BLOWER PERFORMANCE
DCE300 - BOTTOM DUCT CONNECTIONS
(
COOLING APPLICATIONS)
STANDARD DRIVE (m
3
/ s)
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
3.78
4.25
4.72
5.19
5.66
ESP
(Pa)
Output
(KW)
Input
(KW)
ESP
(Pa)
Output
(KW)
Input
(KW)
ESP
(Pa)
Output
(KW)
Input
(KW)
ESP
(Pa)
Output
(KW)
Input
(KW)
ESP
(Pa)
Output
(KW)
Input
(KW)
1010
6.0**
399
5.7
6.4
249
6.6
7.5
125
7.6
8.7
-
-
-
-
-
-
1064
5.0
473
6.1
6.9
349
7.2
8.0
224
8.3
9.3
75
9.5
10.6
-
-
-
1118
4.0
573
6.6
7.4
448
7.7
8.6
324
8.9
10.0
249
10.1
11.4
50
11.5
12.9
1172
3.0
673
7.0
7.9
548
8.2
9.2
424
9.5
10.6
274
10.8
12.2
125
12.2
13.7
STANDARD DRIVE (CFM)
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
8,000
9,000
10,000
11,000
12,000
ESP
(iwg)
Output
(BHP)
Input
(KW)
ESP
(iwg)
Output
(BHP)
Input
(KW)
ESP
(iwg)
Output
(BHP)
Input
(KW)
ESP
(iwg)
Output
(BHP)
Input
(KW)
ESP
(iwg)
Output
(BHP)
Input
(KW)
1010
6.0**
1.6
7.6
6.4
1.0
8.9
7.5
0.5
10.4
8.7
-
-
-
-
-
-
1064
5.0
1.9
8.2
6.9
1.4
9.6
8.0
0.9
11.1
9.3
0.3
12.7
10.6
-
-
-
1118
4.0
2.3
8.8
7.4
1.8
10.3
8.6
1.3
11.9
10.0
0.7
13.6
11.4
0.2
15.4
12.9
1172
3.0
2.7
9.4
7.9
2.2
11.0
9.2
1.7
12.7
10.6
1.1
14.5
12.2
0.5
16.4
13.7
NOTES: 1. Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
2. Refer to Page 14 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
MODEL
SIZE
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR
PULLEY
2
FIXED BLOWER PULLEY
BELT
(NOTCHED)
kW /
HP
FRAME
EFF.
(%)
DESIG-
NATION
PITCH
DIA. mm
(IN.)
BORE
(IN.)
DESIG-
NATION
PITCH
DIA. mm
(IN.)
BORE
mm
(IN.)
DESIG-
NATION
PITCH
LENGTH
mm
(IN.)
QTY.
300
980 /1170 7.5 / 10
254T
89
2MVP70
178 - 213
(7.0-
8.4
)
P2
BUSH-
ING
2BK110H
264
(10.4)
27
(1-7/16)
BX84
2179
(85.8)
2
1
All motors have a nominal speed of 1450 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream
of any heating device.
2
Do NOT close this pulley below 1 turn open.
STATIC RESISTANCES*
BLOWER MOTOR AND DRIVE DATA
EXTERNAL STATIC PRESSURE DROP
DESCRIPTION
RESISTANCE, Pa / iwg
m
3
/s / CFM
4.25 / 9,000
4.72 / 10,000
5.19 / 11,000
WET COIL
25 / 0.1
25 / 0.1
25 / 0.1
GAS HEAT
25 / 0.1
25 / 0.1
25 / 0.1
ELECTRIC HEAT OPTIONS
18 KW
25 / 0.1
25 / 0.1
25 / 0.1
36 KW
25 / 0.1
50 / 0.2
75 / 0.3
54 KW
50 / 0.2
75 / 0.3
100 / 0.4
72 KW
50 / 0.2
100 / 0.4
150 / 0.6
ECONOMIZER OPTION
25 / 0.1
25 / 0.1
25 / 0.1
HORIZONTAL DUCT CONNECTIONS
50 / 0.2
75 / 0.3
125 / 0.5
*
Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections
(Shaded ). Add these values due to less airflow resistance.
530.26-TG4YI
Unitary Products Group
5