546039-YTG-C-0211
38
Unitary Products Group
Electric Heat Minimum Supply Air
Size
(Tons)
Model
Voltage
Minimum Supply Air (CFM)
Heater kW
5.0
6.5
10
15
024
(2.0)
NM
208/230-1-60
800
800
800
775
030
(2.5)
NM
208/230-1-60
800
800
800
775
036
(3.0)
NM
208/230-1-60
800
800
800
775
042
(3.5)
NM
208/230-1-60
800
800
800
775
048
(4.0)
NM
208/230-1-60
1300
1300
1270
1160
060
(5.0)
NM
208/230-1-60
1300
1300
1270
1160
024
(2.0)
UQ
208/230-1-60
800
800
800
750
030
(2.5)
UQ
208/230-1-60
800
800
800
750
036
(3.0)
UQ
208/230-1-60
800
800
800
750
042
(3.5)
UQ
208/230-1-60
1300
1300
1270
1270
048
(4.0)
UQ
208/230-1-60
1300
1300
1270
1270
060
(5.0)
UQ
208/230-1-60
1300
1300
1270
1270
Indoor Blower Specifications
Size
(Tons)
Model
Motor
HP RPM Eff. SF
Frame
024
(2.0)
UM
1/2
1075
0.8
1.0
48
030
(2.5)
UM
1/2
1075
0.8
1.0
48
036
(3.0)
UM
1/2
1075
0.8
1.0
48
042
(3.5)
UM
1/2
1100
0.8
1.0
48
048
(4.0)
UM
1
1100
0.8
1.0
48
060
(5.0)
UM
1
1100
0.8
1.0
48
024
(2.0)
UQ
1/2
1100
0.8
1.0
48
030
(2.5)
UQ
1/2
1100
0.8
1.0
48
036
(3.0)
UQ
1/2
1100
0.8
1.0
48
042
(3.5)
UQ
1
1100
0.8
1.0
48
048
(4.0)
UQ
1
1100
0.8
1.0
48
060
(5.0)
UQ
1
1100
0.8
1.0
48
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Nominal
Applied
240
208
0.75
230
0.92