COOLING SYSTEM

The cooling section is a complete factory package utilizing an
air-cooled condenser. The system is factory-charged with
Refrigerant-22.

The compressors are hermetically sealed, internally sprung
and base-mounted with rubber-insulated hold-down bolts.

The compressors also have inherent (internal) protection. If
there is an abnormal temperature rise in a compressor, the
protector will open to shut down the compressor.

PRELIMINARY OPERATION COOLING

After installation has been completed, energize the crankcase
heaters for at least four hours before operating unit. After this
initial warm-up, the compressors should be given three false
starts (energized just long enough to make a few revolutions)
with 5-7 minutes delay between each start before being put into
full time service.

NOTE: Prior to each cooling season, the crankcase heaters

must be energized at least 10 hours before system is
put into operation.

COOLING SEQUENCE OF OPERATION

When the thermostat calls for “first-stage” cooling, the low
voltage control circuit from “R” to “G” and “Y1" (wiring
schematic) is completed to energize compressor #1,
condenser fan motor #1 and blower motor simultaneously.

When the thermostat calls for “2nd-stage” cooling, the low
voltage control circuit from “R” to “Y2" is completed to energize
compressor #2 and condenser fan motor #2.

After the thermostat is satisfied and opens, all components
likewise stop simultaneously.

CONTINUOUS BLOWER - Continuous blower operation is
possible by closing the R to G circuit on the thermostat.

SAFETY CONTROLS

Each refrigerant system is equipped with the following safety
controls:

1. A Suction Line Freezestat to protect against low evaporator

temperatures due to a low air flow or a low return air
temperature. (Opens at 26

°

F + 5

°

F and resets at 38

°

F +

5

°

F).

2. A High Pressure Cutout Switch to protect against excessive

discharge pressures due to a blocked condenser coil or a
condenser motor failure. (Opens at 380 psig + 10 and
resets at 300 psig +10).

3. A Low Pressure Switch/Loss Of Charge to protect against

loss of refrigerant charge. (Opens at 7 psig + 3 and resets
at 22 psig + 5).

If either one of the above safety controls opens, that individual
refrigerant system will bo locked out. The other refrigerant
system will continue in operation unless it too is effected by the
same fault. The lock out of either system can be reset by
opening the 24V circuit either at the room thermostat or at the
unit disconnect.

HEATING SEQUENCE OF OPERATION

The following sequence describes the operation of the gas heat
section.

CONTINUOUS BLOWER: With the room thermostat switch set
to “ON”, the supply air blower will operate continuously. The
normally closed contact “K5-1" provides 24 volt power to the
“M3” relay. The “M3-1” and “M3-2" power contacts close and
the blower motor operates.

INTERMITTENT BLOWER: With the room thermostat
system switch set to the “AUTO” or “HEAT” position and the
fan switch set to “AUTO”, the supply air blower will operate
after the room thermostat calls for heat and the time delay
relay closes.

OPERATION

MODEL

POWER

SUPPLY

COMPRESSOR

(#1 and #2)

OUTDOOR

FAN

MOTOR,

(#1 & #2)

FLA

EACH

SUPPLY

AIR

BLOWER

MOTOR,

FLA

TOTAL

UNIT

AMPACITY,

AMPS

MAX.

FUSE
SIZE

1

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

RLA

EACH

LRA

EACH

2HP

3HP

5HP

2HP

3HP

5HP

D3CG090

208/230-3-60

460-3-60
575-3-60

14.1

7.1
5.8

130

64
52

2.3
1.3
1.3

7.5
3.4
2.7



-—


43.8
21.9
18.3





50
25
20

50
25

D3CG102

208/230-3-60

460-3-60
575-3-60

16.0

8.3
7.1

137

69
58

2.3
1.3
1.3

7.5
3.4
2.7

10.6

4.8
3.9



48.2
24.8
21.2

51.3
26.2
22.4



60
30
25

60
30

D3CG120

208/230-3-60

460-3-60
575-3-60

16.7

9.6
8.3

150

73
62

2.3
1.3
1.3

7.5
3.4
2.7

10.6

4.8
3.9



49.6
27.6
24.1

52.7
29.0
25.3



60
35
30

60
35

D4CG090

208/230-3-60

460-3-60
575-3-60

13.1

6.7
5.8

90
45
36

2.3
1.3
1.3

7.5
3.4
2.7





41.6
21.1
18.3





50
25
20

50
25

D4CG120

208/230-3-60

460-3-60
575-3-60

17.2

8.5
6.4

125

67
50

2.3
1.3
1.3

7.5
3.4
2.7

10.6

4.8
3.9



50.8
25.1
19.7

53.9
26.5
20.9



60/70
30/35

25

60/70
30/35

D4CG150

208/230-3-60

460-3-60
575-3-60

21.8

9.6
9.0

158

79
65

3.5
2.5
2.5



10.6

4.8
3.9

15.1

7.5
5.9



66.6
31.4
29.1

71.1
34.1
31.1

80/90

40

35/40

90/100

50

NOTES:

1. Dual element, time delay type. Amps shown as “80/90" indicates rating for 3 HP / 5 HP, respectively.
2. Based on 75

°

C copper conductors.

TABLE 10 - ELECTRICAL DATA

530.18-N10Y

Unitary Products Group

13

Summary of Contents for Sunline 2000 D3CG090

Page 1: ...ccessory 530 18 N10 5V Propane Conversion Accessory USA 530 18 N10 6V High Altitude Accessory Nat Gas 530 18 N10 7V High Altitude Accessory Propane 690 15 N28V Low Ambient Accessory Renewal Parts Refer to the Renewal Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products...

Page 2: ... Gas Heat Application Data 5 3 Pipe Sizing 5 4 Physical Data 8 5 Point Loads 10 6 Supply Air Blower Perf 7 1 2 10 Ton 11 7 Supply Air Blower Perf 12 1 2 Ton 12 8 Accessory Static Resistances 12 9 Blower Motor and Drive Data 12 10 Electrical Data 13 11 Limit Control Setting 14 12 Blower Motor Pulley Adjustment 16 13 Gas Rate Cubic Feet Per Hour 17 FIGURES No Description Page 1 Center of Gravity 3 2...

Page 3: ...ing must be applied to all surfaces that come in contact with the unit underside 5 Maintain level tolerance to 1 2 maximum across the entire length or width of the unit RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Sp...

Page 4: ... above the floor where it will not be subject to drafts sun exposure or heat from electrical fixtures or appliances Follow manufacturer s instructions enclosed with thermostat for general installation procedure Seven color coded insulated wires 18 AWG should be used to connect thermostat to unit POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the National Electrical...

Page 5: ...cases unless superseded by local codes or gas company requirements The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utility requirement specifying a minimum diameter for gas piping All units require a 1 2 or 3 4 inch pipe connection at the gas valve GAS CONNECTION The gas supply line can be routed through the...

Page 6: ...n three main factors 1 The vaporization rate which depends on a the temperature of the liquid and b the wetted surface area of the container or containers 2 The proper pressure regulation Two stage regulation is recommended from the standpoint of both cost and effi ciency 3 The pressure drop in the lines between regulators and between the second stage regulator and the appliance Pipe size required...

Page 7: ...sing 6 gasketed screws in each side plate 4 Secure the flange on the hood cover to the duct panel with 3 screws Use holes in the cover flange as a template and drill 3 holes 9 64 dia 26 drill into the duct panel 5 Insert two 2 1 filters into the center of the hood coming to rest in the center filter support at the back of the hood Press filters up against the filter guide angles on the side plates...

Page 8: ...er Unit PROPELLER DIA in 24 ea 24 ea 24 ea 24 ea FAN MOTOR HP 1 2 ea 1 2 ea 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 3200 ea 3600 ea 4400 ea CONDENSER COIL ROWS DEEP 2 2 2 2 FINS PER INCH 13 13 13 13 FACE AREA Sq Ft 16 7 20 0 24 0 29 3 AIR FILTERS SEE NOTE QUANTITY PER UNIT 12 X 24 X 2 2 2 QUANTITY PER UNIT 16 X 24 X 2 2 2 2 3 QUANTITY PER UNIT 18 X 24 X 2 2 2 TOTAL FACE AREA sq ft 9 3 9 3 11 3 14 0 CH...

Page 9: ... in the insulation UTILITIES ENTRY DATA RETURN AIR OUTDOOR AIR Economizer SUPPLY AIR CONDENSER AIR DUCT COVERS Units are shipped with all air duct openings covered For side duct applications 1 Remove and discard the supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For bottom duct applications 1 Remove the side supply and return air duct covers to gain ac...

Page 10: ...ht Side Cond Coil 24 Below Unit1 20 Above Unit2 72 with 36 maximum Horizontal Overhang For Condenser Air Discharge 1 Locate unit so that the vent air outlet hood is at least Three 3 feet above any forced air inlet located within 10 horizontal feet excluding those integral to the unit Four 4 feet below 4 horizontal feet from or 1 foot above any door or gravity air inlet into the building Four 4 fee...

Page 11: ...39 1 54 1 44 0 04 1 75 1 63 1070 0 86 1 46 1 36 0 54 1 68 1 57 0 20 1 89 1 76 0 04 2 11 1 97 1130 1 07 1 57 1 46 0 73 1 83 1 71 0 39 2 04 1 90 0 13 2 22 2 06 1175 1 27 1 67 1 56 0 94 1 92 1 79 0 58 2 18 2 03 0 28 2 34 2 16 1220 1 44 1 81 1 69 1 10 2 10 1 96 0 66 2 37 2 15 0 36 2 78 2 56 MODEL DCG102 BOTTOM DUCT APPLICATIONS BLOWER SPEED RPM CFM 3000 3500 4000 4500 5000 ESP BHP KW ESP BHP KW ESP BH...

Page 12: ... 54 0 11 3 03 2 83 1000 1 20 2 33 2 17 0 93 2 62 2 45 0 65 2 91 2 72 0 35 3 24 3 03 0 16 4 20 3 91 1050 1 42 2 55 2 37 1 14 2 86 2 67 0 85 3 17 2 96 0 62 4 06 3 79 0 39 4 53 4 22 1090 1 63 2 72 2 54 1 34 3 06 2 86 1 10 3 78 3 53 0 78 4 28 3 99 0 58 4 79 4 46 1105 1 74 3 08 2 87 1 47 3 45 3 22 1 18 3 88 3 62 0 85 4 35 4 06 0 66 4 89 4 56 1140 1 91 3 25 3 03 1 63 3 66 3 41 1 35 4 11 3 83 1 02 4 53 4...

Page 13: ...frigerant charge Opens at 7 psig 3 and resets at 22 psig 5 If either one of the above safety controls opens that individual refrigerant system will bo locked out The other refrigerant system will continue in operation unless it too is effected by the same fault The lock out of either system can be reset by opening the 24V circuit either at the room thermostat or at the unit disconnect HEATING SEQU...

Page 14: ...tes when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the ignition control and closing the main gas valve and energizing the blower 2 Centrifugal Switch CS If the draft motor should fail the centrifugal switch attached to the shaft of the motor pre vents the ignition control and gas valve from being ener gized 3 Redundant Gas Valve This valve is an in...

Page 15: ...ows 1 Remove the cap on the regulator It s located next to the push on electrical terminals 2 To decrease the gas pressure turn the adjusting screw coun terclockwise 3 To increase the gas pressure turn the adjusting screw clock wise NOTE The correct manifold pressure for these furnaces is 3 5 IWG 0 3 PILOT CHECKOUT The pilot flame should envelope the end of the flame sensor as shown in Proper Flam...

Page 16: ...ted 1 Remove the dot plugs from the holes in the filter access and blower access panels as shown in the Dimensions and Clearances figure 2 Insert at least 8 of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the evaporator or indoor coil NOTE The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres ...

Page 17: ...being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size CFM Btuh Input x 0 8 1 08 x o F Temp Rise SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjust temperature settings ...

Page 18: ...pplied along top of the burner COMBUSTION AIR DISCHARGE Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need cleaning If the element should...

Page 19: ...t effect the test if it is done within 5 minutes of furnace shut down 2 The supply air blower operates but the draft motor does not when the room thermostat is set to call for heat and the fan switch in the ON position a The draft motor has inherent protection If the motor shell is hot to the touch wait for the internal overload to reset b If the motor shell is cold with the room thermostat callin...

Page 20: ...arryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another 9 Main burners light but exhibit erratic flame characteristics a Adjust air shutters as described in BURNER AIR SHUTTER ADJUSTMENT b Check the main burner orifices for obstruction and alignment Removal procedure is described in BURNER INSTRUCTIONS ...