
BHP
CFM
RPM
KW
BHP
0.2
9445
1025
6.94
8.79 9021 993
6.211 7.87 8684 962
5.59
7.08 8422
929
5.057
6.41 8028
896
4.516
5.72 7677.5
863
4.00758 5.08
0.4
9172
1027 6.629 8.40 8645 995
5.912 7.49 8282 963
5.3
6.72 8022
930
4.781
6.06 7605
897
4.259
5.40
7243
864
3.75462 4.76
0.6
8689
1028 6.283 7.96 8262 996
5.606 7.10 7869 965
5
6.34 7585
931
4.482
5.68 7160
898
3.971
5.03 7182.8
864
3.47616 4.41
0.8
8363
1028 5.979 7.58 7859 997
5.284 6.70 7434 965
4.67
5.92 7136
932
4.171
5.29 6684
899
3.671
4.65 6421.9
865
3.24768 4.12
1
7944
1029 5.612 7.11 7410 998
4.924 6.24 6950 966
4.3
5.45 6643
933
3.836
4.86 6142
900
3.328
4.22 5834.4
866
2.92638 3.71
1.2
7498
1030 5.238 6.64 6936 1000 4.556 5.77 6443 967
3.95
5.01 6104
934
3.496
4.43 5595
901
1.224
1.55 5217.3
867
2.59998 3.29
1.4
6997
1033 4.835 6.13 6429 1001 4.179 5.30 5921 969
3.58
4.54 5406
936
3.098
3.93 4942
902
2.672
3.39
4488
868
2.26746 2.87
1.6
6421
1034 4.443 5.63 5916 1002
3.79
4.80 5296 970
3.21
4.07 4691
938
2.699
3.42 4318
903
2.391
3.03
1.8
5814
1036 4.024 5.10 5277 1004 3.402 4.31 4608 971
2.84
3.60
2
5234
1038 3.605 4.57 4676 1005 3.066 3.89
7.5 HP motor
5 HP motor
Chart shading corresponds to minimum motor horsepower requirements as defined below.
5 Turns
6 Turns
DR240 Standard Drive Blower Performance (Horizontal Discharge)
1 Turn
2 Turns
3 Turns
4 Turns
20-Ton Standard Drive
1VP68 & 1BK110
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
External Static ("WC)
CFM
6 Turns
5 Turns
3 Turns
2 Turns
1 Turn
4 Turns