FACTORY-INSTALLED OPTIONS

ECONOMIZERS - Interlocked outdoor and return air dampers
are positioned by a fully modulating, spring return damper
actuator capable of introducing up to 100% outdoor air with
nominal 1% leakage type dampers. As the outdoor air intake
dampers open, the return air dampers close. The changeover
from compressor to economizer cooling is determined by one
or two solid state enthalpy controls.

On single enthalpy, an outdoor air sensor determines when the
outdoor air is cool and dry enough to provide “free” cooling. On
differential enthalpy, one sensor monitors the outdoor air while
a second sensor monitors the return air. Whenever the outdoor
air is cooler and drier than the return air, the unit will switch to
economizer operation. For either option, the first compressor
stage can provide additional cooling during economizer
operation if the room thermostat calls for second stage.

The dampers and controls are installed and wired at the factory.

Only the accessory rain hood needs to be assembled and

installed in the field.
These economizer options can be used on all duct configurations.
POWER EXHAUST - Both the single and differential

economizer options are available with power exhaust.

Whenever the outdoor air intake dampers are opened for free

cooling, the exhaust fan will be energized to prevent the

conditioned space from being over-pressurized during

economizer operation.

The exhaust fan, motor and controls are installed and wired at
the factory. Only the back-draft damper assembly needs to be
field installed and the accessory rain hoods need to be
assembled and installed in the field.

The power exhaust option can only be used on bottom duct

configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Interlocked

outdoor and return air dampers are controlled by a 2-position,

spring return damper actuator. The outdoor damper will open

to some pre-set position whenever the supply air blower is

operating and will drive fully closed when the blower shuts

down.
The damper and controls are installed and wired at the factory.

Only the accessory rain hood needs to be assembled in the field.
This damper option can be used on all duct configurations.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS

- Includes a slide-in / plug-in damper assembly with fully

modulating spring-return monitor actuator capable of

introducing up to 100% outdoor air with nominal 1% leakage

type dampers.
The enthalpy system contains one sensor that monitors the

outdoor air and determines when the air is cool enough and dry

enough to provide “free” cooling.
The rainhood is painted to match the basic unit and must be

field-assembled before installing.
On units built prior to January 1995, an accessory field harness

must be installed.
Power exhaust is not available as  a field installed option.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS -
Includes a slide-in / plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1% leakage
type dampers.

This enthalpy system contain one sensor that monitors the

outdoor air and one sensor that monitors the return air. The

logic module compares these two values and modulates the

dampers providing the maximum efficiency of economizer

system.
The rainhood is painted to match the basic unit and must be

field-assembled before installing.
On units built prior to January 1995, an accessory field harness

must be installed.

Power exhaust is not available as a field installed option.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a
slide-in / plug-in damper assembly with a 2-position, spring
return motor actuator which opens to some pre-set position
whenever the supply air blower is operating and will drive fully
closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be
field assembled before installing.

On units built prior to January 1995 an accessory field harness

must be installed.
Power exhaust is not available as a field installed option.

ROOF CURBS - 343mm (14") high roof curbs provide a
water-tight seal between the unit and the finished roof. These
full perimeter curbs meet the requirements of the National
Roofing Contractors Association (NRCA) and are shipped
knocked-down for field assembly. They’re designed to fit inside
the base rails of the unit and include both a wood nailing strip
and duct hanger supports.

ANTI-RECYCLE TIMERS - Three solid state timers prevent
the compressors from short-cycling. Once a compressor is
de-energized, it will remain de-energized for approximately five
minutes.

HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot

orifices are provided for proper furnace operation at altitudes

up to 1824m (6,000 ft).

PROPANE - Burner orifices, pilot orifices and gas valve parts
are provided to convert a natural gas furnace to propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices
are provided for proper furnace operation at altitudes up to
1824m (6,000 ft). This accessory supplements the basic
propane conversion kit.

SIDE DUCT FLANGES - 25mm (1") flanges replace the supply
and return air panels on the rear of the unit to accommodate
horizontal duct connections. These flanges can also be used
individually for bottom supply/horizontal return or horizontal
supply/bottom return. They cannot be used on units with power
exhaust.

TABLE OF CONTENTS

Physical Data ....................................................................... 6
Electrical Data - Clg. and Gas Heating................................ 6
Electrical Data - Units with Electric Heating ........................ 6
Field Wiring (DCE/DCG Units) ............................................ 7
Unit Dimensions................................................................... 8
Roof Curb Dimensions....................................................... 10
Typical Applications ............................................................11

Description ........................................................................... 1
Factory-Installed Options..................................................... 2
Field-Installed Accessories .................................................. 2
Ratings ................................................................................. 3
Cooling Capacities............................................................... 4
Blower Performance ............................................................ 5
Static and Power Exhaust Resistances............................... 5
Blower Motor and Drive Data .............................................. 5

530.26-TG4YI

2

Unitary Products Group

Summary of Contents for Sunline 2000

Page 1: ...e mounted over the opening in the return air panel With horizontal ductwork it should be mounted on the return air duct All supply air blowers are equipped with a belt drive that can be adjusted to me...

Page 2: ...a field installed option DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS Includes a slide in plug in damper assembly with fully modulating spring return monitor actuator capable of introducing up to 100 ou...

Page 3: ...LAR HEAT EXCHANGERS ECONOMIZER HOOD 2 DISPOSABLE FILTERS OUTDOOR AIR OPENING FOR SLIDE IN PLUG IN INTERNAL ECONOMIZER OPTION SIDE AND BOTTOM SUPPLY RETURN AIR DUCT OPENINGS SIDE X SIDE 1 NPTI CONDENSA...

Page 4: ...6 87 6 28 5 88 83 78 65 80 9 32 0 81 76 71 62 Air On Evaporator Coil Temperature of Air on Condenser Coil OD Dry Bulb 80 F OD Dry Bulb 95 F OD Dry Bulb 115 F Total Cap MBH Power Input KW Sensible Capa...

Page 5: ...the supply and return air duct system All internal unit resistances have been deducted from the total static pressure of the blower Do NOT close the pulley below 1 turn open Factory setting MODEL SIZE...

Page 6: ...INS PER 25mm 1 in 15 FACE AREA m2 Ft 2 4 02 43 3 COMPRESSOR Qty Per Unit TANDEM 8 TON NOMINAL CAPACITY 3 AIR FILTERS QUANTITY PER UNIT 406 x 508 x 51 mm 2 16 x 20 x 2 in QUANTITY PER UNIT 406 x 635 x...

Page 7: ...FIELD WIRING DCE DCG Electric Electric and Gas Electric Units 530 26 TG4YI Unitary Products Group 7...

Page 8: ...between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculat...

Page 9: ...cting side ducts For bottom duct applications 1 Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers 2 Remove and discard t...

Page 10: ...S 3207 126 1 4 Supply and Return Air including duct support rails as shown are typical for downflow duct applications For location of sideflow duct applications on back of unit refer to Unit Dimension...

Page 11: ...TYPICAL APPLICATIONS TYPICAL ROOF TOP INSTALLATION GAS ELECTRIC UNIT SHOWN 530 26 TG4YI Unitary Products Group 11...

Page 12: ...p P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1996 All Rights Reserved Code EBY EGY 530 26 TG4YI Superce...

Reviews: