BLOWER PERFORMANCE

DCE300 - BOTTOM DUCT CONNECTIONS

 (

COOLING APPLICATIONS)

STANDARD DRIVE (m

3

 / s)

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

AIRFLOW

3.78

4.25

4.72

5.19

5.66

ESP

(Pa)

Output

(KW)

Input

(KW)

ESP

(Pa)

Output

(KW)

Input

(KW)

ESP

(Pa)

Output

(KW)

Input

(KW)

ESP

(Pa)

Output

(KW)

Input

(KW)

ESP

(Pa)

Output

(KW)

Input
(KW)

1010

6.0**

399

5.7

6.4

249

6.6

7.5

125

7.6

8.7

-

-

-

-

-

-

1064

5.0

473

6.1

6.9

349

7.2

8.0

224

8.3

9.3

75

9.5

10.6

-

-

-

1118

4.0

573

6.6

7.4

448

7.7

8.6

324

8.9

10.0

249

10.1

11.4

50

11.5

12.9

1172

3.0

673

7.0

7.9

548

8.2

9.2

424

9.5

10.6

274

10.8

12.2

125

12.2

13.7

STANDARD DRIVE (CFM)

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

AIRFLOW

8,000

9,000

10,000

11,000

12,000

ESP

(iwg)

Output

(BHP)

Input

 (KW)

ESP

(iwg)

Output

(BHP)

Input

 (KW)

ESP

(iwg)

Output

(BHP)

Input

 (KW)

ESP

(iwg)

Output

(BHP)

Input

 (KW)

ESP

(iwg)

Output

(BHP)

Input

 (KW)

1010

6.0**

1.6

7.6

6.4

1.0

8.9

7.5

0.5

10.4

8.7

-

-

-

-

-

-

1064

5.0

1.9

8.2

6.9

1.4

9.6

8.0

0.9

11.1

9.3

0.3

12.7

10.6

-

-

-

1118

4.0

2.3

8.8

7.4

1.8

10.3

8.6

1.3

11.9

10.0

0.7

13.6

11.4

0.2

15.4

12.9

1172

3.0

2.7

9.4

7.9

2.2

11.0

9.2

1.7

12.7

10.6

1.1

14.5

12.2

0.5

16.4

13.7

  NOTES: 1. Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.

                 2. Refer to Page 14 for additional static resistances.

                     ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

                  * Do NOT close the pulley below 1 turn open.

                 ** Factory setting.               

MODEL

SIZE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR

PULLEY

2

FIXED BLOWER PULLEY

BELT

(NOTCHED)

kW /

HP

FRAME

EFF.

(%)

DESIG-

NATION

PITCH

DIA. mm

(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

DIA. mm

(IN.)

BORE

mm

(IN.)

DESIG-

NATION

PITCH

LENGTH

mm

(IN.)

QTY.

300

980 /1170 7.5 / 10

254T

89

2MVP70

178 - 213 

(7.0-

8.4

)

P2

BUSH-

ING

2BK110H

264

(10.4)

27

 (1-7/16)

BX84

2179

(85.8)

2

1

All motors have a nominal speed of 1450 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream

  of any heating device.

Do NOT close this pulley below 1 turn open.

STATIC RESISTANCES*

BLOWER MOTOR AND DRIVE DATA

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, Pa / iwg

m

3

/s / CFM

4.25 / 9,000

4.72 / 10,000

5.19 / 11,000

WET COIL

25 / 0.1

25 / 0.1

25 / 0.1

GAS HEAT

25 / 0.1

25 / 0.1

25 / 0.1

ELECTRIC HEAT OPTIONS

18 KW

25 / 0.1

25 / 0.1

25 / 0.1

36 KW

25 / 0.1

50 / 0.2

75 / 0.3

54 KW

50 / 0.2

75 / 0.3

100 / 0.4

72 KW

50 / 0.2

100 / 0.4

150 / 0.6

ECONOMIZER OPTION

25 / 0.1

25 / 0.1

25 / 0.1

HORIZONTAL DUCT CONNECTIONS

50 / 0.2

75 / 0.3

125 / 0.5

*

Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections

  (Shaded               ). Add these values due to less airflow resistance.

530.26-TG4YI

Unitary Products Group

5

Summary of Contents for Sunline 2000

Page 1: ...e mounted over the opening in the return air panel With horizontal ductwork it should be mounted on the return air duct All supply air blowers are equipped with a belt drive that can be adjusted to me...

Page 2: ...a field installed option DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS Includes a slide in plug in damper assembly with fully modulating spring return monitor actuator capable of introducing up to 100 ou...

Page 3: ...LAR HEAT EXCHANGERS ECONOMIZER HOOD 2 DISPOSABLE FILTERS OUTDOOR AIR OPENING FOR SLIDE IN PLUG IN INTERNAL ECONOMIZER OPTION SIDE AND BOTTOM SUPPLY RETURN AIR DUCT OPENINGS SIDE X SIDE 1 NPTI CONDENSA...

Page 4: ...6 87 6 28 5 88 83 78 65 80 9 32 0 81 76 71 62 Air On Evaporator Coil Temperature of Air on Condenser Coil OD Dry Bulb 80 F OD Dry Bulb 95 F OD Dry Bulb 115 F Total Cap MBH Power Input KW Sensible Capa...

Page 5: ...the supply and return air duct system All internal unit resistances have been deducted from the total static pressure of the blower Do NOT close the pulley below 1 turn open Factory setting MODEL SIZE...

Page 6: ...INS PER 25mm 1 in 15 FACE AREA m2 Ft 2 4 02 43 3 COMPRESSOR Qty Per Unit TANDEM 8 TON NOMINAL CAPACITY 3 AIR FILTERS QUANTITY PER UNIT 406 x 508 x 51 mm 2 16 x 20 x 2 in QUANTITY PER UNIT 406 x 635 x...

Page 7: ...FIELD WIRING DCE DCG Electric Electric and Gas Electric Units 530 26 TG4YI Unitary Products Group 7...

Page 8: ...between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculat...

Page 9: ...cting side ducts For bottom duct applications 1 Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers 2 Remove and discard t...

Page 10: ...S 3207 126 1 4 Supply and Return Air including duct support rails as shown are typical for downflow duct applications For location of sideflow duct applications on back of unit refer to Unit Dimension...

Page 11: ...TYPICAL APPLICATIONS TYPICAL ROOF TOP INSTALLATION GAS ELECTRIC UNIT SHOWN 530 26 TG4YI Unitary Products Group 11...

Page 12: ...p P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1996 All Rights Reserved Code EBY EGY 530 26 TG4YI Superce...

Reviews: