127915-YIM-A-0405
Unitary Products Group
51
FIGURE 14 - CHARGING CHART - 15 TON
DR180 Charging Chart
150
170
190
210
230
250
270
290
310
330
350
60
65
70
75
80
85
90
Suction Pressure (psi)
Discharge Pressure (psi
)
115º
105º
95º
85º
Outdoor Temp (ºF)
1. Make sure that both condenser fans are running when charging. One fan may switch off at lower ambient
temperatures making the chart above inaccurate.
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV's have been adjusted in the field,
The charging chart may no longer apply.
75º
65º
FIGURE 15 - CHARGING CHART - 20 TON
DR240 Charging Chart
150
170
190
210
230
250
270
290
310
330
350
60
65
70
75
80
85
90
Suction Pressure (psi)
Outdoor Temp (ºF)
115º
105º
95º
85º
75º
65º
Both fans must be running when charging the unit. One fan may switch off at low ambient temperatures making this chart inaccurate.
Discharge Pressure (psi
)