background image

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

Economizer

1, 3

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

Electric Heaters

1

5 - 15 KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20 - 30 KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

Bottom Duct Connections

1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

Cooling Only

2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1

Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2

Add these resistance values to the available static resistance in the respective Blower Performance Table.

3

The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM

  during full economizer operation.

TABLE 6 - STATIC RESISTANCES

UNIT

SIZE

BLOWER

RANGE

(RPM)

MOTOR*

ADJUSTABLE

MOTOR PULLEY

FIXED

BLOWER PULLEY

BELT

HP

RPM

FRAME

SIZE

SERVICE

FACTOR

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

LENGTH

(in.)

DESIG-

NATION

DCE036

780 - 1090

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

1

37.3

A36

DCE048

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

1

37.3

A36

DCE060

850 - 1220

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.2

1

37.3

A36

DCE072

900 - 1250

1-1/2

1725

56

1.15

2.8 - 3.8

7/8

5.2

1

37.3

A36

*

All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any

TABLE 7 - MOTOR AND DRIVE DATA - Belt-Drive Blower

UNIT

SIZE

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

SCROLL

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

18.0

11.4

6.2
5.0

105.0

90.0
45.0
36.0

1.3
1.3
0.8
0.8

4.4
4.4
2.2
2.2

28.2
20.0
10.8

9.3

45
30
15
15

45
30
15

-

048

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

24.4
14.1

7.1
5.6

140.0
105.0

55.0
44.0

1.3
1.3
0.8
0.8

5.0
5.0
2.2
2.2

36.8
23.9

11.9

10.1

60
35
15
15

60
35
15

-

060

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

28.9
16.0

8.0
6.4

165.0
125.0

67.0
50.0

1.3
1.3
0.8
0.8

6.6
6.6
3.3
3.3

44.0
27.9
14.1
12.1

70
40
20
15

70
40
20

-

072

208/230-3-60

460-3-60
575-3-60

187
414
518

253
504
630

20.3
10.2

8.2

146.0

73.0
58.4

1.3
0.8
0.8

6.8
3.6
3.6

33.5
17.2
14.7

50
25
20

50
25

-

NOTES: 

1. Utilization Range “A” in accordance with ARI Standard 110.          2. Dual element, time delay type.

w/Direct-Drive Blower Motor

TABLE 8 - ELECTRICAL DATA (BASIC UNIT)

UNIT

SIZE

POWER

SUPPLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

SCROLL

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

18.0

11.4

6.2
5.0

105.0

90.0
45.0
36.0

1.3
1.3
0.8
0.8

5.3
5.3
3.1
3.1

29.1
20.9

11.7

10.2

45
30
15
15

45
35
15

-

048

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

24.4
14.1

7.1
5.6

140.0
105.0

55.0
44.0

1.3
1.3
0.8
0.8

8.6
5.2
2.6
2.0

40.4
24.1
12.3

9.9

60
35
15
15

60
35
15

-

060

208/230-1-60
208/230-3-60

460-3-60
575-3-60

187
187
414
518

253
253
504
630

28.9
16.0

8.0
6.4

165.0
125.0

67.0
50.0

1.3
1.3
0.8
0.8

8.6
6.0
3.0
2.4

46.0
27.3
13.8

11.2

70
40
20
15

70
40
20

-

072

208/230-3-60

460-3-60
575-3-60

187
414
518

253
504
630

20.3
10.2

8.2

146.0

73.0
58.4

1.3
0.8
0.8

7.3
3.7
2.8

34.0
17.3
13.9

50
25
20

50
25

-

NOTES: 

1. Utilization Range “A” in accordance with ARI Standard 110.          2. Dual element, time delay type.

TABLE 9 - ELECTRICAL DATA (BASIC UNIT)

w/Belt-Drive Blower Motor

530.18-N7Y

Unitary Products Group

11

Summary of Contents for Sunline 2000

Page 1: ...equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York PA 17405 APPROVALS Design certified by U L and C G A a...

Page 2: ...rf 5 6 Ton Belt Drive 10 6 Static Resistances 11 7 Motor and Drive Data Belt Drive 11 8 Electrical Data Direct Drive 11 9 Electrical Data Belt Drive 11 10 Supperheat 036 12 11 Supperheat 048 12 12 Sup...

Page 3: ...d with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 42 Remove the nesting brackets from the four corners on top of the unit All scre...

Page 4: ...wiring diagram Electrical lines must be sized properly to carry the load USE COPPER CONDUCTORS ONLY Each unit must be wired with a separate branch circuit fed directly from the meter panel and proper...

Page 5: ...hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood be...

Page 6: ...UNIT HAS AN ECONOMIZER REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE SCROLL COMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER O...

Page 7: ...roper size of the supply and return air duct connections SCROLL COMPRESSOR ACCESS 111 2 45 8 3 77 8 61 2 171 2 111 2 171 2 REAR VIEW SIDE SUPPLY AND RETURN AIR OPENINGS UNIT BASE WITH RAILS FRONT VIEW...

Page 8: ...D LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610...

Page 9: ...ATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 6...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...S MIN MAX RLA LRA 036 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 18 0 11 4 6 2 5 0 105 0 90 0 45 0 36 0 1 3 1 3 0 8 0 8 4 4 4 4 2 2 2 2 28 2 20 0 10 8 9 3 45 30 15 15...

Page 12: ...5 2 17 4 19 5 21 6 23 7 25 6 27 5 29 5 31 4 80 7 5 9 6 11 7 13 9 16 0 18 2 20 3 22 6 24 8 27 1 29 3 85 6 1 8 3 10 4 12 6 14 8 16 9 19 5 22 1 24 7 27 3 90 6 6 8 2 9 8 11 4 13 0 16 1 19 1 22 2 25 2 95 5...

Page 13: ...24 1 27 2 28 7 30 2 31 7 33 2 80 5 2 8 5 11 7 15 0 18 2 21 4 24 7 26 3 27 9 29 6 31 2 85 5 3 8 7 12 0 15 4 18 8 22 2 23 9 25 7 27 4 29 2 90 5 1 7 7 10 4 13 0 15 7 18 4 20 7 23 1 25 4 27 8 95 6 8 8 7...

Page 14: ...for heating by the thermostat b Upon a call for heat by the thermostat the first stage of heat will be energized Sequencer 1S or contactor 2M is always the first and last to complete its timing cycle...

Page 15: ...removed in Step 1 NOTE DE ENERGIZE THE SCROLL COMPRESSORS BE FORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL SECURE OWNER S APPROVAL When the system is functioning properly secure the ow...

Page 16: ...air circuit Cleaning should be as often as necessary to keep coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to clean coil be sure power to the unit is shut o...

Reviews: