background image

OPTIONAL ECONOMIZER RAIN HOOD

The following procedure should be used when assembling an
economizer rain hood onto a unit. Refer to Figure 3. The
outdoor and return air dampers, damper actuator, the linkage
and all the controls are factory mounted as part of the
economizer option.

All of the hood components, including the filters, the gasketing
and the hardware for assembling are located above the top filter
racks within the filter section. The outdoor air sensor is in the
bag of parts located at the bottom of the return air section.

1. With filter section access panel removed, take out hood

components, filters and sensor described above. Remove
and discard outdoor air opening cover on back unit (Upper
right hand corner).

2. Remove the 1/2" knockout (A) in the units rear panel

(located to the right side of the outdoor air opening). Insert
the two loose wires from inside the unit, into the 1/2"
bushing provided. Insert wires and bushing into knockout.
Snap bushing into place.

3. Mount the outdoor air sensor to the rear panel, just below

the knockout  described  in Step 2. Secure with two
self-drilling screws at dimples (B) provided in the panel.

NOTE: Sensor must be positioned so that the sensing

ports are at the top (louvers pointing downward)
and terminal connections to the right.

4. Connect the two wires, indicated in Step 2, to the sensor

as follows:

Wire #73 to terminal (+)

Wire #74 to terminal (S)

5. Assemble the LH and RH side plates to the top cover

(2 screws each side) to form the hood. Apply gasketing to
the flange surface on each side plate. Extend gasketing
1/4" beyond top and bottom of each flange to insure ade-
quate corner sealing. Secure this assembly to the unit back
panel (upper right hand corner). First, remove screw (C) on

unit top cover. Then slip flange of hood cover in under flange
of unit top cover, replace screw (C), engaging hole (E) in
hood flange and tighten. Attach the two side plates to the
unit panel by using two self-drilling screws for each side
plate at dimples (D) provided in the panel.

6. Position fillpiece at bottom of hood, between the two side

plates but do not secure at this time. (Slotted openings
MUST be downward for drainage). After fillpiece is properly
positioned, note where contact is made with the unit panel.
Remove fillpiece and apply gasket material to this area to
provide a seal. Reposition fillpiece and secure with 2
screws.

7. Install the two filters into the hood assembly, sliding down

along retainers on side plates, into fillpiece at bottom of
hood.

NOTE: Install filters so that “Air Flow” arrows point toward

the unit.

8. Install filter cover over the end of the hood with one screw

(center of hood), securing filters into position.

CAUTION: When proceeding with steps 9 and 10, extreme

care must be exercised while turning both the set
point and minimum position adjusting screws to
prevent twisting them off.

9. The enthalpy set point for the dampers may now be set by

selecting the desired set-point from graph in Figure 6. For
a single enthalpy economizer, carefully turn the set-point
adjusting screw to the “A”, “B”, “C” or “D” setting
corresponding to the lettered curve. For a dual enthalpy
economizer, carefully turn the set-point adjusting screw
fully clockwise past the “D” setting.

10. To check that the damper blades move smoothly without

binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals “R” to “G”. With terminals “R” to “G” energized,
turn the minimum position screw counterclockwise until the
desired minimum position has been attained.

11. Replace the filter section access panel.

B

GASKET

C

HOOD
COVER

OUTDOOR AIR
SENSOR

A

FILTER SECTION
ACCESS PANEL

D

GASKETED
FLANGE

R. H.
SIDE
PLATE

D

E

D

D

GASKETED
FLANGE

FILTER
COVER

L. H. SIDE
PLATE

FILTERS

FILLPIECE

OUTDOOR AIR
OPENING COVER

SIDE DUCT

APPLICATION SHOWN

FIG. 3 - ECONOMIZER RAIN HOOD ASSEMBLY (OPTION)

530.18-N7Y

Unitary Products Group

5

Summary of Contents for Sunline 2000

Page 1: ...equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York PA 17405 APPROVALS Design certified by U L and C G A a...

Page 2: ...rf 5 6 Ton Belt Drive 10 6 Static Resistances 11 7 Motor and Drive Data Belt Drive 11 8 Electrical Data Direct Drive 11 9 Electrical Data Belt Drive 11 10 Supperheat 036 12 11 Supperheat 048 12 12 Sup...

Page 3: ...d with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 42 Remove the nesting brackets from the four corners on top of the unit All scre...

Page 4: ...wiring diagram Electrical lines must be sized properly to carry the load USE COPPER CONDUCTORS ONLY Each unit must be wired with a separate branch circuit fed directly from the meter panel and proper...

Page 5: ...hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood be...

Page 6: ...UNIT HAS AN ECONOMIZER REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE SCROLL COMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER O...

Page 7: ...roper size of the supply and return air duct connections SCROLL COMPRESSOR ACCESS 111 2 45 8 3 77 8 61 2 171 2 111 2 171 2 REAR VIEW SIDE SUPPLY AND RETURN AIR OPENINGS UNIT BASE WITH RAILS FRONT VIEW...

Page 8: ...D LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610...

Page 9: ...ATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 6...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...S MIN MAX RLA LRA 036 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 18 0 11 4 6 2 5 0 105 0 90 0 45 0 36 0 1 3 1 3 0 8 0 8 4 4 4 4 2 2 2 2 28 2 20 0 10 8 9 3 45 30 15 15...

Page 12: ...5 2 17 4 19 5 21 6 23 7 25 6 27 5 29 5 31 4 80 7 5 9 6 11 7 13 9 16 0 18 2 20 3 22 6 24 8 27 1 29 3 85 6 1 8 3 10 4 12 6 14 8 16 9 19 5 22 1 24 7 27 3 90 6 6 8 2 9 8 11 4 13 0 16 1 19 1 22 2 25 2 95 5...

Page 13: ...24 1 27 2 28 7 30 2 31 7 33 2 80 5 2 8 5 11 7 15 0 18 2 21 4 24 7 26 3 27 9 29 6 31 2 85 5 3 8 7 12 0 15 4 18 8 22 2 23 9 25 7 27 4 29 2 90 5 1 7 7 10 4 13 0 15 7 18 4 20 7 23 1 25 4 27 8 95 6 8 8 7...

Page 14: ...for heating by the thermostat b Upon a call for heat by the thermostat the first stage of heat will be energized Sequencer 1S or contactor 2M is always the first and last to complete its timing cycle...

Page 15: ...removed in Step 1 NOTE DE ENERGIZE THE SCROLL COMPRESSORS BE FORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL SECURE OWNER S APPROVAL When the system is functioning properly secure the ow...

Page 16: ...air circuit Cleaning should be as often as necessary to keep coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to clean coil be sure power to the unit is shut o...

Reviews: