5167821-YTG-J-0518
Johnson Controls Ducted Systems
25
115°F
125°F
1250
77
63.5
5.4
32.6
27.3
21.9
-
-
-
56.7
6.1
30.5
24.9
19.2
-
-
-
72
57.9
5.3
41.4
34.9
28.3
21.8
-
-
53.0
5.9
39.3
32.6
25.9
19.3
-
-
67
52.3
5.2
50.1
42.4
34.7
28.3
21.8
-
49.4
5.8
48.0
40.3
32.6
26.1
19.5
-
62
50.2
5.1
49.0
45.1
41.1
34.7
28.2
21.8
46.8
5.7
45.5
42.4
39.4
32.9
26.5
20.0
1500
77
62.3
5.4
36.6
28.7
20.8
-
-
-
55.7
6.0
34.5
26.3
18.0
-
-
-
72
58.0
5.3
44.1
36.5
29.0
21.4
-
-
53.1
5.9
41.8
34.2
26.6
18.9
-
-
67
53.6
5.2
51.6
44.4
37.2
29.4
21.6
-
50.5
5.8
49.1
42.1
35.1
27.2
19.3
-
62
51.8
5.1
50.6
48.0
45.4
37.4
29.3
21.3
48.3
5.7
47.0
45.3
43.6
35.5
27.4
19.3
57
50.0
5.0
49.6
49.6
49.6
45.4
37.1
28.8
46.2
5.6
44.8
44.8
44.8
43.8
35.5
27.2
1750
77
61.2
5.3
40.5
30.0
19.6
-
-
-
54.7
5.9
38.6
27.7
16.9
-
-
-
72
58.1
5.2
46.8
38.2
29.6
21.0
-
-
53.2
5.8
44.4
35.8
27.2
18.5
-
-
67
54.9
5.2
53.2
46.4
39.6
30.5
21.4
-
51.5
5.7
50.2
43.8
37.5
28.3
19.1
-
62
53.4
5.1
52.3
51.0
49.7
40.0
30.4
20.8
49.8
5.7
48.5
48.1
47.8
38.1
28.4
18.6
57
51.9
5.1
51.3
51.3
51.3
49.6
39.4
29.3
48.0
5.6
46.7
46.7
46.7
46.7
37.6
27.3
2000
77
60.1
5.3
44.4
31.4
18.4
-
-
-
53.7
5.8
42.6
29.1
15.7
-
-
-
72
58.2
5.2
49.6
39.9
30.3
20.6
-
-
53.3
5.7
47.0
37.4
27.8
18.2
-
-
67
56.2
5.1
54.7
48.4
42.1
31.7
21.2
-
52.6
5.7
51.3
45.6
39.9
29.4
18.9
-
62
55.0
5.1
53.9
53.9
53.9
42.7
31.5
20.3
51.2
5.6
50.0
50.0
50.0
40.6
29.3
17.9
57
53.8
5.1
53.1
53.1
53.1
53.1
41.8
29.8
49.9
5.6
48.6
48.6
48.6
48.6
39.6
27.4
2250
72
58.3
5.2
52.3
41.6
30.9
20.2
-
-
53.3
5.7
49.5
38.9
28.4
17.8
-
-
67
57.5
5.1
56.2
50.4
44.5
32.8
21.1
-
53.7
5.6
52.4
47.4
42.3
30.5
18.7
-
62
56.6
5.1
55.5
55.5
55.5
45.4
32.6
19.8
52.7
5.6
51.5
51.5
51.5
43.2
30.2
17.2
57
55.7
5.1
54.8
54.8
54.8
54.8
44.1
30.3
51.8
5.6
50.5
50.5
50.5
50.5
41.7
27.5
2500
72
58.4
5.1
55.0
43.3
31.5
19.8
-
-
53.4
5.6
-
40.5
29.0
17.5
-
-
67
58.7
5.1
57.8
52.4
47.0
33.9
20.9
-
54.7
5.6
-
49.1
44.7
31.6
18.6
-
62
58.1
5.1
57.2
57.2
57.2
48.1
33.7
19.3
54.2
5.6
-
53.0
53.0
45.8
31.2
16.5
57
57.5
5.1
56.6
56.6
56.6
56.6
46.5
30.8
53.6
5.6
-
52.4
52.4
52.4
43.8
27.6
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT061 High Speed Compressor (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65