background image

HEAT ANTICIPATOR SETPOINT

It is important that the anticipator setpoint be correct. Too high a
setting results in longer heat cycles and a greater temperature
swing in the conditioned space. Reducing the value below the
correct setpoint causes shorter “ON” cycles and may result in
the lowering of the temperature within the conditioned space.
Refer to Table 9 for the required heat anticipator setting.

CHECKING SUPPLY AIRFLOW

The RPM of the supply air blower will depend on the required
airflow, the unit accessories and the static resistances of both
the supply and the return air duct systems. With this
information, the RPM for the supply air blower and the motor
pulley adjustment (turns open) can be determined from the
blower performance data in Table 4.

Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 10.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The
variable pitch pulley on the blower motor can be adjusted to
obtain the desired supply air flow.

Note the following:

1. The supply airflow must be within the limitations shown in

Table 1.

2. Pulleys can be adjusted in half turn increments.

3. The tension on the belt should be adjusted as shown in

Figure 8.

Start the supply air blower motor. Adjust the resistances in both
the supply and the return air duct systems to balance the air

distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.

To check the supply airflow after the initial balancing has been
completed:

1. Remove the two dot plugs from the blower motor and the fil-

ter access panels shown in Figure 7.

2. Insert at least 200mm (8") of tubing (approximately 6mm

(1/4") diameter) into each of these holes for sufficient pene-
tration into the air flow on both sides of the indoor coil.

NOTE: The tubes must be inserted and held in a position

perpendicular to the air flow so that velocity pres-
sure will not affect the static pressure readings.

3. Using an inclined manometer, determine the pressure drop

across a dry indoor coil. Since the moisture on an indoor
coil may vary greatly, measuring the pressure drop across
a wet coil under field conditions would be inaccurate. To en-
sure a dry coil, the compressors should be de-energized
while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual air

flow through the unit and clean filters, can be determined
from the curve in Figure 9.

WARNING: Failure to properly adjust the total system air quan-

tity can result in extensive blower damage.

After readings have been obtained, remove the tubes and
reinstall the two dot plugs that were removed in Step 1.

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE

TAKING ANY TEST MEASUREMENTS TO ENSURE
A DRY INDOOR COIL.

035-18895-000-A-0902

Unitary Products Group

13

HEATER

kW

SETTING, AMPS

TH1

TH2

18

0.29

-

36

0.29

0.29

54

0.29

0.29

72

0.29

0.29

TABLE 9 - HEAT ANTICIPATOR SETTING

TURNS

OPEN*

BLOWER DRIVE RANGE (RPM)

180 UNIT

6

845

5

885

4

925

3

960

2

1000

1

1040

*Pulleys can be adjusted in half-turn increments.

Do NOT close pulley below 1 turn open.

TABLE 10 - SUPPLY AIR BLOWER MOTOR PULLEY

ADJUSTMENT

NOMINAL CFM (THOUSANDS) SUPPLY AIR

4

5

6

7

8

9

10

0.65

0.55

0.45

0.35

0.25

180 MBH

P

R

E

S

S

U

R

E

 D

R

O

P

 (

iw

g

)

1.61

1.36

1.12

81

 62

P

R

E

S

S

U

R

E

 D

R

O

P

 (

P

a

)

m

3

/s SUPPLY AIR

1.9

2.4

2.8

3.3

3.8

4.2

4.7

FIG. 9 - PRESSURE DROP ACROSS A DRY INDOOR

COIL VS SUPPLY AIRFLOW

FIG. 8 - BELT ADJUSTMENT

Summary of Contents for SUNLINE 2000 B2CH180

Page 1: ...esign installation operation and service of this equipment is available in the following reference documents 55 70 N7 General Installation 55 70 N2 Pre start Post start Check List 44 320 10 Barometric...

Page 2: ...4 Supply Air Blower Performance 10 5 Static Resistances 11 6 Blower Motor and Drive Data 11 7 Electrical Data Basic Units 11 8 Electrical Data Units w Elec Heat 11 9 Heat Anticipator Setpoints 13 10 B...

Page 3: ...ST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUST BE A...

Page 4: ...ccess panel per the instructions above to en sure moisture is not drawn into the unit during op eration The covering over the mounting holes only need be removed Do not remove the opening cover CONDEN...

Page 5: ...ired with a separate branch circuit fed directly from the meter panel and properly fused CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST BE USE...

Page 6: ...ENTHALPY SETPOINT ADJUSTMENT Remove the economizer access panel from the unit to check the following adjustments Loosen but do not remove the two panel latches CAUTION Extreme care must be exercised...

Page 7: ...15 FAN MOTOR kW HP 3 0 4 INDOOR COIL ROWS DEEP 4 FINS PER INCH 13 FACE AREA m2 Ft 2 1 45 15 5 OUTDOOR FANS Two Per Unit PROPELLER DIA mm in 762 30 ea FAN MOTOR kW HP 0 7 1 ea NOMINAL AIRFLOW m3 s 2 8...

Page 8: ...0 0 Above Unit 1829 72 With 914 36 Maximum Horizontal Overhang For Outdoor Air Discharge NOTE Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric hea...

Page 9: ...s 1 Remove and discard the side supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For downflow duct applications 1 Remove the side supply and return air duct...

Page 10: ...N AIRFLOW 3750 CFM 4380 CFM 5000 CFM 5630 CFM 6250 CFM ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW 845 6...

Page 11: ...FRAME SIZE EFF PITCH DIA mm in BORE mm in DESIG NATION PITCH DIA mm in BORE mm in DESIG NA TION PITCH LENGTH mm in DESIG NATION QTY 180 845 1040 3 0 4 0 184T 83 109 135 4 3 5 3 29 1 1 8 1VP56 188 7 4...

Page 12: ...nt supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambien...

Page 13: ...e the two dot plugs from the blower motor and the fil ter access panels shown in Figure 7 2 Insert at least 200mm 8 of tubing approximately 6mm 1 4 diameter into each of these holes for sufficient pen...

Page 14: ...defrost cycle even though the liquid sensor terminated defrost after three minutes During troubleshooting the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module...

Page 15: ...ccur if the bearings are overlubri cated Use grease sparingly WARNING Perform all maintenance operations on the blower motor with power disconnected from the unit Do not attempt to lubricate bearings...

Page 16: ...035 18895 000 A 0902 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2002 All Rights Reserved...

Reviews: