The rainhood is painted to match the basic unit and must 
be field-assembled before installing.

Power exhaust is not available as a field installed 
option.

POWER EXHAUST

 - Our single economizer options are 

available with power exhaust. Whenever the outdoor air 
intake dampers are opened for free cooling, the exhaust 
fan will be energized to prevent the conditioned space 
from being over-pressurized during economizer opera-
tion.

The exhaust fan, motor and controls are installed and 
wired at the factory. The rain hood and the back-draft 
damper need to be assembled and installed in the field.

The power exhaust option can only be used on bot-
tom duct configurations.

MOTORIZED OUTDOOR AIR INTAKE DAMPER

 - 

Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a 
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit 
shuts down.

The rain hood is painted to match the basic unit and 
must be field assembled before installing.

PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS

 - Special coating process that utilizes 

Technicoat 10-1" processes. Coating is applied by total 
immersion of the complete coil for maximum protection.

ELECTRIC HEATERS

 wired for single point power sup-

ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent 
operation at excessive temperatures.

FILTER OPTIONS

 - Standard units are shipped with 2” 

throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.

BAS

 - See “Additional Options” section in the product 

nomenclature.

SMOKE DETECTORS

 - (supply air & return air) The 

smoke detectors stop operation of the unit by interrupting 
power to the control board if smoke is detected within the 
air compartment.

COIL GUARD

 - Customers can purchase a coil guard kit 

to protect the condenser coil from damage. This is not a 
hail guard kit.

STAINLESS STEEL HEAT EXCHANGER

 - For applica-

tions in corrosive environments, this option provides a 
full stainless steel heat exchanger assembly.

PHASE MONITORS 

- Designed to prevent unit damage. 

The phase monitor will shut the unit down in an out-of-
phase condition.

DIRTY FILTER SWITCH 

- This kit includes a differential 

pressure switch that energizes the fault light on the unit 

thermostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option 
or field installed accessory.

HINGED FILTER DOOR/”TOOLESS” BLOWER AND 
ACCESS PANELS (not hinged) 

- This option allows for 

easy access and maintenance.

NOTE:

Knobs are shipped separately within the unit to 
prevent shipping damage. These must be field 
installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS

 - Includes a slide-in / plug-in damper assembly 

with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal 
1% leakage type dampers.

The enthalpy system contains one sensor that monitors 
the outdoor air and determines when the air is cool 
enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must 
be field-assembled before installing.

Power exhaust is not available as a field installed option.

MOTORIZED OUTDOOR AIR INTAKE DAMPER

 - 

Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to 
some pre-set position whenever the supply air blower is 
operating and will drive fully closed when the blower unit 
shuts down.

The rain hood is painted to match the basic unit and 
must be field assembled before installing.

Power exhaust is not available as a field installed option.

ROOF CURBS

 - Fourteen-inch high roof curbs provide a 

water-tight seal between the unit and the finished roof. 
These full perimeter curbs meet the requirements of the 
National Roofing Contractors Association (NRCA) and 
are shipped knocked-down for field assembly.

They're designed to fit inside the base rails of the unit 
and include both a wood nailing strip and duct hanger 
supports.

HIGH ALTITUDE NATURAL GAS

 - Burner orifices and 

pilot orifices are provided for proper furnace operation at 
altitudes up to 6,000 feet.

PROPANE

 - Burner orifices, pilot orifices and gas valve 

parts are provided to convert a natural gas furnace to 
propane.

HIGH ALTITUDE PROPANE 

- Burner orifices and pilot 

orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the 
basic propane conversion kit.

Summary of Contents for Sunline 2000

Page 1: ...verhead rigging Every unit is completely piped wired charged and tested at the fac tory to simplify the field installation and to provide years of depend able operation Powder paint cabinets provide a...

Page 2: ...HOOD 20 6 CENTER OF GRAVITY 20 7 ROOF CURB DIMENSIONS ALL MODELS 21 8 ROOF CURB BENEFITS 21 9 UNIT CURB AND APPLICATIONS 21 10 TYPICAL APPLICATION 22 11 TYPICAL ROOF TOP INSTALLATION 22 LIST OF TABLES...

Page 3: ...alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection and Strikes To prevent nuisance trouble calls the control board uses a three times you re out p...

Page 4: ...phase monitor will shut the unit down in an out of phase condition DIRTY FILTER SWITCH This kit includes a differential pressure switch that energizes the fault light on the unit thermostat indicating...

Page 5: ...y should be mounted on the return air duct ENTHALPY ACCESSORY CONTROL KIT This kit contains the required components to convert a single enthalpy economizer to dual enthalpy BURGLAR BARS Mount in the s...

Page 6: ...ust N Options 2 3 D Std Mtr Drive Motorized Damper P Options 2 4 Heat Type Nominal Heat Capacity F Std Mtr Drive 4 Filters Q Options 2 3 4 C00 Cooling Only No field installed electric heat G Std Mtr D...

Page 7: ...ontroller DFS APS Technicoat Cond Coil Phase Monitor CG CPC Controller DFS APS Technicoat Cond Coil Coil Guard CH CPC Controller DFS APS Technicoat Cond Coil Phase Monitor Coil Guard CJ CPC Controller...

Page 8: ...oil Phase Monitor Coil Guard Hinged Filter Door Tooless Access Panels EN Johnson UNT Controller DFS APS Technicoat Evap Cond Coils Hinged Filter Door Tooless Access Panels EP Johnson UNT Controller DF...

Page 9: ...Phase Monitor JC Johnson UNT Controller DFS APS Coil Guard JD Johnson UNT Controller DFS APS Phase Monitor Coil Guard JE Johnson UNT Controller DFS APS Technicoat Cond Coil JF Johnson UNT Controller D...

Page 10: ...coat Evap Coil Phase Monitor Hinged Filter Door Tooless Access Panels PL Novar ETC 3 Controller DFS APS Technicoat Evap Coil Coil Guard Hinged Filter Door Tooless Access Panels PM Novar ETC 3 Controll...

Page 11: ...Technicoat Evaporator Coil Phase Monitor Hinged Filter Door Tooless Access Panels UL Technicoat Evaporator Coil Coil Guard Hinged Filter Door Tooless Access Panels UM Technicoat Evaporator Coil Dirty...

Page 12: ...27 3 67 49 32 88 32 0 62 45 28 20 100 24 0 90 71 53 35 94 26 4 89 69 51 34 83 31 2 83 64 47 30 17 94 23 5 94 94 74 55 90 25 9 90 89 72 53 79 30 5 79 77 66 47 14 94 23 5 94 94 88 76 89 25 8 89 89 83 74...

Page 13: ...5 268 265 247 230 9000 73 362 24 6 219 164 110 341 27 1 214 158 105 295 31 8 200 144 93 68 334 23 9 287 228 171 116 315 26 2 282 222 166 111 275 30 7 261 206 151 96 63 311 23 2 311 296 236 178 295 25...

Page 14: ...1040 3 0 443 6 6 5 4 347 8 1 6 7 228 9 7 8 0 1070 2 0 489 6 9 5 7 396 8 5 7 0 280 10 2 8 3 1100 1 0 536 7 3 6 0 445 8 9 7 3 332 10 6 8 7 1130 0 0 583 7 6 6 2 495 9 3 7 6 385 11 0 9 0 DM300 UNIT DOWNF...

Page 15: ...ted in the respective blower performance table except for Horizontal Duct Connections Add these values due to less airflow resistance TABLE 7 BLOWER MOTOR AND DRIVE DATA MODEL SIZE BLOWER RANGE RPM MO...

Page 16: ...or 102mm optional QUANTITY PER UNIT 406 x 508 x 51 mm 2 16 x 20 x 2 in QUANTITY PER UNIT 406 x 635 x 51 mm 4 16 x 25 x 2 in QUANTITY PER UNIT 457 x 610 x 51 mm 3 14 x 20 x 2 in TOTAL FACE AREA m2 Ft 2...

Page 17: ...26 9 2 37 4 76 0 90 E054 40 4 2 56 2 94 0 100 E072 53 8 2 74 9 98 6 110 1 Electric Heat CORRECTION FACTORS 2 Dual element time delay fuse or HACR breaker NOMINAL VOLTAGE VOLTAGE KW CAP MULTIPLIER 415...

Page 18: ...AL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Ju...

Page 19: ...be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge outlet Note Cool Only Models Units and ductwork are approved for zero clearance to combustible materi...

Page 20: ...are closed with sheet metal covers except when the unit includes a power exhaust option The cov ering consists of a black paper composition 3 Replace the side supply and return air compartment panels...

Page 21: ...ONS ALL MODELS Supply and Return air including duct support rails as shown are typical for Downflow duct applications For location of Sideflow duct applica tions on back of unit refer to Unit Dimensio...

Page 22: ...036 21060 004 A 1102 22 Unitary Products Group FIGURE 10 TYPICAL APPLICATION FIGURE 11 TYPICAL ROOF TOP INSTALLATION GAS ELECTRIC UNIT SHOWN...

Page 23: ...036 21060 004 A 1102 Unitary Products Group 23...

Page 24: ...o change without notice Printed in U S A 036 21060 004 A 1102 Copyright by Unitary Products Group 2002 All rights reserved Supersedes 036 21060 003 A 0802 Unitary 5005 Norman Products York OK Group Dr...

Reviews: