background image

ELECTRIC HEATERS

Electric heaters are available as field-installed accessories.
Refer to Form 530.18-N7.1V for installation instruction. These
UL and CGA approved heaters are located within the central
compartment of the unit (see Figure 5 for access panel) with
the heating elements extending into the supply air chamber.

The heaters are wired for a single point power supply. Power
supply need only be brought into the single point terminal block
and thermostat wiring to the low voltage terminal strip located
in the upper portion of the unit control box.

Fuses are supplied, where required, by the factory. Some KW
sizes require fuses and others do not. Refer to the accessory
instruction for electrical data.

FIG. 6 - ENTHALPY SET POINT ADJUSTMENT

w/Direct-Drive Blower

TABLE 3 - SUPPLY AIR PERFORMANCE - 3 THRU 6 TON

UNIT

SIZE

MOTOR

SPEED

Available External Static Pressure - IWG*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts

036

HI

MED
LOW

-

1684
1487

-
  800
  710

-

1631
1464

-

780
690

1699
1582
1421

825
750
670

1650
1524
1367

785
720
650

1570
1410
1315

755
690
620

1430
1324
1246

725
650
605

1360
1260

1185

700
630
590

1280

1185

1110

680
610
570

1180
1100

1020

655
590
545

048

HI

MED
LOW

1996
1804
1681

960
838
760

1933
1765
1640

936
810
738

1868
1714
1604

910
785
715

1795
1650
1541

880
765
695

1722
1589
1490

845
735
670

1635
1508
1416

820
705
645

1544
1407
1337

790
675
620

1419
1306
1230

765
645
595

1300

1195
1120

740
625
575

060

HI

MED
LOW

2400
2290
2150

1155
1105
1020

2338
2214
2100

1125

1065
  990

2274
2145
2029

1095
1030
  950

2167
2071
1965

1045
  990
  910

2096
1990
1905

1010
  950
  880

1990

1911

1816

980
920
838

1887
1828
1724

945
885
800

1771
1724
1644

905
835
770

1629
1604
1531

855
798
710

072

HI

2461 1480 2402 1440 2361 1395 2260 1350 2178 1305 2101 1260 2000 1205 1914 1155 1830

1110

NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95. 

*

INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS AND GAS-FIRED HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE

  VALUES ON APPLICATIONS OTHER THAN GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.

- Side Duct Connections

GAS HEAT VALUES SHOWN @ 230/460/575 VOLTS

530.18-N7Y

8

Unitary Products Group

Summary of Contents for Sunline 2000

Page 1: ...equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York PA 17405 APPROVALS Design certified by U L and C G A a...

Page 2: ...rf 5 6 Ton Belt Drive 10 6 Static Resistances 11 7 Motor and Drive Data Belt Drive 11 8 Electrical Data Direct Drive 11 9 Electrical Data Belt Drive 11 10 Supperheat 036 12 11 Supperheat 048 12 12 Sup...

Page 3: ...d with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 42 Remove the nesting brackets from the four corners on top of the unit All scre...

Page 4: ...wiring diagram Electrical lines must be sized properly to carry the load USE COPPER CONDUCTORS ONLY Each unit must be wired with a separate branch circuit fed directly from the meter panel and proper...

Page 5: ...hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood be...

Page 6: ...UNIT HAS AN ECONOMIZER REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE SCROLL COMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER O...

Page 7: ...roper size of the supply and return air duct connections SCROLL COMPRESSOR ACCESS 111 2 45 8 3 77 8 61 2 171 2 111 2 171 2 REAR VIEW SIDE SUPPLY AND RETURN AIR OPENINGS UNIT BASE WITH RAILS FRONT VIEW...

Page 8: ...D LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610...

Page 9: ...ATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 6...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...S MIN MAX RLA LRA 036 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 18 0 11 4 6 2 5 0 105 0 90 0 45 0 36 0 1 3 1 3 0 8 0 8 4 4 4 4 2 2 2 2 28 2 20 0 10 8 9 3 45 30 15 15...

Page 12: ...5 2 17 4 19 5 21 6 23 7 25 6 27 5 29 5 31 4 80 7 5 9 6 11 7 13 9 16 0 18 2 20 3 22 6 24 8 27 1 29 3 85 6 1 8 3 10 4 12 6 14 8 16 9 19 5 22 1 24 7 27 3 90 6 6 8 2 9 8 11 4 13 0 16 1 19 1 22 2 25 2 95 5...

Page 13: ...24 1 27 2 28 7 30 2 31 7 33 2 80 5 2 8 5 11 7 15 0 18 2 21 4 24 7 26 3 27 9 29 6 31 2 85 5 3 8 7 12 0 15 4 18 8 22 2 23 9 25 7 27 4 29 2 90 5 1 7 7 10 4 13 0 15 7 18 4 20 7 23 1 25 4 27 8 95 6 8 8 7...

Page 14: ...for heating by the thermostat b Upon a call for heat by the thermostat the first stage of heat will be energized Sequencer 1S or contactor 2M is always the first and last to complete its timing cycle...

Page 15: ...removed in Step 1 NOTE DE ENERGIZE THE SCROLL COMPRESSORS BE FORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL SECURE OWNER S APPROVAL When the system is functioning properly secure the ow...

Page 16: ...air circuit Cleaning should be as often as necessary to keep coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to clean coil be sure power to the unit is shut o...

Reviews: