![background image](http://html2.mh-extra.com/html/york/sunline-2000/sunline-2000_technical-manual_4177261017.webp)
036-21060-004-A-1102
Unitary Products Group
17
TABLE 10: ELECTRICAL DATA - UNITS WITH ELECTRIC HEAT
MODEL
DM
POWER
SUPPLY
HEATER OPTION
MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
OVERCURRENT
DEVICE
2
(AMPS)
MODEL
KW
1
STAGES
AMPS
300
380-3-50
E018
11.3
1
17.1
76.0
90
E036
22.6
2
34.3
76.0
90
E054
33.8
2
51.4
87.9
90
E072
45.1
2
68.6
109.4
110
415-3-50
E018
13.5
1
18.7
76.0
90
E036
26.9
2
37.4
76.0
90
E054
40.4
2
56.2
94.0
100
E072
53.8
2
74.9
98.6
110
1
Electric Heat CORRECTION FACTORS:
2
Dual element time delay fuse or HACR breaker.
NOMINAL VOLTAGE
VOLTAGE
KW CAP.
MULTIPLIER
415
400
0.93
WEIGHTS (KG. / LBS.)
BASIC UNIT
DM300 (Cooling only)
1238 / 2730
DM300 (Gas / Electric)
N24
N32
1332 / 2930
1360 / 2992
OPTIONS / ACCESSORIES
Electric Heater
(Elec/Elec only)
18 KW
11.4 / 25
36 KW
13.6 / 30
54 KW
15.9 / 35
72 KW
18.2 / 40
Economizer
73 / 160
Motorized Damper
68 / 150
Roof Curb
84 / 185
Barometric Damper
20 / 45
Wood Skid
1
100 / 220
1. Allows handling of unit using 90° (2300mm) long forks.