VENT AND COMBUSTION AIR HOODS

The vent and combustion air hoods are shipped attached to the
blower housing in the blower compartment. These hoods must
be installed on the outside of the gas heat access panel to
ensure proper unit function. The necessary mounting screws
are  provided in a bag also attached to the blower housing.

The screen for the combustion air intake hood is secured to the
inside of the access panel opening with three fasteners and the
screws used for mounting the hood to the panel. The top flange
of this hood slips in under the top of the access panel opening
when installing. Refer to Figure 5. Remove the protective label
covering the opening just prior to installing this hood.

The vent hood (including its screen) is installed by inserting the
top flange of the hood into the slotted opening in the access
panel. The top screw secures the hood to the access panel.
The remaining two side screws must be installed after the
access panel is installed on the unit. These screws engage the
bottom flue box flange.

CAUTION: All three screws in the vent hood must be properly

installed before furnace operation to insure all com-
bustion products are exhausted from the unit.

OPTIONAL ECONOMIZER RAIN HOOD

The following procedure should be used when assembling an
economizer rain hood onto a unit. Refer to Figure 6. The
outdoor and return air dampers, damper actuator, the linkage
and all the controls are factory mounted as part of the
economizer option.

All of the hood components, including the filters, the gasketing
and the hardware for assembling are located above the top filter
racks within the filter section. The outdoor air sensor is in the
bag of parts located at the bottom of the return air section.

1. With filter section access panel removed, take out hood

components, filters and sensor described above. Remove
and discard outdoor air opening cover on back unit (Upper
right hand corner).

2. Remove the 1/2" knockout (A) in the units rear panel

(located to the right side of the outdoor air opening). Insert
the two loose wires from inside the unit, into the 1/2"
bushing provided. Insert wires and bushing into knockout.
Snap bushing into place.

3. Mount the outdoor air sensor to the rear panel, just below

the knockout described in Step 2. Secure with two
self-drilling screws at dimples (B) provided in the panel.

NOTE: Sensor must be positioned so that the sensing ports

are at the top (louvers pointing downward) and terminal
connections to the right.

4. Connect the two wires, indicated in Step 2, to the sensor

as follows:

Wire #73 to terminal (+)

Wire #74 to terminal (S)

5. Assemble the LH and RH side plates to the top cover (2

screws each side) to form the hood. Apply gasketing to the
flange surface on each side plate. Extend gasketing 1/4"
beyond top and bottom of each flange to insure adequate
corner sealing. Secure this assembly to the unit back panel
(upper right hand corner). First, remove screw (C) on unit
top cover. Then slip flange of hood cover in under flange of
unit top cover, replace screw (C), engaging hole (E) in hood
flange and tighten. Attach the two side plates to the unit
panel by using two self-drilling screws for each side plate
at dimples (D) provided in the panel.

6. Position fillpiece at bottom of hood, between the two side

plates but do not secure at this time. (Slotted openings MUST
be downward for drainage). After fillpiece is properly posi-
tioned, note where contact is made with the unit panel. Re-
move fillpiece and apply gasket material to this area to provide
a seal. Reposition fillpiece and secure with 2 screws.

7. Install the two filters into the hood assembly, sliding down

along retainers on side plates, into fillpiece at bottom of
hood.

FIG. 5 - VENT AND COMBUSTION AIR HOODS

B

GASKET

C

HOOD
COVER

OUTDOOR AIR
SENSOR

A

FILTER SECTION
ACCESS PANEL

D

GASKETED
FLANGE

R. H.
SIDE
PLATE

D

E

D

D

GASKETED
FLANGE

FILTER
COVER

L. H. SIDE
PLATE

FILTERS

FILLPIECE

OUTDOOR AIR
OPENING COVER

SIDE DUCT

APPLICATION SHOWN

FIG. 6 - ECONOMIZER RAIN HOOD ASSEMBLY (OPTION)

530.18-N8Y

Unitary Products Group

7

Summary of Contents for SUNLINE 2000 D2CG 072

Page 1: ...P O Box 1592 York PA 17405 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in the U S A on wood flooring or Class A B or C roof covering material 4 For use with natural gas and or propane LP gas Not suitable for use with conventional venting systems ...

Page 2: ... 5 Physical Data 9 6 Supply Air Blower Perf 3 6 Ton Direct Drive 9 7 Motor Drive Data Belt Drive Blower 9 8 Supply Air Blower Perf 3 4 Ton Belt Drive 10 9 Supply Air Blower Perf 5 6 Ton Belt Drive 11 10 Electrical Data Direct Drive 12 11 Electrical Data Belt Drive 12 12 Superheat 036 12 13 Superheat 048 13 14 Superheat 060 13 15 Superheat 072 13 16 Limit Control Setting 16 17 Belt Drive Supply Air...

Page 3: ...mulation in your area RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS...

Page 4: ...he internal wiring harness furnished with this unit is an integral part of a UL and CGA design certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced repla...

Page 5: ...RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE SCROLL COMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER ON A SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH04701024 COOLING HEATING 24 VOLT THERMOSTAT COOLING HEATING 24 VOLT ELECTRONIC THERMOSTAT 24 VOLT TRANSFORMER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 ADD JUMPER...

Page 6: ...FLAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equa...

Page 7: ...nd corner 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B p...

Page 8: ...ing carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R to G energized turn the minimum position screw counterclockwise until the desired minimum position has been attained 11 Replace the filter section access panel FIG 7 ENTHALPY SET POINT ADJUSTMENT EXTERNAL STATIC PRESSURE DROP DESCRIPTION RESISTANCE IWG CFM 100...

Page 9: ...ZE MOTOR SPEED Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts 036 HI MED LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 57...

Page 10: ...RS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 048 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920...

Page 11: ...ure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090...

Page 12: ...3 504 630 28 9 16 0 8 0 6 4 165 0 125 0 67 0 50 0 1 3 1 3 0 8 0 8 8 6 6 0 3 0 2 4 46 0 27 3 13 8 11 2 70 40 20 15 70 40 20 072 208 230 3 60 460 3 60 575 3 60 187 414 518 253 504 630 20 3 10 2 8 2 146 0 73 0 58 4 1 3 0 8 0 8 7 3 3 7 2 8 34 0 17 3 13 9 50 25 20 50 25 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 11 ELECTRICAL DATA BASIC UNIT w B...

Page 13: ... 32 3 33 4 75 13 7 15 9 18 1 20 3 22 5 24 7 26 9 28 1 29 3 30 5 31 8 80 10 4 12 8 15 1 17 4 19 8 22 1 24 5 25 9 27 3 28 7 30 2 85 7 2 9 7 12 2 14 6 17 1 19 6 22 0 23 7 25 3 27 0 28 6 90 6 6 8 9 11 3 13 6 16 0 18 3 20 6 22 8 25 0 27 3 95 5 7 7 9 10 1 12 4 14 6 17 4 20 3 23 1 25 9 100 6 5 8 2 9 9 11 6 14 6 17 6 20 6 23 6 105 5 1 6 3 7 4 8 6 11 8 15 0 18 1 21 3 110 5 6 9 0 12 3 15 7 19 0 115 6 1 9 7 ...

Page 14: ...le material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculate Locate unit so that the vent air outlet hood is at least Three 3 feet above any forced air inlet located within 10 horizontal feet excluding those integral to the unit Four 4 feet below 4 horizontal feet from or 1 foot a...

Page 15: ...DMC is energized The DMR or DMC power contacts close which energizes the line voltage draft motor As the speed of the draft motor reaches approximately 2500 RPM the centrifugal switch contact CS located on the end of the draft motor shaft closes to power the ignition control IC After 15 seconds the IC will start the ignitor sparking and will open the redundant valve located inside the main gas val...

Page 16: ...ut Output 3 4 3 4 5 5 6 6 50 75 100 125 100 125 100 125 40 60 79 99 79 99 79 99 165 165 165 165 165 165 165 165 TABLE 16 LIMIT CONTROL SETTING Gas Valve Anticipator Setpoint Honeywell VR8204M 0 60 amp White Rodgers 36E36 0 54 amp START UP OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an intermittent pilot and automatic re ignition system DO NOT attempt to manually light the pilot TO...

Page 17: ...r Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the holes located on the filter access...

Page 18: ...he permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it varies widely from city to city SECURE OWNER S APPROVAL When the system is functioning properly secure th...

Page 19: ... Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent tube from the flue collector end 9 If soot build up is particularly bad remove the vent motor and clean the wheel and housing Run the wire brush down the flue extentions at the outlet of the vent housing 10 After brushing is complete blow all brushed areas with air or nitrogen Vacuum as needed 1...

Page 20: ...it is within the proper limits as described in the POST START CHECK LIST and that the pilot adjust screw is allowing some flow of gas as described in PILOT CHECKOUT b Checkallwiringbetweentheignitorcontrolandthegasvalve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and COMMON on the ignitor control If 24 volts is not present r...

Reviews: