5167821-YTG-J-0518
Johnson Controls Ducted Systems
19
115°F
125°F
750
77
24.2
2.2
18.6
14.3
9.9
-
-
-
20.5
2.5
19.3
14.6
10.0
-
-
-
72
23.1
2.2
20.0
16.3
12.6
8.9
-
-
20.1
2.5
19.2
15.6
11.9
8.3
-
-
67
22.5
2.2
21.3
18.3
15.3
11.4
7.6
-
20.4
2.4
19.1
16.5
13.9
10.1
6.4
-
62
22.5
2.1
21.3
19.6
18.0
13.9
9.9
5.9
21.0
2.4
19.2
17.5
15.8
11.9
8.0
4.1
900
77
24.7
2.2
20.3
14.5
8.6
-
-
-
20.9
2.5
-
14.0
7.9
-
-
-
72
24.2
2.2
21.4
17.0
12.6
8.2
-
-
21.2
2.4
-
15.8
11.4
7.1
-
-
67
23.7
2.1
22.4
19.5
16.6
12.2
7.7
-
21.5
2.4
-
17.5
15.0
10.7
6.3
-
62
23.5
2.1
22.4
21.5
20.6
16.1
11.6
7.1
21.7
2.4
-
19.3
18.5
14.2
10.0
5.7
57
23.2
2.1
22.4
22.4
22.4
20.1
15.5
10.9
21.9
2.4
-
20.3
20.3
17.8
13.6
9.4
1050
77
25.2
2.2
22.1
14.6
7.2
-
-
-
21.3
2.4
21.1
13.5
5.8
-
-
-
72
25.3
2.1
22.8
17.7
12.6
7.4
-
-
22.3
2.4
21.1
16.0
10.9
5.8
-
-
67
25.0
2.1
23.6
20.8
17.9
12.9
7.8
-
22.7
2.4
21.1
18.6
16.0
11.2
6.3
-
62
24.4
2.1
23.6
23.4
23.3
18.3
13.3
8.3
22.4
2.4
21.2
21.2
21.1
16.5
11.9
7.3
57
23.9
2.1
23.6
23.6
23.6
23.2
17.7
12.2
22.1
2.4
21.3
21.3
21.3
21.1
15.9
10.7
1200
77
25.7
2.1
23.8
14.8
5.8
-
-
-
21.7
2.4
21.7
12.9
3.7
-
-
-
72
26.5
2.1
24.3
18.4
12.6
6.7
-
-
23.5
2.4
22.0
16.2
10.4
4.6
-
-
67
26.3
2.1
24.7
22.0
19.3
13.6
7.9
-
23.8
2.4
22.1
19.6
17.1
11.7
6.3
-
62
25.4
2.1
24.7
24.7
24.7
20.5
15.0
9.4
23.1
2.4
22.2
22.2
22.2
18.8
13.8
8.8
57
24.5
2.1
24.5
24.5
24.5
24.5
19.9
13.5
22.3
2.4
22.3
22.3
22.3
22.3
18.2
12.0
1350
72
27.6
2.1
25.7
19.1
12.5
6.0
-
-
24.6
2.4
23.0
16.5
9.9
3.4
-
-
67
27.5
2.1
25.9
23.2
20.6
14.3
8.0
-
24.9
2.4
23.1
20.6
18.2
12.2
6.3
-
62
26.3
2.1
25.9
25.9
25.9
22.7
16.6
10.6
23.7
2.4
23.2
23.2
23.2
21.1
15.8
10.4
57
25.1
2.1
25.1
25.1
25.1
25.1
22.1
14.8
22.5
2.4
22.5
22.5
22.5
22.5
20.5
13.3
1500
72
28.7
2.1
-
19.8
12.5
5.2
-
-
25.7
2.4
-
-
-
-
-
-
67
28.8
2.1
-
24.5
21.9
15.0
8.1
-
26.1
2.4
-
-
-
-
-
-
62
27.3
2.1
-
27.1
27.1
24.8
18.3
11.8
24.4
2.4
-
-
-
-
-
-
57
25.7
2.1
-
25.7
25.7
25.7
24.3
16.1
22.7
2.4
-
-
-
-
-
-
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT037 Low Speed Compressor (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65