background image

evaporator coil may vary greatly, measuring the pressure
drop across a wet coil under field conditions would be
inaccurate. To assure a dry coil, the scroll compressors
should be de-energized while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual CFM

through the unit can be determined from the curve in Figure 15.

The temperature rise (or temperature difference between the return
air and the heated air from the furnace) must lie within the range
shown on the UL or CGA rating plate and the data in Table 2.

If the CFM is above or below the specified value, the supply air
motor speed may have to be changed by moving the motor
speed tap to another terminal.

WARNING: Failure to properly adjust the total system air quan-

tity can result in poor system performance.

5. After readings have been obtained, remove the tubes and

seal the holes with the 

5

16

" dot plugs removed in Step 1.

NOTE: DE-ENERGIZE THE SCROLL COMPRESSORS BE-

FORE TAKING ANY TEST MEASUREMENTS TO
ASSURE A DRY INDOOR COIL.

CHECKING GAS INPUT

NATURAL GAS

1. Turn off all other gas appliances connected to the gas meter.

2. With the furnace turned on, measure the time needed for one

revolution of the hand on the smallest dial on the meter. A
typical gas meter usually has a 1/2 or a 1 cubic foot test dial.

3. Using the number of seconds for each revolution and the

size of the test dial increment, find the cubic feet of gas
consumed per hour from Table 18.

If the actual input is not within 5% of the furnace rating (with
allowance being made for the permissible range of the regulator
setting) replace the orifice spuds with spuds of the proper size.

NOTE To find the Btu input, multiply the number of cubic feet of

gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)

SECURE OWNER’S APPROVAL

When the system is functioning properly, secure the owner’s approval. Show him the

location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature
settings within the limitations of the system.

 CFM 

=

 

Btuh Input x 0.8

1.08 x 

o

F Temp. Rise

 FIG. 15 PRESSURE DROP vs SUPPLY AIR CFM

Seconds

for One

Rev.

Size of Test Dial

1/2 cu. ft.

1 cu. ft.

10
12
14
16
18

180
150
129
113
100

360
300
257
225
200

20
22
24
26
28

90
82
75
69
64

180
164
150
138
129

30
32
34
36
38

60
56
53
50
47

120
113
106
100

95

40
42
44
46
48

45
43
41
39
37

90
86
82
78
75

50
52
54
56
58
60

36
35
34
32
31
30

72
69
67
64
62
60

Example:  By actual measurement, it takes 38 seconds for the hand on the 1-cubic
foot dial to make a revolution with just a 100,000 Btuh furnace running. Using this
information, locate 38 seconds in the first column in the table above. Read across
to the column headed “1 Cubic Foot”, where you will see that 95 cubic feet of gas
per hour are consumed by the furnace at that rate. Multiply 95 x 1050 (the Btu
rating of the gas obtained from the local gas company). The result is 99,750 Btuh,
which is close to the 100,000 Btuh rating of the furnace.

TABLE 18 - GAS RATE - CUBIC FEET PER HOUR

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

750

1250

1750

2250

2750

3250

3750

036

048

072

NOMINAL CFM

P

R

ES

SURE

 DROP

 (

IWG)

060

530.18-N8Y

18

Unitary Products Group

Summary of Contents for SUNLINE 2000 D2CG 072

Page 1: ...P O Box 1592 York PA 17405 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in the U S A on wood flooring or Class A B or C roof covering material 4 For use with natural gas and or propane LP gas Not suitable for use with conventional venting systems ...

Page 2: ... 5 Physical Data 9 6 Supply Air Blower Perf 3 6 Ton Direct Drive 9 7 Motor Drive Data Belt Drive Blower 9 8 Supply Air Blower Perf 3 4 Ton Belt Drive 10 9 Supply Air Blower Perf 5 6 Ton Belt Drive 11 10 Electrical Data Direct Drive 12 11 Electrical Data Belt Drive 12 12 Superheat 036 12 13 Superheat 048 13 14 Superheat 060 13 15 Superheat 072 13 16 Limit Control Setting 16 17 Belt Drive Supply Air...

Page 3: ...mulation in your area RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS...

Page 4: ...he internal wiring harness furnished with this unit is an integral part of a UL and CGA design certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced repla...

Page 5: ...RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE SCROLL COMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER ON A SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH04701024 COOLING HEATING 24 VOLT THERMOSTAT COOLING HEATING 24 VOLT ELECTRONIC THERMOSTAT 24 VOLT TRANSFORMER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 ADD JUMPER...

Page 6: ...FLAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equa...

Page 7: ...nd corner 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B p...

Page 8: ...ing carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R to G energized turn the minimum position screw counterclockwise until the desired minimum position has been attained 11 Replace the filter section access panel FIG 7 ENTHALPY SET POINT ADJUSTMENT EXTERNAL STATIC PRESSURE DROP DESCRIPTION RESISTANCE IWG CFM 100...

Page 9: ...ZE MOTOR SPEED Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts 036 HI MED LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 57...

Page 10: ...RS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 048 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920...

Page 11: ...ure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090...

Page 12: ...3 504 630 28 9 16 0 8 0 6 4 165 0 125 0 67 0 50 0 1 3 1 3 0 8 0 8 8 6 6 0 3 0 2 4 46 0 27 3 13 8 11 2 70 40 20 15 70 40 20 072 208 230 3 60 460 3 60 575 3 60 187 414 518 253 504 630 20 3 10 2 8 2 146 0 73 0 58 4 1 3 0 8 0 8 7 3 3 7 2 8 34 0 17 3 13 9 50 25 20 50 25 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 11 ELECTRICAL DATA BASIC UNIT w B...

Page 13: ... 32 3 33 4 75 13 7 15 9 18 1 20 3 22 5 24 7 26 9 28 1 29 3 30 5 31 8 80 10 4 12 8 15 1 17 4 19 8 22 1 24 5 25 9 27 3 28 7 30 2 85 7 2 9 7 12 2 14 6 17 1 19 6 22 0 23 7 25 3 27 0 28 6 90 6 6 8 9 11 3 13 6 16 0 18 3 20 6 22 8 25 0 27 3 95 5 7 7 9 10 1 12 4 14 6 17 4 20 3 23 1 25 9 100 6 5 8 2 9 9 11 6 14 6 17 6 20 6 23 6 105 5 1 6 3 7 4 8 6 11 8 15 0 18 1 21 3 110 5 6 9 0 12 3 15 7 19 0 115 6 1 9 7 ...

Page 14: ...le material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculate Locate unit so that the vent air outlet hood is at least Three 3 feet above any forced air inlet located within 10 horizontal feet excluding those integral to the unit Four 4 feet below 4 horizontal feet from or 1 foot a...

Page 15: ...DMC is energized The DMR or DMC power contacts close which energizes the line voltage draft motor As the speed of the draft motor reaches approximately 2500 RPM the centrifugal switch contact CS located on the end of the draft motor shaft closes to power the ignition control IC After 15 seconds the IC will start the ignitor sparking and will open the redundant valve located inside the main gas val...

Page 16: ...ut Output 3 4 3 4 5 5 6 6 50 75 100 125 100 125 100 125 40 60 79 99 79 99 79 99 165 165 165 165 165 165 165 165 TABLE 16 LIMIT CONTROL SETTING Gas Valve Anticipator Setpoint Honeywell VR8204M 0 60 amp White Rodgers 36E36 0 54 amp START UP OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an intermittent pilot and automatic re ignition system DO NOT attempt to manually light the pilot TO...

Page 17: ...r Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the holes located on the filter access...

Page 18: ...he permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it varies widely from city to city SECURE OWNER S APPROVAL When the system is functioning properly secure th...

Page 19: ... Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent tube from the flue collector end 9 If soot build up is particularly bad remove the vent motor and clean the wheel and housing Run the wire brush down the flue extentions at the outlet of the vent housing 10 After brushing is complete blow all brushed areas with air or nitrogen Vacuum as needed 1...

Page 20: ...it is within the proper limits as described in the POST START CHECK LIST and that the pilot adjust screw is allowing some flow of gas as described in PILOT CHECKOUT b Checkallwiringbetweentheignitorcontrolandthegasvalve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and COMMON on the ignitor control If 24 volts is not present r...

Reviews: