background image

insulated wires 1.0mm

2

(#18 AWG) should be used to connect

thermostat to unit. Eight conductors are required.

The subbase on the low voltage thermostat includes an
“Emergency Heat ” position on the system switch and a pilot
light. In the “Emergency Heat” position, the thermostat
provides electric resistance heat only. The compressors will not
run. The pilot light indicates that the switch is on “EM HT”. Nine
conductors are required for this application.

POWER AND CONTROL WIRING

Field wiring to the unit and electrical grounding of the unit must
conform to the applicable national, and local or municipal
codes. Voltage tolerances which must be maintained at the
compressor terminals during starting and running conditions
are indicated on the unit Rating Plate and Table 1.

The internal wiring harness furnished in this unit is an integral
part of the unit. Field alteration to comply with electrical codes
should not be required.

A fused disconnect switch should be field provided for the unit.
The switch must be separate from all other circuits. Refer to
Figure 7 for installation location. If any of the wire supplied with
the unit must be replaced, replacement wire must be of the type
shown on the wiring diagram. Refer to Table 7 for electrical
data.

Electrical line must be sized correctly to carry the load. USE
COPPER CONDUCTORS ONLY. Each unit must be wired
with a separate branch circuit fed directly from the meter panel
and properly fused.

CAUTION: When connecting electrical power and control wir-

ing to the unit, waterproof type connectors MUST

BE USED so that water or moisture cannot be
drawn into the unit during normal operation. The
above waterproofing conditions will also apply
when installing a field-supplied disconnect switch.

Refer to Figure 5 for typical field wiring and to the appropriate
unit wiring diagram for control circuit and power wiring
information.

OPTIONAL ELECTRIC HEATERS

The factory installed heaters are wired for single point power
supply. Power supply need only be brought into the single point
terminal block and thermostat wiring to the low voltage terminal
strip located in the upper portion of the unit control box.

035-18895-000-A-0902

Unitary Products Group

5

FIG. 5 - TYPICAL FIELD WIRING

Heater

Model

Minimum

Airflow

m

3

/s (CFM)

Output by Operation Mode and

Heat Stage

kW @ 400/415V*

Normal Operation

Emergency Heat

180

W1

W2

W1

W2

E018

2.12

(4500)

Mechanical 11.3/13.5 11.3/13.5

None

E036

2.12

(4500)

Mechanical 11.3/13.5 11.3/13.5 11.3/13.5

E054

2.36

(5000)

Mechanical 11.3/13.5 11.3/13.5 22.6/26.9

E072

2.36

(5000)

Mechanical 22.6/26.9 22.6/26.9 22.6/26.9

*Refer to Table 8 for total heater output kW for the respective heater.

TABLE 2 - ELECTRIC HEAT APPLICATION DATA

CONTACTOR

NEUTRAL

TERMINAL

BLOCK

GRD. 

LUG

NOTE: REFER TO ELECTRICAL DATA TABLES

TO SIZE THE WIRE, DISCONNECT SWITCH AND

OVERCURRENT PROTECTION.

FIELD-SUPPLIED

DISCONNECT

THREE

PHASE

POWER

SUPPLY

POWER WIRING

Summary of Contents for SUNLINE 2000 B2CH180

Page 1: ...esign installation operation and service of this equipment is available in the following reference documents 55 70 N7 General Installation 55 70 N2 Pre start Post start Check List 44 320 10 Barometric...

Page 2: ...4 Supply Air Blower Performance 10 5 Static Resistances 11 6 Blower Motor and Drive Data 11 7 Electrical Data Basic Units 11 8 Electrical Data Units w Elec Heat 11 9 Heat Anticipator Setpoints 13 10 B...

Page 3: ...ST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUST BE A...

Page 4: ...ccess panel per the instructions above to en sure moisture is not drawn into the unit during op eration The covering over the mounting holes only need be removed Do not remove the opening cover CONDEN...

Page 5: ...ired with a separate branch circuit fed directly from the meter panel and properly fused CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST BE USE...

Page 6: ...ENTHALPY SETPOINT ADJUSTMENT Remove the economizer access panel from the unit to check the following adjustments Loosen but do not remove the two panel latches CAUTION Extreme care must be exercised...

Page 7: ...15 FAN MOTOR kW HP 3 0 4 INDOOR COIL ROWS DEEP 4 FINS PER INCH 13 FACE AREA m2 Ft 2 1 45 15 5 OUTDOOR FANS Two Per Unit PROPELLER DIA mm in 762 30 ea FAN MOTOR kW HP 0 7 1 ea NOMINAL AIRFLOW m3 s 2 8...

Page 8: ...0 0 Above Unit 1829 72 With 914 36 Maximum Horizontal Overhang For Outdoor Air Discharge NOTE Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric hea...

Page 9: ...s 1 Remove and discard the side supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For downflow duct applications 1 Remove the side supply and return air duct...

Page 10: ...N AIRFLOW 3750 CFM 4380 CFM 5000 CFM 5630 CFM 6250 CFM ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW 845 6...

Page 11: ...FRAME SIZE EFF PITCH DIA mm in BORE mm in DESIG NATION PITCH DIA mm in BORE mm in DESIG NA TION PITCH LENGTH mm in DESIG NATION QTY 180 845 1040 3 0 4 0 184T 83 109 135 4 3 5 3 29 1 1 8 1VP56 188 7 4...

Page 12: ...nt supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambien...

Page 13: ...e the two dot plugs from the blower motor and the fil ter access panels shown in Figure 7 2 Insert at least 200mm 8 of tubing approximately 6mm 1 4 diameter into each of these holes for sufficient pen...

Page 14: ...defrost cycle even though the liquid sensor terminated defrost after three minutes During troubleshooting the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module...

Page 15: ...ccur if the bearings are overlubri cated Use grease sparingly WARNING Perform all maintenance operations on the blower motor with power disconnected from the unit Do not attempt to lubricate bearings...

Page 16: ...035 18895 000 A 0902 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2002 All Rights Reserved...

Reviews: