![background image](http://html1.mh-extra.com/html/york/r-410f/r-410f_technical-manual-for-installation-and-maintenance_3522978026.webp)
546039-YTG-C-0211
26
Unitary Products Group
115°F
125°F
1000
77
33.7
3.7
16.4
10.6
7.4
-
-
-
31.7
4.1
17.3
9.0
6.6
-
-
-
72
29.4
3.7
20.8
16.5
12.3
8.0
-
-
26.8
4.0
19.7
15.5
11.3
7.1
-
-
67
25.1
3.6
25.1
22.5
17.2
13.0
8.7
-
22.0
4.0
22.0
22.0
16.0
11.8
7.6
-
62
23.5
3.6
23.5
23.5
18.2
13.9
9.7
5.4
21.6
4.0
21.6
21.6
16.3
12.1
8.0
3.8
1100
77
35.0
3.8
20.4
13.0
8.5
-
-
-
32.7
4.2
21.5
12.4
7.6
-
-
-
72
30.6
3.7
23.3
18.7
14.1
9.6
-
-
27.7
4.1
22.1
17.5
13.0
8.5
-
-
67
26.1
3.7
26.1
24.4
19.8
15.2
10.6
-
22.7
4.0
22.7
22.7
18.4
13.9
9.4
-
62
24.4
3.7
24.4
24.4
20.9
16.3
11.7
7.2
22.3
4.0
22.3
22.3
18.8
14.3
9.8
5.2
57
26.3
3.3
26.3
26.3
22.5
17.9
13.3
8.8
24.6
3.4
24.6
24.6
20.7
16.2
11.6
7.1
1200
77
36.3
3.9
24.3
15.5
9.6
-
-
-
33.8
4.2
25.6
15.9
8.6
-
-
-
72
31.7
3.8
25.7
20.8
16.0
11.1
-
-
28.6
4.2
24.5
19.6
14.7
9.9
-
-
67
27.1
3.8
27.1
26.2
22.3
17.5
12.6
-
23.4
4.1
23.4
23.4
20.8
16.0
11.1
-
62
25.4
3.7
25.4
25.4
23.6
18.7
13.8
8.9
23.1
4.1
23.1
23.1
21.3
16.4
11.5
6.7
57
27.3
3.3
27.3
27.3
25.4
20.5
15.6
10.7
25.4
3.4
25.4
25.4
23.4
18.5
13.7
8.8
1300
77
37.6
3.9
28.3
17.9
10.7
-
-
-
34.8
4.3
29.7
19.3
9.7
-
-
-
72
32.9
3.9
28.2
23.0
17.8
12.6
-
-
29.4
4.2
26.9
21.7
16.5
11.3
-
-
67
28.1
3.8
28.1
28.1
24.9
19.7
14.5
-
24.1
4.1
24.1
24.1
23.3
18.1
12.9
-
62
26.3
3.8
26.3
26.3
26.3
21.1
15.9
10.7
23.8
4.1
23.8
23.8
23.8
18.5
13.3
8.1
57
28.3
3.4
28.3
28.3
28.3
23.1
17.9
12.7
26.1
3.5
26.1
26.1
26.1
20.9
15.7
10.5
1350
72
32.9
3.9
28.7
23.3
17.9
12.5
-
-
29.5
4.3
27.5
22.0
16.6
11.2
-
-
67
28.1
3.9
28.1
28.1
25.1
19.7
14.3
-
24.1
4.2
24.1
24.1
23.5
18.1
12.7
-
62
26.3
3.9
26.3
26.3
26.3
20.9
15.5
10.0
23.8
4.2
23.8
23.8
23.8
18.4
12.9
7.5
57
28.3
3.4
28.3
28.3
28.3
22.9
17.5
12.0
26.2
3.6
26.2
26.2
26.2
20.7
15.3
9.9
1400
72
32.9
4.0
29.3
23.7
18.0
12.4
-
-
29.5
4.4
28.0
22.4
16.8
11.1
-
-
67
28.1
4.0
28.1
28.1
25.3
19.6
14.0
-
24.1
4.3
24.1
24.1
23.7
18.1
12.4
-
62
26.3
3.9
26.3
26.3
26.3
20.7
15.1
9.4
23.8
4.3
23.8
23.8
23.8
18.2
12.5
6.9
57
28.3
3.5
28.3
28.3
28.3
22.7
17.1
11.4
26.2
3.6
26.2
26.2
26.2
20.5
14.9
9.3
1. These capacities are Net capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
UQ036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65