background image

LIMITATIONS

These units must be installed in accordance with applicable
national and local or municipal safety codes.

Refer to Table 1 for Unit Application Data and to Table 2 for
Electric Heat Application Data.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. Unit is designed for outdoor installation only.

2. Outdoor coils must have an unlimited supply of air.

3. For ground level installation, use a level concrete slab with

a minimum thickness of 102mm (4"). The length and width
should be at least 152mm (6") greater than the unit base
rails. Do not tie slab to the building foundation.

4. Roof structure must be able to support the weight of the unit

and its options and/or accessories. Unit must be installed
on a solid level roof curb or appropriate angle iron frame.

CAUTION: If a unit is to be installed on a roof curb or spe-

cial frame other than a YORK roof curb, gasket-
ing must be applied to all surfaces that come in
contact with the unit underside.

5. Maintain level tolerance to 13mm (1/2") maximum across

the entire length or width of the unit.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreaders, whose length exceeds
the largest dimension across the unit, MUST be used across
the top of the unit. Refer to Figure 1.

Units may also be moved or lifted with a forklift, from the front or
rear only, providing that an accessory skid is used.

LENGTH OF FORKS MUST BE A MINIMUM OF 2286mm
(90").

Refer to Table 3 for unit weights and to Figure 2 for approximate
center of gravity.

CLEARANCES

All units require certain clearances for correct operation and
service. Refer to the unit dimensions detail, Figure 7, for the
clearances required for combustible construction, servicing,
and unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct outdoor air discharge outlet.

DUCTWORK

A closed return duct system shall be used. This does not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.

The supply and return air duct systems should be designed for
the airflow and static requirements of the job. They should NOT
be sized to match the dimensions of the duct connections on
the unit.

CAUTION: When fastening ductwork to side duct flanges on

unit, insert screws through duct flanges only. DO
NOT insert screws through casing.

Outdoor ductwork must be insulated and water-
proofed.

Refer to Figure 7 for information concerning side and bottom
supply and return air duct openings.

035-18895-000-A-0902

Unitary Products Group

3

INSTALLATION

Voltage Variation (Min. / Max.)

400 / 415V

360 / 456V

Wet Bulb Temperature of Air on

Indoor Coil, (Min. / Max.)

°

C

14 / 22

°

F

57 / 72

Dry Bulb Temperature of Air on

Outdoor Coil, (Min./ Max.)

°

C

7 / 52

°

F

45 / 125

TABLE 1 - UNIT APPLICATION DATA

FIG. 1 - TYPICAL RIGGING

FIG. 2 - CENTER OF GRAVITY

2337
(92")

3181 (125-1/4") (180)

OUTDOOR COIL
END OF UNIT

1143
(45")

1524

(60")

Summary of Contents for SUNLINE 2000 B2CH180

Page 1: ...esign installation operation and service of this equipment is available in the following reference documents 55 70 N7 General Installation 55 70 N2 Pre start Post start Check List 44 320 10 Barometric...

Page 2: ...4 Supply Air Blower Performance 10 5 Static Resistances 11 6 Blower Motor and Drive Data 11 7 Electrical Data Basic Units 11 8 Electrical Data Units w Elec Heat 11 9 Heat Anticipator Setpoints 13 10 B...

Page 3: ...ST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUST BE A...

Page 4: ...ccess panel per the instructions above to en sure moisture is not drawn into the unit during op eration The covering over the mounting holes only need be removed Do not remove the opening cover CONDEN...

Page 5: ...ired with a separate branch circuit fed directly from the meter panel and properly fused CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST BE USE...

Page 6: ...ENTHALPY SETPOINT ADJUSTMENT Remove the economizer access panel from the unit to check the following adjustments Loosen but do not remove the two panel latches CAUTION Extreme care must be exercised...

Page 7: ...15 FAN MOTOR kW HP 3 0 4 INDOOR COIL ROWS DEEP 4 FINS PER INCH 13 FACE AREA m2 Ft 2 1 45 15 5 OUTDOOR FANS Two Per Unit PROPELLER DIA mm in 762 30 ea FAN MOTOR kW HP 0 7 1 ea NOMINAL AIRFLOW m3 s 2 8...

Page 8: ...0 0 Above Unit 1829 72 With 914 36 Maximum Horizontal Overhang For Outdoor Air Discharge NOTE Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric hea...

Page 9: ...s 1 Remove and discard the side supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For downflow duct applications 1 Remove the side supply and return air duct...

Page 10: ...N AIRFLOW 3750 CFM 4380 CFM 5000 CFM 5630 CFM 6250 CFM ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW 845 6...

Page 11: ...FRAME SIZE EFF PITCH DIA mm in BORE mm in DESIG NATION PITCH DIA mm in BORE mm in DESIG NA TION PITCH LENGTH mm in DESIG NATION QTY 180 845 1040 3 0 4 0 184T 83 109 135 4 3 5 3 29 1 1 8 1VP56 188 7 4...

Page 12: ...nt supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambien...

Page 13: ...e the two dot plugs from the blower motor and the fil ter access panels shown in Figure 7 2 Insert at least 200mm 8 of tubing approximately 6mm 1 4 diameter into each of these holes for sufficient pen...

Page 14: ...defrost cycle even though the liquid sensor terminated defrost after three minutes During troubleshooting the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module...

Page 15: ...ccur if the bearings are overlubri cated Use grease sparingly WARNING Perform all maintenance operations on the blower motor with power disconnected from the unit Do not attempt to lubricate bearings...

Page 16: ...035 18895 000 A 0902 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2002 All Rights Reserved...

Reviews: